ELECTRICAL WIRING:RESIDENTAL-6 PLANS
ELECTRICAL WIRING:RESIDENTAL-6 PLANS
18th Edition
ISBN: 9781305098329
Author: MULLIN
Publisher: CENGAGE L
bartleby

Concept explainers

bartleby

Videos

Textbook Question
Book Icon
Chapter 4, Problem 36R

In problem 35, it is desired to keep the voltage drop to 3% maximum. What minimum size wire would be installed to accomplish this 3% maximum voltage drop? See 210.19(A), Informational Note No. 4 and 215.2(A)(1), Informational Note No. 2.

Expert Solution & Answer
Check Mark
To determine

Find the minimum size wire that should be installed to accomplish 3% maximum voltage drop.

Answer to Problem 36R

10 AWG or larger value conductor should be installed to accomplish 3% maximum voltage drop.

Explanation of Solution

Given data:

Supply voltage is 120-volt.

Current is 10 A.

The distance between panel and heater is approximately 140 ft.

14 AWG, 12 AWG, 10AWG, and 8 AWG copper conductor.

Calculation:

Write the expression for voltage drop in a single-phase circuit.

Ed=K×I×L×2CMA (1)

Here,

Ed is the voltage drop,

K is the approximate resistance in ohms per circular-mil foot at 75°C. The value of K for the uncoated copper wire is 12.9 and for aluminum wire is 21.2.

I is the current, and

CMA is cross-sectional area of the conductors.

Modify Equation (1) for 14 AWG copper wire.

Ed(14AWG)=K×I×L×2CMA(14AWG) (2)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 14 AWG is 4110.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 4110 for CMA(14AWG) in Equation (2) to find the voltage drop in 14 AWG copper wire.

Ed(14AWG)=12.9×10×140×24110=8.788Volts drop8.79Volts drop

Modify Equation (1) for 12 AWG copper wire.

Ed(12AWG)=K×I×L×2CMA(12AWG) (3)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 12 AWG is 6530.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 6530 for CMA(12AWG) in Equation (3) to find the voltage drop in 12 AWG copper wire.

Ed(12AWG)=12.9×10×140×26530=5.531Volts drop5.53Volts drop

Modify Equation (1) for 10 AWG copper wire.

Ed(10AWG)=K×I×L×2CMA(10AWG) (4)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 10 AWG is 10,380.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 10,380 for CMA(10AWG) in Equation (4) to find the voltage drop in 10 AWG copper wire.

Ed(10AWG)=12.9×10×140×210,380=3.479Volts drop3.48Volts drop

Modify Equation (1) for 8 AWG copper wire.

Ed(8AWG)=K×I×L×2CMA(8AWG) (5)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 8 AWG is 16,510.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 16,510 for CMA(8AWG) in Equation (5) to find the voltage drop in 8 AWG copper wire.

Ed(8AWG)=12.9×10×140×216,510=2.187Volts drop2.19Volts drop

Tabulate the calculated value of the voltage drop as shown in Table 1.

Table 1

Sl. No.Conductor SizeVoltage drop
114 AWG8.79Volts drop
212 AWG5.53Volts drop
310 AWG3.48Volts drop
48 AWG2.19Volts drop

Find the value of 3% voltage drop of the applied voltage.

Voltage drop3% applied voltage=3%(120V)=3100(120V)=3.6V

Compare the obtained value of 3% voltage drop of applied voltage with voltage drops of each conductor as tabulated in Table 1.

A voltage drop of 8AWG conductor (that is 2.19 Volts drop) is less than 3% voltage drop of the applied voltage (that is 3.6 Volts drop). Therefore, conductor size with 10 AWG or larger should be installed to accomplish 3% maximum voltage drop.

Conclusion:

Thus, 10 AWG or larger value conductor should be installed to accomplish 3% maximum voltage drop.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
what is the largest size conductor allowed to be used with a wirenut
In the conduit diagram shown in Figure 1–3, determine how many wires are in each conduit between each piece of equipment. Identify each wire terminal connection and the quantity of wires, as shown in the example, above the disconnect switch.
XLPE insulated high voltage underground cable will be installed along a street. The cable will then continue on a street route that cuts the street perpendicularly. Since the cable diameter is 10 cm, what should be the minimum bend radius of the cable?

Chapter 4 Solutions

ELECTRICAL WIRING:RESIDENTAL-6 PLANS

Ch. 4 - For nonmetallic-sheathed cable, may the...Ch. 4 - Prob. 12RCh. 4 - Under what condition may nonmetallic-sheathed...Ch. 4 - a. What is the maximum distance permitted between...Ch. 4 - Prob. 15RCh. 4 - Prob. 16RCh. 4 - Prob. 17RCh. 4 - Prob. 18RCh. 4 - Prob. 19RCh. 4 - Circle the correct answer to the following...Ch. 4 - When running Type NM cable through a bored hole in...Ch. 4 - Where is the main service-entrance panel located...Ch. 4 - Is it permitted to use flexible metal conduit over...Ch. 4 - Liquidtight flexible metal conduit may serve as a...Ch. 4 - It is permissible for an electrician to connect...Ch. 4 - Terminals of switches and receptacles marked...Ch. 4 - Wire connectors marked AL/CU are suitable for use...Ch. 4 - A wire connector bearing no marking or reference...Ch. 4 - When Type NM cable is run through a floor, it must...Ch. 4 - When nonmetallic-sheathed cables are bunched or...Ch. 4 - In diagrams A and B, nonmetallic-sheathed cable is...Ch. 4 - The marking on the outer jacket of a...Ch. 4 - A 120-volt branch circuit supplies a resistive...Ch. 4 - In problem 35, it is desired to keep the voltage...Ch. 4 - Prob. 37RCh. 4 - The allowable ampacity of a 4 AWG THHN from Table...Ch. 4 - If, because of some obstruction in a wall space,...Ch. 4 - The recessed fluorescent luminaires installed in...Ch. 4 - Prob. 41RCh. 4 - What size overcurrent device protects the...Ch. 4 - May the 20-ampere small-appliance branch circuits...Ch. 4 - A 30-ampere branch circuit is installed for an...Ch. 4 - In many areas, metal framing members are being...Ch. 4 - Are set screwtype connectors permitted to be used...Ch. 4 - Most armored cable today has 90C conductors. What...Ch. 4 - If you saw two different types of SE cables, how...Ch. 4 - Circle the correct answer defining the type of...
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Demos: Dielectric breakdown; Author: Caltech's Feynman Lecture Hall;https://www.youtube.com/watch?v=2YrHh1ikefI;License: Standard Youtube License