Three 20-kVA, 24,000/277-V distribution transformers are connected in
The open-circuit test was performed on the low-voltage side of this transformer bank, and the following data were recorded:
The short-circuit test was performed on the high-voltage side of this transformer bank, and the following data were recorded:
- Find the per-unit equivalent circuit of this transformer bank.
- Find the voltage regulation of this transformer bank at the rated load and 0.90 PF lagging.
- What is the transformer bank’s efficiency under these conditions?
Trending nowThis is a popular solution!
Chapter 2 Solutions
Electric machinery fundamentals
Additional Engineering Textbook Solutions
ELECTRICITY FOR TRADES (LOOSELEAF)
Programmable Logic Controllers
Principles Of Electric Circuits
Principles and Applications of Electrical Engineering
ANALYSIS+DESIGN OF LINEAR CIRCUITS(LL)
Introductory Circuit Analysis (13th Edition)
- An infinite bus, which is a constant voltage source, is connected to the primary of the three-winding transformer of Problem 3.53. A 7.5-MVA,13.2-kV synchronous motor with a sub transient reactance of 0.2 per unit is connected to the transformer secondary. A5-MW,2.3-kV three-phase resistive load is connected to the tertiary Choosing a base of 66 kV and 15 MVA in the primary, draw the impedance diagram of the system showing per-unit impedances. Neglect transformer exciting current, phase shifts, and all resistances except the resistive load.arrow_forwardContract load demand of a new facility in your workplace is 62 kVA and the load diversity may be taken to be 80%. A 65 kVA, 11000 V/415 V, 50 Hz, 3-phase transformer has been proposed for this facility. This transformer from ABC Ltd. guarantees a voltage regulation of 4.4% and 97% full load power efficiency at 0.8 lagging power factor. A continuous full load operation for a considerable period of time is expected every day. Full load power factor is 0.82 lagging. Utility side voltage can be considered to be well regulated at 11000 V. find out the following, Rated current of the transformer (secondary side) find out the load current at full load Compare the load current at full load with the transformer rated currentarrow_forwardA 3-phase,50Hz, 150 KVA, 22001220 V transformer supplies a 3- phase load drawing 120 KVA and 90 KW lagging on the 220 V side. The transformer is made up of three single phase transformers connected Y/Y and having the following per phase values given: Ru=0.4Q; Xe=2; Re=4m®; X1=20me; Res=10k€; Xgsz =8k, Determine: (a) The primary voltage. (b) Efficiency. (c) The voltage regulation of the transformer.arrow_forward
- No-load operation and short circuit tests were performed on three-phase, 50 Hz 480/220 delta / Y connected transformer. In these testsThe line voltage, line current and three-phase total power have been measured from the high voltage windings and the test results are below.pictures. 100 A DC current when 1.08 V DC voltage from non-transferable software is applied to the low voltage windingshas attracted.Find the single phase equivalent circuit parameters of this transformer.idle test:Voltage: 480V Power:114w current: 0.71Ashort circiut test:V: 10v P: 78w c: 18.3aarrow_forwardQ.) A single-phase transformer is rated at 10 kVA, 230 V/100 V. When the secondary terminals are open-circuited and the primary winding is supplied at normal voltage (230 V), the current input is 2.6 A at a power factor of 0.3. When the secondary terminals are short-circuited, a voltage of 18 V applied to the primary causes the full-load current (100 A) to flow in the secondary, the power input to the primary being 240 W. Calculate: (i) The efficiency of the transformer at full load, unity power factor. (ii) The load at which maximum efficiency occurs. (iii) The value of the maximum efficiencyarrow_forwardOn the plate of a single-phase transformer, it is written 20 kVa, 2000/200V, 50Hz. The results in the figure were obtained in the open-circuit test performed on the transformer. Draw the electrical equivalent circuit of the transformer for the high-voltage open-circuit no-load test by writing on the circuit element and on it. open circuit test high voltage side open circuit V= 200 A = 6a W = 200W closed circuit experiment low voltage side short circuit V= 200v A = 10 A W= 400Warrow_forward
- Three 20-kVA, 24000/277-V distribution transformers are connected in Δ-Y. The open-circuit test was performed on the low voltage side of this transformer bank, and the following data were recorded: Vline, OC = 480 V Iline, OC = 4.1 A P3φ, OC = 945 W The open-circuit test was performed on the low voltage side of this transformer bank, and the following data were recorded: Vline, SC = 1400 V Iline, SC = 1.8 A P3φ, SC = 912 W What is the magnetization reactance of this transformer, XM, in pu?arrow_forwardA single-phase, 20-kVA, 20,000/480 V, 60Hz distribution transformer is tested with the followingresults:VOC=480V VSC=1130 VIOC=1.60 A ISC= 1APOC= 305 W PSC= 260Wa. Find the equivalent circuit referred to the low-voltage side. Hint: First find out whether the testsabove are referred to the LV or HV side.b. Find the equivalent circuit referred to the high-voltage side.c. Find the equivalent circuit in pu d. Use the equivalent circuit referred to the low-voltage side, find the voltage regulation and theefficiency of the transformer for full load, 0.85 pf lagging.e. Repeat d in pu.arrow_forwardThe following data were obtained on a 2.5 MVA, 50-Hz, 19.1-kV:3.81-kV single-phase transformertested at 50 Hz:Voltage (V) Current (A) Power (kW)LV winding with HV terminals open-circuited: 3810 9.86 8.14HV winding with LV terminals short-circuited: 920 141 10.3a. Calculate the cantilever equivalent-circuit parameters as referred to the transformer high-voltagewinding.b. Calculate the cantilever equivalent-circuit parameters as referred to the transformer low-voltagewinding.c. With the transformer carrying rated load and rated voltage at its low-voltage terminal, calculate thepower dissipated in the transformer.d. Repeat part a and b in per-unit. Compare and comment on your result.arrow_forward
- 2.A 10 kVA, 1000 V / 200 V, 50 Hz, single phase transformer has HV and LV sidewinding resistances as 1.1 Ωand 0.05 Ω respectively. The leakage reactances of HV and LV sides are respectively 5.2 Ω and 0.15 Ωrespectively. Calculate [i] the voltage to be applied to the HV side in order to circulate rated current with LVside shorted, [ii] Also calculate the power factor under this condition.arrow_forward1.The secondary line to line voltage of a star-delta connected transformer is measured to be400 V. If theturns ratio between the primary and secondary coils is 2 : 1, the applied line to line voltage in theprimary is:(A) 462 V (B) 346 V (C) 1386 V (D) 800 Varrow_forwardThe following data from the open circuit and short circuit tests of the 10 kVA, 120/2400 V, 60 Hz single-phase transformer were recorded: Short-circuit test (low side short-circuited): VA = 160 V, IA = 4 A, PA = 100 W; Open circuit test (high side open): VB = 120 V, IB = 3.5 A, PB = 75 W. Obtain the equivalent circuit parameters referred to the high circuit.arrow_forward
- Delmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningPower System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning