In problem 35, it is desired to keep the voltage drop to 3% maximum. What minimum size wire would be installed to accomplish this 3% maximum voltage drop? See 210.19(A), Informational Note No. 4 and 215.2(A)(1), Informational Note No. 2.
Find the minimum size wire that should be installed to accomplish 3% maximum voltage drop.
Answer to Problem 36R
10 AWG or larger value conductor should be installed to accomplish 3% maximum voltage drop.
Explanation of Solution
Given data:
Supply voltage is 120-volt.
Current is 10 A.
The distance between panel and heater is approximately 140 ft.
14 AWG, 12 AWG, 10AWG, and 8 AWG copper conductor.
Calculation:
Write the expression for voltage drop in a single-phase circuit.
Here,
K is the approximate resistance in ohms per circular-mil foot at
I is the current, and
CMA is cross-sectional area of the conductors.
Modify Equation (1) for 14 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 14 AWG is 4110.
Substitute
Modify Equation (1) for 12 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 12 AWG is 6530.
Substitute
Modify Equation (1) for 10 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 10 AWG is 10,380.
Substitute
Modify Equation (1) for 8 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 8 AWG is 16,510.
Substitute
Tabulate the calculated value of the voltage drop as shown in Table 1.
Table 1
Sl. No. | Conductor Size | Voltage drop |
1 | 14 AWG | |
2 | 12 AWG | |
3 | 10 AWG | |
4 | 8 AWG |
Find the value of
Compare the obtained value of 3% voltage drop of applied voltage with voltage drops of each conductor as tabulated in Table 1.
A voltage drop of 8AWG conductor (that is 2.19 Volts drop) is less than
Conclusion:
Thus, 10 AWG or larger value conductor should be installed to accomplish 3% maximum voltage drop.
Want to see more full solutions like this?
Chapter 4 Solutions
ELECTRICAL WIRING:RESIDENTAL-6 PLANS
Additional Engineering Textbook Solutions
Electric Circuits (10th Edition)
Electric Motors and Control Systems
Principles Of Electric Circuits
Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf
Electric Circuits. (11th Edition)
Programmable Logic Controllers
- a. What size and type of conductors are installed for the service in this text? _____________ b. What size conduit is installed? _____________ c. What size grounding electrode conductor is installed? (not neutral) _____________ d. Is the grounding electrode conductor insulated, armored, or bare? _____________arrow_forwardWhat unit of measurement is used for the diameter of wires?arrow_forwardWhat unit of measurement is used for the cross-sectional area of wires? __________arrow_forward
- Define service-drop conductors.arrow_forwardIs it permitted to use flexible metal conduit over 6 ft (1.8 m) in length as a grounding means? (Yes) (No) (Circle the correct answer.)arrow_forwardWhich of the following statements about equipment grounding conductors (EGCs) is true?A. The National Electrical Code permits the EGC to also perform as a grounding electrode conductor.B. More than one EGC must be used if multiple circuits are installed in a single raceway, cable, or cable tray.C. No current should be present in the EGC during normal operation.D. EGCs are required to be decreased in size to address voltage drop.arrow_forward
- What is the mean of wiringarrow_forwardwhat is the minimum size single conductor of copper jacketed mineral insulated cable that can for a consumer's service?arrow_forwardIn the conduit diagram shown in attached picture, determine how many wires are in each conduit between each piece of equipment. Identify each wire terminal connection and the quantity of wires, as shown in the example, above the disconnectarrow_forward
- Where insulated conductors are deflected within a wireway, either at the ends or where conduits, fittings, or other raceways or cables enter or leave the wireway, or where the direction of the wireway is deflected greater than ____, dimensions corresponding to one wire per terminal in Table 312.6(A) shall apply.arrow_forwardNEC Article 800.44 states that where communication cables enter buildings, they shall_______. A. where practicable, be located below the electric light or power conductors. B. not be attached to a cross-arm that carries electric light or power conductors. C. have a vertical clearance of not less than 8 ft from all points of roofs that they passabove.D. all of thesearrow_forwardHow to compute the conduit size, when i have the given of the wire size no.12 awg? Should I use 20mmø?arrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT