Question
Chapter 20.2, Problem 8R
To determine
Calculate the maximum demand for the appliances.
Expert Solution & Answer
Trending nowThis is a popular solution!
Students have asked these similar questions
When an individual branch circuit supplies a counter-mounted cooking unit, what Code reference tells us that it is “against Code” to apply the demand factors of Table 220.55 and requires us to calculate the load based on the appliance's actual nameplate rating?
What is the demand load for the service for two 3.5-kW wall-mounted ovens and one 5-kW counter-mounted cooking unit ? All of the appliances are supplied from a single branch circuit and are located in the same room of a one-family dwelling
Calculate the voltage drop of a 120/240-volt, three-wire underground residential service installed with 2 AWG aluminum URD cable if the load is 80 amps and the one-way length of the underground service conductors is100 feet.
Chapter 20 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- May the 20-ampere small-appliance branch circuits in the kitchen of a residence also supply the lighting above the kitchen sink and under-cabinet lighting? Check the correct answer. Yes______ No ______arrow_forwardIn a single-family dwelling, how is overcurrent protection for branch circuits required to be provided? See NEC 210.20. __________arrow_forwardDuplex receptacles connected to the 20-ampere small-appliance branch circuits in kitchens and dining rooms (Circle the correct answer): a. may be rated 15 amperes.(True)(False) b. must be rated 15 amperes.(True)(False) c. may be rated 20 amperes.(True)(False) d. must be rated 20 amperes.(True)(False)arrow_forward
- small appliance receptacles included in the 3 volt-ampere per square foot load calculationarrow_forwardA sound level meter is placed in front of a loudspeaker of a 60W audio system reads 70dB. All else being equal, when placed in front of a 120W system, the meter will read ________?arrow_forward17.b. Which of the following is the best example of a building supplied by a single branch circuit?A. A detached carport with no doors, walls, or windowsB. A detached garage at a dwelling occupancyC. A ground-mounted air conditionerD. A university dormitoryarrow_forward
- Does the NEC permit the receptacle for the refrigerator to be supplied by one of the required 20-ampere small appliance branch circuit A) Yes B) Noarrow_forwardThe LRT trolley system 10 miles ling is fed by two substations that generate 600 volts and 500 volts, respectively. The resistance of the trolley wire and the rail return is 0.3 ohm per mile. If the car is located 4 miles from the 600-volt station draws 200 A from the line. How much is the current supplied by each station?arrow_forwardWhen installing ceiling-suspended (paddle) fans, per the requirements found in NEC 314.27(C) and NEC 422.18 and the UL Product Spec database, the outlet box or outlet system consist of the following:arrow_forward
- Take a look at the wire supplying your house, another residential house, commercial and industrial buildings in your locality, count how many wires are connected to the building (from the electric meter to the weather head OR the service drop itself)? Are the wires different from each other? If so, why?arrow_forwardAn eighteen-unit multifamily dwelling contains the following appliances in each unit : a 1-kVA, 115-volt dishwasher, a 1/3 hp, 115-volt in-sink waste disposer and a 4500-watt, 230 volt water heater. Using the standard method, what is the service neutral load contribution, in volt-amperes , for these appliances ? ( Assume water heater watt rating equivalent to volt-ampere )arrow_forward8. What is the maximum load to be connected to a single receptacle rated at 20A?arrow_forward
arrow_back_ios
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
What is an electric furnace and how does it work?; Author: Fire & Ice Heating and Air Conditioning Inc;https://www.youtube.com/watch?v=wjAWecPGi0M;License: Standard Youtube License