Question
Book Icon
Chapter 29, Problem 4PP
To determine

The missing values in the given table.

Expert Solution & Answer
Check Mark

Answer to Problem 4PP

Primary Secondary Load
EP = 23000 V EP = 120 V EP = 208 V
IP = 0.626A IP = 120.08 A IP = 69.33 A
EL = 23000 V EL = 208 V EL = 208 V
IL = 1.084 A IL = 120.08 A IL = 120.08 A
Ratio = 191.52:1 Z = 3 Ω

Explanation of Solution

DELMAR'S STANDARD TXTBK.OF...>CUSTOM<, Chapter 29, Problem 4PP

In the figure, three single-phase transformers have been connected to form a delta–wye bank.

The primary is connected to a three-phase line of 23000 V.

The secondary voltage is 208 V.

A three-phase resistive load with an impedance of 3 Ω per phase is connected to the secondary of the transformer.

The primary windings of the three single-phase transformers are connected to form a delta connection. In a delta connection, the phase voltage is equal to line voltage.

EP(PRIMARY)=EL(PRIMARY)=23000 V

The secondary windings are connected as a wye. In a wye connection, the phase voltage is less than the line voltage by a factor of 1.732 (the square root of 3). Therefore, the phase value of the primary voltage can be calculated using the formula

EP(SECONDARY)=EL(SECONDARY)1.732=2081.732=120 V

The turns ratio can be calculated by comparing the phase voltage of the primary with the phase voltage of the secondary:

Ratio=Primary VoltageSecondary Voltage=23000120.09=191.521Ratio=191.52:1

The load is connected directly to the output of the secondary. The line voltage applied to the load must therefore be the same as the line voltage of the secondary:

EL(LOAD)=208 V

The load bank is connected in a delta connection. The voltage across the phase of the load bank will equal to the line voltage.

EP(LOAD)=EL(LOAD)=208 V

The phase current of the load can be calculated using Ohm’s law:

IP(LOAD)=EP(LOAD)Z=2083= 69.33 A

The amount of line current supplying a delta-connected load will be 1.732 times the phase current of the load:

IL(LOAD)=1.732×IP(LOAD)           =1.732×69.33           =120.08 A

Since the secondary of the transformer is supplying current to only one load, the line current of the secondary will be the same as the line current of the load:

IL(SECONDARY)=120.08 A

The phase current in a wye connection is equal to the line current.

IP(SECONDARY)=IL(SECONDARY)=120.08 A

The phase current of the transformer primary can now be calculated using the phase current of the secondary and the turns ratio. Because the primary has a higher voltage than the secondary, it will have a lower current. (Volts times amperes input must equal volts times amperes output.)

IP(PRIMARY)=IP(SECONDARY)Turns Ratio=120.08191.52= 0.626 A

All the transformed values of voltage and current take place across the phases, the primary has a phase current of 6.68 A. In a delta connection, the line current is 1.732 times the phase current:

IL(PRIMARY)=1.732×IP(PRIMARY)              =1.732×0.626              =1.084 A

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
12. If overcurrent protection is provided in the transformer of a separately derived system, which of the following statements is correct?A. A ground electrode must be present at the transformer and the building's disconnect.B. There's no need for service equipment or a panelboard in the separate building.C. An equipment grounding conductor must be run with the conductors between the transformer and the building's disconnect.D. The neutral should be bonded to the equipment grounding conductor at the service equipment in the separate building.
Two different transformers details are tabulated below. Calculate the missed values in the table. Secondary terminal voltage of the second transformer is 487.5V when loaded. Determine the regulation of the transformer.?
A 300-kilovolt-ampere transformer bank consisting of three 100-kilovolt-ampere transformers has a 3-phase, 480-volt delta primary and a 120/240-volt, 3-phase, 4-wire delta-connected secondary.For problems 1 through 4 show calculations and/or source of information. 3. What is the proper rating of the fuses to install for overcurrent protection of the secondary?
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
Text book image
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Text book image
Electricity for Refrigeration, Heating, and Air C...
Mechanical Engineering
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Cengage Learning
How does a Transformer work - Working Principle electrical engineering; Author: The Engineering Mindset;https://www.youtube.com/watch?v=UchitHGF4n8;License: Standard Youtube License