If Vab = 400 V in a balanced Y-connected three-phase generator, find the phase voltages, assuming the phase sequence is:
- (a) abc
- (b) acb
(a)
Find the phase voltages for the abc sequence.
Answer to Problem 1P
For the abc sequence,
The phase voltage
The phase voltage
The phase voltage
Explanation of Solution
Given data:
For a balanced Y-connected three phase generator,
The line to line voltage (line voltage)
The phase sequence is abc.
Formula used:
The line voltage in the Y-connection can be written as follows in abc sequence.
Reduce the equation to find the rms value of the phase voltage.
Here,
In Y-connection, the phase voltages can be written as follows on positive phase sequence abc.
Substitute equation (1) in equations (2), (3) and (4).
The phase voltage
The phase voltage
And
The phase voltage
Or the phase voltage
Calculation:
Substitute
Substitute
Substitute
Or from equation (8) the phase voltage
Conclusion:
Thus, for the abc sequence,
The phase voltage
The phase voltage
The phase voltage
(b)
Find the phase voltages for the acb sequence.
Answer to Problem 1P
For the acb sequence,
The phase voltage
The phase voltage
The phase voltage
Explanation of Solution
Given data:
The phase sequence is acb.
Formula used:
The line voltage in the Y-connection can be written as follows in acb sequence.
Reduce the equation to find the rms value of the phase voltage.
Here,
In Y-connection, the phase voltages can be written as follows on positive phase sequence acb.
Substitute equation (9) in equations (10), (11) and (12).
The phase voltage
The phase voltage
And
The phase voltage
Or the phase voltage
Calculation:
Substitute
Substitute
Substitute
Or from equation (16) the phase voltage
Conclusion:
Thus, for the acb sequence,
The phase voltage
The phase voltage
The phase voltage
Want to see more full solutions like this?
Chapter 12 Solutions
FUND.OF ELECTRIC CIRCUITS(LL)-W/CONNECT
- A balanced Δ - connected load having a 15 Ω resistance in each leg is connected to a three -phase , four wires, Y-connected ABC sequence AC generator, if the line volatge EAB=, calculate 1. The phase voltages of the generator 2. The phase voltages of the load 3. The phase currents of the load 4. The line currentsarrow_forwardA balanced 3-phase, delta-connected load is connected across a 208 V, balanced 3-phase, ABC source. If it dissipates 10 KW at 60% p.f. lagging, its line current, Ia is ANSWER QUICKLYarrow_forwardA balanced Y - connected load having a 25 Ω resistance in each leg is connected to a three -phase , four wires, Y-connected ABC sequence AC generator, if the line volatge EAB=, calculate 1. The phase voltages of the generator 2. The phase voltages of the load 3. The phase currents of the load 4. The line currentsarrow_forward
- Calculate the line current required for a 30-kW three-phase motor having a power factor of 0.85 lagging if it is connected to a balanced source with a line voltage of 440 V.arrow_forwardA single – phase transmission line supplies a reactive load at a lagging power factor. The load draws 1.2 pu current at 0.6 pu voltage while drawing 0.5 pu (true) power. If the base voltage is 20 kV and the base current is 160 A, calculate the power factor and the ohmic value of the resistance of the load.arrow_forwardA balanced Y - connected load having in each leg a 10 Ω resistance in series with 10 Ω inductive reactance is connected to a three -phase , four wires, Y-connected ABC sequence AC generator, if the line volatge EAB=120 angle 0 degree space v, calculate 1. The phase voltages of the generator 2. The phase voltages of the load 3. The phase currents of the load 4. The line currentsarrow_forward
- Two wattmeters are used to measure the total power drawn by a balaced delta connected load. If the wattmeters read 1200 W and 800 W respectively, and the line to line voltage is 208 V, solve for the impedance per phase of the load.arrow_forward:A three-phase, three-wire, ABC system has effective line voltage 173.2 V. Wattmeters in lines A and B read -301 W and 1327 W, respectively. Find the impedance of the balanced Y-connected load. (Answer 10 angle -70° )arrow_forwardThe input power to a 3-phase load is measured as 17kW. If the line voltage and power factor of the load are 400 V and 0.5, then the value of line current is given byarrow_forward
- Given ??? = 208 ∠ − 40° V in a three-phase ACB circuit, find the currents of the phasor line for a balanced load that absorbs 10 kW at a power factor of 0.8 lagging.arrow_forward- A three-phase, positive-sequence, balanced star source has a phase voltage of Van = 240 ∠90° Vrms. Determine the source line voltagesarrow_forward2. Solve the following problem: A THREE-PHASE PLANT CONSUMES 600 KVA, WITH A VOLTAGE OF 2400 VOLTS AND A POWER FACTOR OF 0.8 BEHIND. a) DETERMINE THE EQUIVALENT DELTA IMPEDANCE OF THE PLANT. b) IF THE PLANT WERE A STAR, CALCULATE THE RESISTANCE, REACTANCE AND THE CORRESPONDING PASSIVE ELEMENT.arrow_forward
- Introductory Circuit Analysis (13th Edition)Electrical EngineeringISBN:9780133923605Author:Robert L. BoylestadPublisher:PEARSONDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningProgrammable Logic ControllersElectrical EngineeringISBN:9780073373843Author:Frank D. PetruzellaPublisher:McGraw-Hill Education
- Fundamentals of Electric CircuitsElectrical EngineeringISBN:9780078028229Author:Charles K Alexander, Matthew SadikuPublisher:McGraw-Hill EducationElectric Circuits. (11th Edition)Electrical EngineeringISBN:9780134746968Author:James W. Nilsson, Susan RiedelPublisher:PEARSONEngineering ElectromagneticsElectrical EngineeringISBN:9780078028151Author:Hayt, William H. (william Hart), Jr, BUCK, John A.Publisher:Mcgraw-hill Education,