Consider the wye-delta system shown in Fig. 12.60. Let
Find the phase and line currents for the
Answer to Problem 51P
The phase currents
The line currents
Explanation of Solution
Given data:
Refer to Figure 12.60 for the
In the Y-connected source:
The line to neutral voltage
The line to neutral voltage
The line to neutral voltage
In the delta-connected unbalanced load:
The impedance
The impedance
The impedance
Formula used:
Write the expression to find the line to line voltage
Here,
Write the expression to find the line to line voltage
Here,
Write the expression to find the line to line voltage
Here,
Write the expression to find the line to line current
Here,
Write the expression to find the line to line current
Here,
Write the expression to find the line to line current
Here,
Write the expression to find the line current
Here,
Write the expression to find the line current
Here,
Write the expression to find the line current
Calculation:
Re-draw the given Figure 12.60 as follows.
Substitute
Substitute
Substitute
Substitute
Substitute
Substitute
Or
Thus, the phase currents are,
Substitute
Substitute
Substitute
Thus, the line currents are,
PSpice simulation:
Assume the angular frequency
Write the expression to find the capacitive reactance.
Substitute
Write the expression to find the inductive reactance.
Substitute
Draw the circuit as shown in Figure 2 in PSpice, connect the
Provide the Simulation settings as in Figure 2.
Now, run the simulation and check the output file in newly opened PSpice A/D window.
From the PSpice results the phase currents are,
FREQ IM(V_IAB) IP(V_IAB)
1.5916E-01 2.0785E+00 1.2000E+02
FREQ IM(V_IBC) IP(V_IBC)
1.5916E-01 2.0785E+00 9.0000E+01
FREQ IM(V_ICA) IP(V_ICA)
1.5916E-01 2.0785E+00 1.5000E+02
The phase current
The phase current
The phase current
From the PSpice results the line currents are,
FREQ IM(V_IaA) IP(V_IaA)
1.5916E-01 1.0759E+00 4.5000E+01
FREQ IM(V_IbB) IP(V_IbB)
1.5916E-01 1.0759E+00 1.5000E+01
FREQ IM(V_IcC) IP(V_IcC)
1.5916E-01 2.0785E+00 -1.5000E+02
The line current
The line current
The line current
Conclusion:
Thus,
The phase currents
The line currents
Want to see more full solutions like this?
Chapter 12 Solutions
Package: Fundamentals Of Electric Circuits With 2 Semester Connect Access Card
- 3. A balanced delta connected load of "14+J18" ohm - per phase is connected at the end of a three-phase line. The line impedance is "7+J12" ohm - per phase. The line is supplied from a three-phase source with a line-to-line voltage of 207.85 Vrms. Taking phase "a" voltage Va as reference, determine the following: (a) Current in phase a. (b) Total complex power supplied from the source. (c) Magnitude of the line-to-line voltage at the load terminal.arrow_forwardA load connected in delta, with impedances of 24 ≮ 20°, has a current IAC = 20 ≮ 10°, Calculate:a- Phase currentsb- Line currentsc- Line-Line voltagesarrow_forwardA balanced three-phase Y-source with Vph=221 vrms drives a Y-connected three-phase load with phase impedance Za=84 Ohm, Zb=2+j11 ohm, and Zc=j84 ohm. Calculate the line currents and total complex power delivered to the load. Assume that the neutrals are connected.arrow_forward
- A three-phase line with an impedance of (0.2+j1.0)/ phase feeds three balanced three-phase loads connected in parallel. Load 1: Absorbs a total of 150 kW and 120 kvar. Load 2: Delta connected with an impedance of (150j48)/phase. Load 3: 120 kVA at 0.6 PF leading. If the line-to-neutral voltage at the load end of the line is 2000 v (rms), determine the magnitude of the line-to-line voltage at the source end of the line.arrow_forwardTwo balanced three-phase loads that are connected in parallel are fed by a three-phase line having a series impedance of (0.4j2.7) per phase. One of the loads absorbs 560 kVA at 0.707 power factor lagging, and the other 132 kW at unity power factor. The line-to-line voltage at the load end of the line is 2203V. Compute (a) the line-to-line voltage at the source end of the line. (b) the total real and reactive power losses in the three-phase line, and (c) the total three-phase real and reactive power supplied at the sending end of the line. Check that the total three-phase complex power delivered by the source equals the total three-phase comp lex power absorbed by the line and loads.arrow_forwardConsider a three-phase Y-connected source feeding a balanced- load. The phasor sum of the line currents as well as the neutral current are always zero. (a) True (b) Falsearrow_forward
- A balanced Y-Y system with generator phase voltages Van = 15kV @ 0 degrees is connected through transmission lines to a load with phase impedance of 24+j18 Ω. What is the current phasor through the B transmission line?arrow_forward12) If Vab = 223 Vrms in a balanced Y-connected three-phase generator, find the magnitude of the phase-c voltage (in Vrms), assuming the phase sequence is acb.arrow_forward16) In a balanced three-phase Y-Y system, the source is an abc sequence of voltages and Van = 139∠12° Vrms. The line impedance per phase is 1.1 + j1.9Ω , while the per-phase impedance of the load is 7 + j13Ω . Calculate the magnitude of the voltage drop across the load of phase-b (in Vrms).arrow_forward
- Athree-phase delta-connected load of 15 j180 per phase is supplied by an abc-sequence balanced three-phase wye-connected source with a line voltage of 400 V. The line impedance is 1 + 120 per phase. Taking E as reference, determine the line currents, phase load currents, phase load voltages, and the total complex power supplied by the sourcearrow_forward1. An unbalanced, three-phase, delta-connected load, is supplied by an alternator three-phase system given in abc phase sequence in which Vbc is 220∠0° V. The load impedances Zab, Zbc, and Zca are given as 5∠60°, 10∠0°, and 15∠−20° Ω, respectively. Determine the following: (a) The phase currents Iab, Ibc, and Ica (b) The line currents Ia, Ib, and Ic (c) The powers absorbed by the individual impedances of the load (d) The total power absorbed by the load (e) The power recorded on each wattmeter assuming line B is the common.arrow_forwardA three phase delta-connected load of 15+j18 per phase is supplied by an abc-sequence balance three phase wye connected source with a line voltage of 400v. The line impedance is 1+j2 per phase. Taking EA as a refeference, determine the line currents, phase load currents, phase voltages, and total complex power supplied by the source.arrow_forward
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning