Determine the efficiency of three-phase 400 kVA, 11kV/ 380 V transformer at over-loading condition by 15% of its rated with unity power factor load. The copper and iron losses at full load are 16 kW, 4 kW respectively. b) State one or more of the ways to reduce the losses that taken place in transformers.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter8: Symmetrical Components
Section: Chapter Questions
Problem 8.39P
icon
Related questions
Question

Determine the efficiency of three-phase 400 kVA, 11kV/ 380 V transformer at over-loading
condition by 15% of its rated with unity power factor load. The copper and iron losses at
full load are 16 kW, 4 kW respectively.
b) State one or more of the ways to reduce the losses that taken place in transformers.

Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning