17 A3-phase generator rated 3000 KVA, 20 kV, 900 r/min, 60 Hz delivers power to a 2400 KVA, 16 kV load having a lagging power factor of 0.8. If the synchronous reactance is 100 N, calculate the value of E, per phase.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.48P: With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a...
icon
Related questions
Question

Number 17

NCHRONOUS GENERATORS
383
kept
Calculate
age and
a. The synchronous impedance Z, per phase
b. The total resistance of the circuit, per
phase
c. The total reactance of the circuit, per
phase
d. The line current
reac-
lo sgs e. The line-to-neutral voltage across the
w the
load
d ex-
f. The line voltage across the load
g. The power of the turbine driving the
alternator
eters.
xcitation
s. Using
h. The phase angle between E, and the
voltage across the load
how the
17
A 3-phase generator rated 3000 KVA, 20 kV,
900 r/min, 60 Hz delivers power to a 2400
KVA, 16 kV load having a lagging power
factor of 0.8. If the synchronous reactance is
100 N, calculate the value of E, per phase.
exciting
ad line
cO,
The generator in Fig. 2 has a synchronous
reactance of 0.4 2, per phase. It is con-
nected to an infinite bus having a line volt-
age of 14 kV, and the excitation voltage is
18
chro-
ation
g. 19).
E for a
age
adjusted to 1.14 pu.
hasor
Calculate
1S KA
a. The torque angle § when the generator
delivers 420 MW
of E
b. The mechanical displacement angle a
c. The linear pole shift (measured along
the inside stator circumference)
ive
nms.
er phase
corresponding to this displacement
angle [in]
For what
19 A test taken on the 500 MVA alternator of
Fig. 2 yields the following results:
Onen-circuit line voltage is 15 kV for a
Power
14
Transcribed Image Text:NCHRONOUS GENERATORS 383 kept Calculate age and a. The synchronous impedance Z, per phase b. The total resistance of the circuit, per phase c. The total reactance of the circuit, per phase d. The line current reac- lo sgs e. The line-to-neutral voltage across the w the load d ex- f. The line voltage across the load g. The power of the turbine driving the alternator eters. xcitation s. Using h. The phase angle between E, and the voltage across the load how the 17 A 3-phase generator rated 3000 KVA, 20 kV, 900 r/min, 60 Hz delivers power to a 2400 KVA, 16 kV load having a lagging power factor of 0.8. If the synchronous reactance is 100 N, calculate the value of E, per phase. exciting ad line cO, The generator in Fig. 2 has a synchronous reactance of 0.4 2, per phase. It is con- nected to an infinite bus having a line volt- age of 14 kV, and the excitation voltage is 18 chro- ation g. 19). E for a age adjusted to 1.14 pu. hasor Calculate 1S KA a. The torque angle § when the generator delivers 420 MW of E b. The mechanical displacement angle a c. The linear pole shift (measured along the inside stator circumference) ive nms. er phase corresponding to this displacement angle [in] For what 19 A test taken on the 500 MVA alternator of Fig. 2 yields the following results: Onen-circuit line voltage is 15 kV for a Power 14
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
State Variable Analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning