// State true or false 1. The line currents drawn by a A connected load has no zero sequence components. 2. The relation between the line to line voltage and line to neutral voltage in a three phase system is VL = v2 V-N %3D 3. The positive sequence of a transformer is equal to 3 times its negative sequence reactance.
Q: Consider Figure 1 of the text. For an ideal phase-shifting transformer, the impedance is unchanged…
A: Referring to the given hints, the impedance of the secondary side seen from the primary side:
Q: The operated distfibution transformer has constant iron * and copper losses? False True
A: the operated distribution transformer has constant iron and copper losses true or false
Q: Using various types of transformers, give 1 impact to the end-users per type of transformer in terms…
A: NOTE:- As per our company policy, only FIRST 3 sub-parts of a Question can be answered at a time,…
Q: A three-phase generator step-up transformer i
A:
Q: ngle phase transformer has arated secondary voltage of (230v).when Loaded by a purely inductive load…
A: TRANSFORMER: The transformer transfers power from one circuit to another circuit without a change…
Q: TRUE or FALSE: If a 13800 / 480-V, three-phase transformer is connected wye-delta, then the turns…
A:
Q: Using various types of transformers, give 10 impacts to the end-users per type of transformer in…
A: Transformer: Transformer is the static device that either step-up or step-down the voltage. It works…
Q: Consider Figure 1 of the text. For an ideal phase-shifting transformer, the impedance is unchanged…
A: Whenever the impedance is seen from the other side of the transformer it is given as:
Q: Q3) What are the elements finding from no-load test of single phase transformer?
A: At no load test rated voltage is applied with secondary open circuited. At no load only magnetizing…
Q: The point of common coupling always located at the secondary side of the service transformer. True…
A: Service transformer : A transformer that steps down utility-supplied voltages to voltages that used…
Q: 3. A 100 KVA, 4000V / 200V, 50 Hz single phase transformer has 100 secondary tu Determine (a) the…
A: In this question , we will find currents in both windings , turn and maximum flux..
Q: b) A single-phase transformer with 10: 1 turns-ratio and rated at 50 kVA, 2400-V/240-V, 50-Hz is…
A: (b): Given in the question: Turns ratio: N1N2=101 Voltage on the primary side is: V1 = 2400V Voltage…
Q: Using various types of transformers, give 10 impacts to the end-users per type of transformer in…
A: In this solution physical features, advantages and applications of Autotransformer, Power…
Q: Q2) A 140-kVA, 7500/277-V distribution transformer has the following resistances and reactances: R,…
A: As per the guidelines of Bartley we supposed to answer first three subpart only.
Q: It is possible to connect A-Y transformer in parallel with another A-Y transformer? True O False
A: Is it possible to connect delta star transformer with another delta star transformer in parallel
Q: Derive step by step, the electromotive force equation for a single-phase transformer.
A:
Q: Q2: Draw the circuit diagram, write down the governing equations, and draw the phasor diagram with…
A: Equivalent circuit diagram. Let the turn ratio is a,
Q: a) An ideal single-phase two-winding transformer with turns ratio a, = N1/N2 is con nected with a…
A: A. The basic relation for a single- phase two winding transformer…
Q: "The per unit value of impedance, voltage and current of a transformer are not same regardless of…
A: Per unit value is given as Per unit = actual value / base value
Q: (a) A 5 MVA 230/10.5-kV single-phase power transformer has a per-unit resistance of 1.5% and a…
A:
Q: The % resistance and the % leakage reactance of a 5 kVA, 220 V / 440 V, 50 Hz, single phase…
A: Given values are - Resistance%=3%ResistancePer unit=0.03Reactance%=4%ReactancePer…
Q: Using various types of transformers, give 10 impacts to the end-users per type of transformer in…
A: As per Bartleby policy we can answer only first 3 parts. Please repost the question for other parts.…
Q: 4. A 3-phase transformer, ratio 33/6.6-kV, A/Y, 2-MVA has a primary resistance of 89 per phase and a…
A:
Q: Q.2 (a) Give TWO reasons why we must use transformer in electrical system. (b) A single-phase…
A: a) To reduce transmission line losses, transformers are utilised to boost up the input voltage.…
Q: 60 KVA, 415-220 V, 50 Hz transformer I.(exciting current)=2% of the rated current current at 0.75…
A:
Q: Transformer rated powers and relative short-circuit rates in a step-down transformer station are…
A: For the electrical design of the electrical substation, Short circuit MVA and Short circuit current…
Q: The per-unit system calculations method allows to: Select one: O a. eliminate the need for explicit…
A: Most of human energy requirement is meet by generating electrical energy. Once electrical energy is…
Q: Hw2.1-3: Derive the following: ing. The shift angle of line voltages for delta/star transformer…
A: In a delta-Star connected transformer, the primary is connected in delta and the secondary is…
Q: (a) An ideal single-phase two-winding transformer with turns ratio at = N1/N2 is connected with a…
A: The relation between the single-phase two winding transformers is given as:
Q: Explain the importance of transformer and basic insulation level in the distribution system. Justify…
A: The Basic Insulation Level (BIL) of a transformer is a method of expressing the voltage surge the…
Q: A 5 kVA, 50 Hz single phase transformer has ratio 200/400V. The data taken on the LV side at rated…
A:
Q: Three Phase Transformer connections: Discuss Fully the various methods available for transforming…
A: The methods of transformation of a 3-phase voltage into higher or lower 3-phase voltages is done…
Q: The transformer shown operates at 50Hz with the turn numbers N1=200 and N2=100 for primary and…
A:
Q: Determine the efficiency of three-phase 400 kVA, 11kV/ 380 V transformer at over-loading condition…
A:
Q: Quiz2: We wish to connect a 6 kVA, 120/240 V transformer as an autotransformer to a 120 V source to…
A:
Q: The efficiency of a 20 kVA 15.4 / 0.4 kV three-phase power transformer is 74,1% for a load with…
A: Given: The efficiency of a 20 kVA 15.4/0.4 kV three-phase power transformer is 74.1% for a load with…
Q: Q2: A 5kVA, 200/400V, 50Hz single phase transformer gave the following test figures: No-load:…
A: Given values are = 5kVA, 200/400V, 50Hz single phase transformer. Tests results are = No-load:…
Q: 1. A quantity is expressed in per unit if it is divided by a chosen base quantity having the same…
A: Given, Base power= 10 KW Base Voltage (HV)=2400 V Base voltage (LV)=240 V Base current (LV)=Base…
Q: A transformer of 100MVA, 60Hz, 138/69 kV, works as step down, has the following parameters: r1 =…
A:
Q: The efficiency of a 20 kVA 15.4 / 0.4 kV three-phase power transformer is 75,4% for a load with…
A: Here, Given data 3-ϕ power transformer, Pout=20 KVAVPri=15.4 kVVSec=0.4 kVη=75.4%PF=1 The Short…
Q: Justify if in a Yy transformer (without neutral wire on the supply side) there are homopolar…
A: Here it is mentioned that in a three Yy transformer there are homopolar components of fluxes,…
Q: Example 1: A single-phase, 100-kVA, 1000:100-V, 60-Hz transformer has the following test results:…
A:
Q: 02/A/ What are the conditions for satisfying parallel operation of single phase transformer? Deduce…
A: “Since you have asked multiple questions, we will solve the first question for you. If you want any…
Q: . A 15kVA single-phase transformer, for 10000V/440V at no load, has resistances and leakage…
A: In this question, We need to determine the value of the secondary voltage at full load, 0.85 power…
Q: 12.a. Comparing the transformer cores of core-form and shell-form transformers shows that the a.…
A: Solution of question (12.a): Four options are given, we need to choose the correct option. The…
Q: True or false? An ideal transformer has no real or reactive power loss.
A:
Q: Q1 The oil test condition analysis is the ultimate starting point for any HV transformer assessment.…
A:
Q: When two winding transformer is not connected to the load, primary balancing current flows in the…
A:
Q: Solved Problems: Single-Phase Transformers Problem 1 A 19.2 KVA, 19200/480-V, 60 Hz, single-phase…
A:
Step by step
Solved in 4 steps with 1 images
- Figure 3.39 shows a oneline diagram of a system in which the three-phase generator is rated 300 MVA, 20 kV with a subtransient reactance of 0.2 per unit and with its neutral grounded through a 0.4- reactor. The transmission line is 64km long with a cries reactance of 0.5-/km. The three-phase transformer T1 is rated 350MVA.230/20kV with a leakage reactance of 0.1 per unit. Transformer T2 is composed of three single-phase transformers, each rated 100 MVA, 127/13.2kV with a leakage reactance of 0.1 per unit. Two 13.2kV motors M1 and M2 with a subtransient reactance of 0.2 per unit for each motor represent the load. M1 has a rated input of 200 MVA with its neutral grounded through a 0.4- current-limiting reactor, M2 has a rated input of 100 MVA with its neutral not connected to ground. Neglect phase shifts associated with the transformers. Choose the generator rating as base in the generator circuit and draw the positive-sequence reactance diagram showing all reactances in per unit.Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X1=0.24 (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio =N2/N1=10. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, Va as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.Consider a single-phase electric system shown in Figure 3.33. Transformers are rated as follows: XY15MVA,13.8/138kV, leakage reactance 10 YZ15MVA,138/69kV, leakage reactance 8 With the base in circuit Y chosen as 15MVA,138kV determine the per-unit impedance of the 500 resistive load in circuit Z, referred to circuits Z, Y, and X. Neglecting magnetizing currents, transformer resistances, and line impedances, draw the impedance diagram in per unit.
- The per-unit equivalent circuit of two transformers Ta and Tb connected in parallel, with the same nominal voltage ratio and the same reactan of 0.1 per unit on the same base, is shown in Figure 3.43. Transformer Tb has a voltage-magnitude step-up toward the load of 1.05 times that of Ta (that is, the tap on the secondary winding of Tb is set to 1.05). The load is represented by 0.8+j0.6 per unit at a voltage V2=1.0/0 per unit. Determine the complex power in per unit transmitted to the load through each transformer, comment on how the transformers share the real and reactive powers.Consider the single-Line diagram of a power system shown in Figure 3.42 with equipment ratings given: Generator G1: 50MVA,13.2kV,x=0.15p.u. Generator G2: 20MVA,13.8kV,x=0.15p.u. Three-phase -Y transformer T1: 80MVA,13.2/165YkV,X=0.1p.u. Three-phase Y- transformer T2: 40MVA,165Y/13.8kV,X=0.1p.u. Load: 40MVA,0.8PFlagging,operatingat150kV Choose a base of 100 MVA for the system and 132-kV base in the transmission-line circuit. Let the load be modeled as a parallel combination of resistance and inductance. Neglect transformer phase shifts. Draw a per-phase equivalent circuit of the system showing all impedances in per unit.The ratings of a three-phase, three-winding transformer are Primary: Y connected, 66kV,15MVA Secondary: Y connected, 13.2kV,10MVA Tertiary: connected, 2.3kV,5MVA Neglecting resistances and exciting current, the leakage reactances are: XPS=0.09 per unit on a 15-MVA,66-kV base XPT=0.08 per unit on a 15-MVA,66-kV base XST=0.05 per unit on a 10-MVA,13.2-kV base Determine the per-unit reactances of the per-phase equivalent circuit using a base of 15 MVA and 66 kV for the primary.
- With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a generator, a step-up transformer bank, a transmission line, a stepown transformer bank, and an impedan load. The generator terminal voltage is 15 kV (line-to-line). (a) Draw the per-phase equivalent circuit, aounting for phase shifts for positive-sequence operation. (b) By choosing the line-to-neutral generator terminal voltage as the reference, determine the magnitudes of the generator current, transmiss ion-line current, load current, and line-to-line load voltage. Also, find the three-phase complex power delivered to the load.Consider a bank of this single-phase two-winding transformers whose high-voltage terminals are connected to a three-phase, 13.8-kV feeder. The low-voltage terminals are connected to a three-phase substation load rated 2.0 MVA and 2.5 kV. Determine the required voltage, current, and MVA ratings of both windings of each transformer, when the high-voltage/low- voltage windings are connected (a) Y-, (b) -Y, (c) Y-Y, and (d) -.Three single-phase two-winding transformers, each rated 25MVA,54.2/5.42kV, are connected to form a three-phase Y- bank with a balanced Y-connected resistive load of 0.6 per phase on the low-voltage side. By choosing a base of 75 MVA (three phase) and 94 kV (line-to-line) for the high-voltage side of the transformer bank, specify the base quantities for the low-voltage side. Determine the per-unit resistance of the load on the base for the low-voltage side. Then determine the load resistance RL in ohms referred to the high-voltage side and the per-unit value of this load resistance on the chosen base.
- PowerWorid Simulator case Problem 3_60 duplicates Example 3.13 except that a resistance term of 0.06 per unit has been added to the transformer and 0.05 per unit to the transmission line. Since the system is no longer lossless, a field showing the real power losses has also been added to the oneline. With the LTC tap fixed at 1.05, plot the real power losses as the phase shift angle is varied from 10 to +10 degrees. What value of phase shift minimizes the system losses?Equipment ratings for the five-bus power system shown in Figure 7.15 are as follows: Generator G1:    50 MVA, 12kV, X=0.2 per unit Generator G2: 100 MVA, 15 kV, X=0.2 per unit Transformer T1: 50 MVA, 10 kV Y/138kVY,X=0.10 per unit Transformer T2: 100 MVA, 15 kV /138kVY,X=0.10 per unit Each 138-kV line: X1=40 A three-phase short circuit occurs at bus 5, where the prefault voltage is 15 kV. Prefault load current is neglected. (a) Draw the positive-sequence reactance diagram in unit on a 100-MVA, 15-kV base in the zone of generator G2. Determine (b) the Thévenin equivalent at the fault, (c) the subtransient fault current in per unit and in kA rms, and (d) contributions to the fault from generator G2 and from transformer T2.Equipment ratings for the four-bus power system shown in Figure 7.14 are as follows: Generator G1: 500 MVA, 13.8 kV, X=0.20 per unit Generator G2: 750 MVA, 18 kV, X=0.18 per unit Generator G3: 1000 MVA, 20 kV, X=0.17 per unit Transformer T1: 500 MVA, 13.8/500YkV,X=0.12 per unit Transformer T2: 750 MVA, 18/500YkV,X=0.10 per unit Transformer T3: 1000 MVA, 20/500YkV,X=0.10 per unit A three-phase short circuit occurs at bus 1, where the prefault voltage is 525 kV. Prefault load current is neglected. Draw the positive-sequence reactance diagram in per unit on a 1000-MVA, 20-kV base in the zone of generator G3. Determine (a) the Thévenin reactance in per unit at the fault, (b) the subtransient fault current in per unit and in kA rms, and (c) contributions to the fault current from generator G1 and from line 1-2.