Example: A 3-phase overhead transmission line has a total series impedance per phase of 200 280° ohms and a total shunt admittance of 0-0013290° Siemen per phase. The line delivers a load of 80 MW at 0-8 p.f. lagging and 220 kV between the lines. Determine the sending end line voltage and current by Rigorous method.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter5: Transmission Lines: Steady-state Operation
Section: Chapter Questions
Problem 5.41P
icon
Related questions
icon
Concept explainers
Question
100%
Example: A 3-phase overhead transmission line has a total series impedance per
phase of 200 280° ohms and a total shunt admittance of 0-0013290° Siemen per
phase. The line delivers a load of 80 MW at 0-8 p.f. lagging and 220 kV between the
lines. Determine the sending end line voltage and current by Rigorous method.
Transcribed Image Text:Example: A 3-phase overhead transmission line has a total series impedance per phase of 200 280° ohms and a total shunt admittance of 0-0013290° Siemen per phase. The line delivers a load of 80 MW at 0-8 p.f. lagging and 220 kV between the lines. Determine the sending end line voltage and current by Rigorous method.
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning