Estimate the distance over which a load of 15,000 kW at 0,85 power factor can be delivered by a 3-phase transmission line having conductors of steel-cored aluminium each of resistance 0.56 per km. The p.d. at the receiving end is to be 132 kV and the loss in transmission is not to exceed 7.5% * 121.9 km 211.9 Km 112.9 Km 243.8 Km

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter5: Transmission Lines: Steady-state Operation
Section: Chapter Questions
Problem 5.48P
icon
Related questions
icon
Concept explainers
Question
3
Estimate the distance over which a load of 15,000 kW at 0.85 power factor can be delivered by
a
3-phase transmission line having conductors of steel-cored aluminium each of resistance 0.56
O per
km. The p.d. at the receiving end is to be 132 kV and the loss in transmission is not to exceed
7.5%
121.9 km
211.9 Km
112.9 Km
243.8 Km
Transcribed Image Text:3 Estimate the distance over which a load of 15,000 kW at 0.85 power factor can be delivered by a 3-phase transmission line having conductors of steel-cored aluminium each of resistance 0.56 O per km. The p.d. at the receiving end is to be 132 kV and the loss in transmission is not to exceed 7.5% 121.9 km 211.9 Km 112.9 Km 243.8 Km
Expert Solution
steps

Step by step

Solved in 3 steps

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning