17 A3-phase generator rated 3000 KVA, 20 kV, 900 r/min, 60 Hz delivers power to a 2400 KVA, 16 kV load having a lagging power factor of 0.8. If the synchronous reactance is 100 N, calculate the value of E, per phase.
Q: What are the values of Vc and Ve from the circuit shown below. +IDV 3.3 k2 B- 110 3.9 k2 0-12 V O a.…
A: As per company guidelines we are supposed to answer only one question. Kindly repost other questions…
Q: Discuss system demand and generator loading
A: System demand System demand management (SDM), also called as management control (DSM) or…
Q: Determine i(t) of the RLC circuit shown below when vs = 2 cos (4t + 30°)
A:
Q: The output for the following clamping circuit is shown below assuming ideal diode calculate the…
A:
Q: A certain digital circuits designed to operate with voltage levels of -0.2Vdc and -3.0Vdc. If H= 1…
A: It is given that:voltage levels:-0.2 Vdc and -3.0 Vdc
Q: Find the power dissipated by 1-ohm resistor. 10 2 6 V 12 iz 8 V O 1.42 W O 1.06 W O 26.37 mW O 62.73…
A:
Q: ca) Compute tne fourier toamsform of each of the follocsing signals. ci) xcn) = co25u[n-1] ci) Hgcn)…
A: As per our guidelines we are supposed to be answer the first question only. Kindly repost the other…
Q: 1. Explain briefly in one(1) sentence how do we maximize the value of the armature current in a…
A: (1) When the load gets added to shunt wound DC motor the speed gets reduced and along with the speed…
Q: 1. 10 Kr 20Kル と)05 2o nF a) Determine the transfer function His) 72。さ Us
A: Note: We are authorized to answer three subparts at a time, since you have not mentioned which part…
Q: Determine the limiting error for the equivalent resistance of the network. R1=(2+ 5%) KN, R2=(8+ 7%)…
A: The solution is given below
Q: 3. Write any three differences between FET and MOSFET
A: The differences between the FET and the MOSFET are listed in the tables shown below: FET MOSFET…
Q: 1. Calculate the total Capacitance in the given circuit below and how much charge provided by the…
A:
Q: What does the negative sign in the voltage gain of the common-emitter fixed-bias configuration indie…
A: Option a is correct
Q: A common base amplifier is referred as a O a. voltage amplifier b. emitter follower • c. current…
A:
Q: In the circuit of Fig. 2.75, calculate V¡ and V2. -구v + + 10 V V2
A: This problem is from kcl and kvl The solution is given below
Q: 12V R1 1ka R2 10kA Vin Q1: what is type of transistor ? Q2: Write down the load line equation. Vc =…
A: As per the guidelines of bartleyby I need to answer first three questions only.So kindly repost…
Q: In an RC circuit, ifR = 1 kn, c = 0.1 µ F, the time constant T will be: O A. 1 ms O B. 0.01 ms…
A: For an RC circuit, the time constant τ = R * C
Q: Table 1: The Resistors in Series V2 (V) 1.50 I2 (A) 0.075 Reg (2) Vtotal (V) Set- R1 (N) 20 R2 (2)…
A: Resistance- It is a property of a device called resistor which opposes the flow of current in the…
Q: Describe the importance of using Bandpass filter in ASK Modulator.
A: In this question we will write importance of bandpass filter in modulator ...
Q: Calculate the current required to produce a deflection of 100°, if the coil of a PMMC instrument has…
A: Given, Deflection angle, θ=100° Number of turns N=60 turns Area, A = W×L=18×10-3×25×10-3=450×10-6 m2…
Q: 5. The input waveforms applied to a 3-input AND gate are as indicated in Figure 3–78. Show the…
A: Note: We are authorized to answer one question at a time, since you have not mentioned which…
Q: Region 0 2. as shown in (iii) z
A: It is given that: μ=2.5μo for 0≤z≤2
Q: Solve for line currents. IaA, IbB, IcC.
A:
Q: Q3 Solve the system of the linear equation below by the Gauss elimination method. -2x2 + 8x3 = 5ld…
A:
Q: Determine the polar and rectangular form of the expression.
A:
Q: emperature coetticient of resistance of the conductor at 0°C? 0.00750 c. 0.00936 . 0.00625 d. 0.0208
A: Temperature coefficient of any resistive material is defined as the change of the value of…
Q: ransfer function GH () = K(8) The system is stable when: O3<K<9 0<K<3 0<K<5
A: Given, Open loop transfer function, GHs=Ks+5ss+1s+2; K>0
Q: What are the values of Vc and Ve from the circuit shown below. +IDV 3.3 kf2 B- 110 3.9 k2 O-12 V O…
A: As per our company guidelines we are supposed to answer only first question kindly repost the other…
Q: Describe the importance of using LPF filter in ASK Demodulator
A: In this question we will write about importance of using LPF filter in ASK Demodulator.....
Q: Q2 A 3-phase, 690 V, star-connected, 50 Hz, 6-pole induction machine has phase-equivalent circuit…
A: “Since you have posted a question with multiple sub-parts, we will solve the first three sub-parts…
Q: A 220V short-shunt compound generator has armature resistance, series field resistance and shunt…
A:
Q: series RLC circuit has the following component values: R = variable, L = 100 mH, and C= 0.1 uF. If R…
A:
Q: 2-6 Find the currents through meters A and B in the circuit of Fig. 2-31. R = 10 kn Rm = 2 kn A =…
A: “Since you have asked multiple questions, we will solve the first question for you. If you want any…
Q: For R1=8, R2=1, R3=5, R4=5, R5=2, V1=9 V and V2=1 V in the shown circuit, apply mesh analysis to…
A:
Q: A spherical capacitor with a = 1.5 cm, b 4 cm has an inhomogeneous dielectric of ɛ 10ɛJr. Calculate…
A:
Q: 5. Simplify F(A,B,C,D) = E m (0,2,4, 5, 7, 8, 10, 13, 15) and don't care = d (1, 9) in SOP using…
A: As per our company guidelines we are supposed to answer only first question kindly repost the other…
Q: 2. Obtain the simplified Boolean expressions for output F and G in terms of the input variables in…
A: Re-draw the given logic diagram Fig: Modified logic…
Q: Q1- A universal motor with 120V,50 Hz,2 poles. runs at speed 7000 rpm and draws full load current…
A: The solution is given below
Q: Define the parts and functions of AC Generator - Define the working principle of AC Generator. -…
A: AC Generator A machine that converts mechanical energy to electrical energy is called AC generator.…
Q: "Resistors in Series and Parallel" PART1: The Resistors in Series Objective: To analyze the…
A:
Q: Determine the net receiver gain for an AM receiver with the following gains and losses: Gains: RF…
A: Given that, Gain RF amplifier = 33 dB IF amplifier =44 dB audio amplifier = 22 dB Loss Preselector…
Q: Sketch v, for the network of the figure below for the input shown. Show the details of your work. c1…
A:
Q: What will be the voltage of point A with respect to B? 50 ww A 15 V- 10 0: 6 A ww B.
A: Given circuit,
Q: What would happen if you reversed the Tachogenerator connections to the Operational Amplifier and…
A: Tachogenerator is define as an electromechanical device which helps to measure the speed and…
Q: Find the capacitor size that wiIl make the light stay on for 10 sec after power is removed switch is…
A: The solution is given below
Q: For R1=15, R2=9, R3=9, R4=9, R5=D2, R6=18, V1=165 V, V2=72 V and V3=11 V in the shown circuit, use…
A: Fig: Given circuit
Q: If in an RC circuit, the capacitance is increased by 25% and the resistance, R, is decreased by 10%,…
A:
Q: QUESTION 3 Find the magnitude of the phase voltage of a wye-delta system that has a balanced load of…
A: This problem is from star delta system of load the answer is option d
Q: Find the power dissipated by 1-ohm resistor. 10Ω ww 6 V 22 ww +-> 12 4Ω 50 8 V O 1.42 W O 1.06 W O…
A: Given:
Q: TUTORIAL PROBLEMS 1. A3 phase overhead transmission line has a total series impedance per phase of…
A: In this question we will find sending end line voltage and current for given transmission line...
Number 17
Step by step
Solved in 2 steps with 1 images
- With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a generator, a step-up transformer bank, a transmission line, a stepown transformer bank, and an impedan load. The generator terminal voltage is 15 kV (line-to-line). (a) Draw the per-phase equivalent circuit, aounting for phase shifts for positive-sequence operation. (b) By choosing the line-to-neutral generator terminal voltage as the reference, determine the magnitudes of the generator current, transmiss ion-line current, load current, and line-to-line load voltage. Also, find the three-phase complex power delivered to the load.Question 3. A three-phase impedance load balanced D a connected load in parallel with a balanced ? connected load made of bonding. D each arm for the load ?D = 6 + 6? and ? each arm for the connected load It is given as ?? = 2 + 2?. ? the connected load ?? = 1? is earthed through the neutral impedance. To this impedance load, the symmetrical component voltages ?0 = 10∠60°, ?1 = 100∠0° and ?2 = Unbalanced phase-to-earth voltages ??, ?? and ?? of 15∠200° volts were applied. a) Draw the zero, positive and negative sequence circuits. b) Find the complex powers imparted to each component circuit.Three zones of a single-phase circuit are identified in the figure with a generator voltage specification of 240 V. The zones are connected by the transformers T1 and T2, whose ratings are shown below.Using base values of 30 kVA and 240 volts in zone 1, draw the pu circuit and determine the pu impedance and pu source voltage. Then calculate the load current in pu and in amperes.*Round the final answer to four decimal places, polar form, and label it with the correct units.
- Sketch the complete per-phase equivalent circuit of a symmetrical non-salient pole three-phase synchronous generator, including the field winding circuit. Your figure should include the synchronous reactance Xs, explain its relation to Xar and Xl. In addition, explain/describe the rest of the different elements of this equivalent circuit.The one-line diagram of a simple power system is shown in Figure 9.20. Each generator is represented by an an emf behind the transient reactance. All impedances are expressed in per unit on a common MVA base. All resistance and shunt capacitances are neglected. The generation are operating on no load at their rated voltage with their emfs in phase. A three-phase fault occurs at bus 1 through a fault impedance of Z_f = j0.08 per unit. Using Thevenin's theorem obtain the impedance to the point of fault and the fault current in per unit. Determine the bus voltages and line currents during fault.3. Which one of the following method uses weak coupling between reactive power and voltage angle?. A. Newton - Raphson Method B. Decoupled Method C. Gauss-Seidal Method
- A (500 MW) generator is delivering (180 MW) to infinite bus through the unit transformer and double transmission lines. The per-unit ractances for a given system are shown in figure below andall the reactances are based on (100 MW) base. The generator emf is ( 1.35p .u.). Determine whether the system remains stable after one circuit of the lines is switch off?Three single-phase two-winding transformers, each rated 400 MVA, 13.8/ 199.2 kV, with leakagereactance Xeq = 0.10 per unit, are connected to form a three-phase bank. Winding resistances andexciting current are neglected. The high-voltage windings are connected in Y. A three-phase loadoperating under balanced positive-sequence conditions on the high-voltage side absorbs 1000 MVA at0.90 p.f. lagging, with VAN = 199.2 ∠00 kV. Determine the voltage Van at the low-voltage bus if the lowvoltage windings are connecteda) in Y,b)A three phase synchronous generator with negligible resistance and Xs=20 ohm has induced voltage as well as terminal voltage per phase equal to 230 V. for the load angle of 30o, power received by the bus is .........W.
- Draw an impedance diagram for the electric power system shown in the figure attached, showing all impedances in per unit on a 100-MVA base. Choose 20kV as the voltage base for generator. The three-phase power and line-line ratings are given in the figure attached.A balanced, star connected three-phase system is directly connected to an unbalanced load, with a solid neutral connection. The line-to-neutral voltage Van on the load side and per phase load impedances (i.e., Za, Zb and Zc) are as below: ?an = 240∠0 ? ?? = 10 + 3? Ω ?? = 16 + 3? Ω ?? = 10 + 3?Ω Draw the circuit diagram and calculate the sequence currents and neutral currentL-type equivalent circuit and parameters for a continuous sinusoidal phase of a 5.5 kW, 1460 rpm, line voltage 220 V and frequency 50 Hz star-connected 3-phase ASM, ignoring core (iron) losses given as follows: R1=0.21 Ohm, R2=0.18 Ohm, X1=X2=0.66 Ohm and Xm=9.9 Ohm How many times the inrush current will be the rated current when the ASM is started directly? Answer options group 3.7473 5.2280 8.0815 7.1534 1.2558 4.3763 2.6455 6.3414