ELEC 111 Installation NEC Questions
Overview
The NEC provides guidance for all types of conduit and raceways approved for use in electrical construction. For each of the questions below, find the answer in the NEC and enter your answer in the box provided.
Questions
1.
What is the purpose of Article 344?
it covers rigid metal conduit
2.
According to Article 34, how often should an electrician secure conduit between enclosures? Where is this answer found?
not exceeding 3 m (10 ft).
3.
What is the difference between EMT and RMC?
EMT is a lot lighter
Installation NEC Questions
ELEC 111
Revised: 07.21 jh
Academic Affairs Department
San Joaquin Valley College
ELEC 111 Installation NEC Questions
4.
What is the purpose of Chapter 9 Table 2 in the National Electrical Code?
NEC Chapter 9 is used for combinations of conductors of different sizes or insulation types installed in the same conduit or
tubing.
5.
What is the maximum cross-sectional conductor area allowed for metal wireways?
20 percent of the interior cross-sectional area of the wireway.
6.
Can cablebus installations transverse a fire wall?
yes it could
7.
Can a switch be enclosed in a nonmetallic auxiliary gutter?
shall not be used to enclose switches
8.
What is the maximum length of a run of FMT?
Installation NEC Questions
ELEC 111
Revised: 07.21 jh
Academic Affairs Department
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
- Access to all documents
- Unlimited textbook solutions
- 24/7 expert homework help
Related Questions
Electrical plants
Define the terms "Main column ." " Line ." " Protection earth " and "
Operating earth
arrow_forward
What is the mean of wiring
arrow_forward
5. Which of the following descriptions of a ground ring is correct?A. A ground ring is a circular formation that's made up of six or more grounding electrodes.B. A ground ring is a coiled conductor that's buried underneath a utility pole.C. A ground ring is a device that's used to clamp a conductor to a water pipe.D. A ground ring is a bare copper conductor that will encircle an entire structure underground.
arrow_forward
7.B. The size of a grounding electrode conductor for a service or separately derived system is generally basedon the size of the largestA. ungrounded supply conductor.B. equipment grounding conductor.C. grounded electrode.D. bonding jumper.7.C. Which of the following statements about bonding is true?A. The joint or termination must offer opposition in the circuit for effective electrical connections.B. Effective bonding keeps impedance high if a fault should occur.C. The entire electrical safety circuit is only as good as its strongest bonded link.D. Bonding connections must endure high levels of fault current until overcurrent protective devices can operate.
arrow_forward
The term "____" is defined in NEC® Article 100 as "connected to establish electrical continuity and conductivity."
Select one:
A. BENDED (BENDING)
B. BONDED (BONDING)
C. SHUNTED (SHUNTING)
D. GROUNDED (GROUNDING)
arrow_forward
13. Which of the following is a method for identifying a grounding terminal for connecting an equipmentgrounding conductor to a device?A. The letters EGCB. A green octagonal nutC. A red pressure wire connectorD. A green screw with a hexagon head
arrow_forward
Wiring methods permitted for service conductors include.
A. Rigid metal conduit B. Electrical metallic tubing
C. Rigid nonmetallic conduit D. all of these
arrow_forward
To testing installation of grounds, the usual procedure is to connect one lead of the megohmmeter to one of the conductors, then the other lead is___.
A, connected to another conductor b, connected to the conduit or raceway c. Connected to a special grounding electrode on the megohmmeter d. Left unconnected
arrow_forward
QUESTION 12
What is the minimum sized IMC conduit we should use for the above wire run if it is 24 inches long?
a
1/2"
b
3/4"
c
1"
d
1 1/4"
arrow_forward
QUESTION 3
We are running 3 wires and a ground in a RMC to a control panel with a 60 amp circuit breaker disconnect in the control panel. The conduit is run along the ceiling where the ambient air temperature is 100 degrees. The control panel feeds our secondary cooling pump. What size are the ungrounded conductors? All conductors have typeTHHN insulation.
arrow_forward
If the NEC provides a requirement to grounding equipment, it generally implies that there will be a direct connection to Earth of connection through a/an
A. Equipment grounding conductor
B. Bonding conductor
C. Grounding electrode conductor
D. Equipotential bonding conductor
arrow_forward
45. A switch or circuit breaker can be used as both the controller and disconnecting means if
it
a. opens all ungrounded conductors as required by NEC 430.103
b. is protected by an overcurrent device in each ungrounded conductor
c. is manually operable, or both power and manually operable
d. All of these answers
arrow_forward
of p
o How many conductors enter the ceiling fan/light wall box?
Switch ond out let boxes
s tirst
10. What type and size of box may be used for the ceiling fan/light wall box?.
11. What type of covers are used with 4 in. square outlet boxes?
12. a. Does the circuit for the Master Bedroom have a grounded circuit conductor?
b. Does it have an equipment grounding conductor?
c. Explain the difference between a "grounded" conductor and an "equipment
grounding" conductor.
13. Approximately how many feet (meters) of 2-wire cable and 3-wire cable are needed to
ft
complete the circuit supplying the Master Bedroom? Two-wire cable:
ft (-
m).
m). Three-wire cable:
14. If the cable is laid in notches in the corner studs, what protection for the cable must be
provided?
15. How high are the receptacles mounted above the finished floor in this bedroom?
16. Approximately how far from the bedroom door is the first receptacle mounted? (See
the plans.)
17. What is the distance from the finished floor to…
arrow_forward
Grounding lighting fixtures. Threre are specific requirements for grounding lighting fixtures. How must they be grounded and with what size conductors?
arrow_forward
24.
The National Electrical Code® _____ contains tables dealing with conductors for general wiring.
Select one:
A.
100
B.
110
C.
310
D.
300
arrow_forward
What assumptions can you make regarding the following receptacle wiring?
Check all that apply.
White neutral wire
Grounding
screw
Brass screw
terminal
Silver screw
terminal
Black hot
wire
Red hot wire
Grounding wires
Grounding
screw
terminal
O device is at end-of-run
device box does not need a ground connection
this is a split-circuit receptacle
neutral side receptacle tab must be removed
arrow_forward
Need all detailed information and answers.
What are three main reasons to install grounds and bonds on an isolated circuit before work is started? When using protective grounds, does the application of the grounding principle control current or voltage? Does all the current in a grounded conductor take the easiest path to earth? What is the bonding principle? When removing protective grounds on an isolated circuit, which set of grounds is more likely to create an arc, the first set or the second set?
arrow_forward
Question 6 B
Thevenin’s Theorem RL
what VTH RTH
Full explain this question very fast solution sent me step by step
Not:- Text typing work only and Don't ignore any part all part work u
arrow_forward
NEC identifies ____ types of rigid PVC conduit.
Select one:
A. FIVE
B. TEN
C. THREE
D. TWO
arrow_forward
QUESTION 3
What is the minimum sized EMT conduit we should use for the above wire run if it is 24 inches long?
a
1/2"
b
3/4"
c
1"
d
1 1/4"
arrow_forward
H1. If you need to make a straight connection to splice two conductors (both size 4 AWG) together, whichof the following connection methods should you use?A. A pressure connectorB. A barrel crimpC. A butt crimpD. A wire nut
H2. A/An _______ is an insulating tube or sleeve that protects an electrical conductor where it passesthrough a hole.A. expansion fittingB. couplingC. gland nutD. bushing
H3. Conductors that are larger than AWG size 8 will come only as a/an _______ conductor.A. aluminumEnd of examB. coveredC. solidD. stranded
arrow_forward
UPVOTE WILL BE GIVEN. WRITE THE COMPLETE SOLUTIONS LEGIBLY (HANDWRITTEN) NO LONG EXPLANATION NEEDED. SOLVE IN 3 DECIMAL PLACES. BOX THE FINAL ANSWER.
arrow_forward
a.2. Which of the following statements about grounding electrode conductors is true?A. They restrict the ground connection.B. They eliminate potential differences between conductive objects and the Earth electrode.C. They facilitate operation of overcurrent protective devices.D. They perform bonding between the Earth and grounded conductors.a.3. Main bonding jumpers are required to be made of _______ or other corrosion-resistant material.A. brassB. aluminumC. copperD. copper-clad aluminum
arrow_forward
Raceway fill calculations are a prerequisite in ____ needed for particular circuits.
Select one:
A. MATERIAL REQUIREMENTS
B. SCHEMATIC REQUIREMENTS
C. DETERMINING THE SIZE OF RACEWAY
D. CIRCUIT LOADS
arrow_forward
1-Calculate the minimum and maximum protection for an A/C , its conductors(75 ºC) and its grounding. For the following values:1- FLC compressor = 30 A2- FLC condenser = 3 A
arrow_forward
List the basic concepts involved in house wiring?
arrow_forward
QUESTION 9
What is the minimum sized Rigid Metal Conduit we should use for the above wire run if it is 24 inches long?
a
3/4"
b
1"
c
1 1/4"
d
1 1/2"
arrow_forward
SEE MORE QUESTIONS
Recommended textbooks for you
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Related Questions
- Electrical plants Define the terms "Main column ." " Line ." " Protection earth " and " Operating eartharrow_forwardWhat is the mean of wiringarrow_forward5. Which of the following descriptions of a ground ring is correct?A. A ground ring is a circular formation that's made up of six or more grounding electrodes.B. A ground ring is a coiled conductor that's buried underneath a utility pole.C. A ground ring is a device that's used to clamp a conductor to a water pipe.D. A ground ring is a bare copper conductor that will encircle an entire structure underground.arrow_forward
- 7.B. The size of a grounding electrode conductor for a service or separately derived system is generally basedon the size of the largestA. ungrounded supply conductor.B. equipment grounding conductor.C. grounded electrode.D. bonding jumper.7.C. Which of the following statements about bonding is true?A. The joint or termination must offer opposition in the circuit for effective electrical connections.B. Effective bonding keeps impedance high if a fault should occur.C. The entire electrical safety circuit is only as good as its strongest bonded link.D. Bonding connections must endure high levels of fault current until overcurrent protective devices can operate.arrow_forwardThe term "____" is defined in NEC® Article 100 as "connected to establish electrical continuity and conductivity." Select one: A. BENDED (BENDING) B. BONDED (BONDING) C. SHUNTED (SHUNTING) D. GROUNDED (GROUNDING)arrow_forward13. Which of the following is a method for identifying a grounding terminal for connecting an equipmentgrounding conductor to a device?A. The letters EGCB. A green octagonal nutC. A red pressure wire connectorD. A green screw with a hexagon headarrow_forward
- Wiring methods permitted for service conductors include. A. Rigid metal conduit B. Electrical metallic tubing C. Rigid nonmetallic conduit D. all of thesearrow_forwardTo testing installation of grounds, the usual procedure is to connect one lead of the megohmmeter to one of the conductors, then the other lead is___. A, connected to another conductor b, connected to the conduit or raceway c. Connected to a special grounding electrode on the megohmmeter d. Left unconnectedarrow_forwardQUESTION 12 What is the minimum sized IMC conduit we should use for the above wire run if it is 24 inches long? a 1/2" b 3/4" c 1" d 1 1/4"arrow_forward
- QUESTION 3 We are running 3 wires and a ground in a RMC to a control panel with a 60 amp circuit breaker disconnect in the control panel. The conduit is run along the ceiling where the ambient air temperature is 100 degrees. The control panel feeds our secondary cooling pump. What size are the ungrounded conductors? All conductors have typeTHHN insulation.arrow_forwardIf the NEC provides a requirement to grounding equipment, it generally implies that there will be a direct connection to Earth of connection through a/an A. Equipment grounding conductor B. Bonding conductor C. Grounding electrode conductor D. Equipotential bonding conductorarrow_forward45. A switch or circuit breaker can be used as both the controller and disconnecting means if it a. opens all ungrounded conductors as required by NEC 430.103 b. is protected by an overcurrent device in each ungrounded conductor c. is manually operable, or both power and manually operable d. All of these answersarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT