The missing values in the table.
Answer to Problem 3PP
ET = 23.99 V | ER = 23.99 V | EL = 23.99 V | EC = 23.99 V |
IT = 2.004 A | IR = 1.999 A | IL =0.399 A | IC =0.533 A |
Z = 11.973 Ω | R = 12 Ω | XL = 60 Ω | XC = 45 Ω |
VA = 48.106 | P = 47.96 W | VARSL = 9.575 | VARSC = 12.791 |
PF = 99.725 % | ∠θ = 4.25° | L = 0.159 H | C = 58.94 µF |
Explanation of Solution
Given data :
The value of the inductor is given by,
The value of the capacitor is given by,
The impedance of the parallel circuit is given as,
To determine the value of total voltage across the parallel R-L-C circuit,
Since the circuit is parallel R-L-C circuit,
The total current flowing through the parallel RLC circuit will be,
The current flowing through the resistor in the parallel RLC circuit will be,
The current flowing through the inductor in the parallel RLC circuit will be,
The current flowing through the capacitor in the parallel RLC circuit will be,
The true power in the parallel circuit will be,
The reactive power of the inductor is given by,
The reactive power of the capacitor is given by,
The Power factor of the circuit is calculated as,
Power factor angle θ will be,
Want to see more full solutions like this?
Chapter 25 Solutions
EBK DELMAR'S STANDARD TEXTBOOK OF ELECT
- THREE PHASE( NEED ONLY HANDWRITTEN SOLUTION PLEASE OTHERWISE DOWNVOTE).arrow_forwardSolve only QUESTION 10.arrow_forwardWhich of the following capacitors could be used to replace a 188-microfarad, 250-volt starting capacitor? 188 microfarad, 120 volt 259 microfarad, 120 volt 200 microfarad, 250 volt 300 microfarad, 250 voltarrow_forward
- Which of the following capacitors or combination of capacitors could be used to replace an 88-microfarad, 250-volt starting capacitor? 180 microfarad, 250 volt 180 microfarad, 330 volt 150 microfarad, 120 volt 150 microfarad, 250 voltarrow_forward18. A 400-amp circuit breaker protects a feeder that's installed in a nonmetallic raceway that requires an equipment grounding conductor. Which of the following is the minimum size of aluminum equipment grounding conductor that should be used in this situation? A. No. 1 B. No. 6 C. No. 2 D. No. 4arrow_forwardthumps up will be given , please solve all the parts..arrow_forward
- You are changing the starting relay on a central air-conditioning unit when you notice that the identifying mark on the compressor-run capacitor is connected to the run winding of the compressor. Should you change the capacitor connection so that the identifying mark is facing the line side or is it correct as connected? Explain your answer.arrow_forwardAnswer number 08 and show a clear and readable solution. Circuit Diagram is given below. Thanks!!!arrow_forwardA workshop is 12m by 6 m by 4 m high and has workbenches 1 m high. Discharge lamps, each with an output of 3700 lm, are to be fitted in aluminium industrial reflectors at ceiling level. The surfaces have reflectances of 0.7 for the ceiling and 0.5 for the walls. The light loss factor is 0.7. The illuminance required on the workbenches is 400 lx. (a) Find the Utilisation Factor for the room. (b) Calculate the number of lamps required.arrow_forward
- Electricity for Refrigeration, Heating, and Air C...Mechanical EngineeringISBN:9781337399128Author:Russell E. SmithPublisher:Cengage LearningDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage Learning