Textbook Question
Chapter 11, Problem 7PP
A bank of electric heaters has a power rating of 25 kW. The heaters are connected to 480 volts. The heaters will operate for more than three hours at a time. The conductors supplying the heaters are to be aluminum with type THWN-2 insulation. The heaters are located in an area with an ambient temperature of
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
Assume a bank of heating strips is rated at 22 KW and is connected to 240 volts. The heat strips operate for 4 hours at a time and are located in an area with an ambient temperature of 86 degrees F. The termination temperature rating of the heat disconnect lugs are unknown. Copper conductors with type THWN-2 insulation are to be used because of the environment of the installation to connect the heaters. What size conductors should be used?
Assume a bank of heating strips is rated at 20 K W and is connected to 240 volts. The heat strips operate for 4 hours ata time and are located in an area with an ambient temperature of 96 degrees F. The termination temperature rating of theheat disconnect lugs is unknown. Three (3) Copper conductors installed in a conduit with type THWN-2 insulation are tobe used to connect the heaters. What size conductors should be used?
Can two 25,000-Btu room air conditioners be wired into the same electricalcircuit protected by a 25-ampere fuse? Each air conditioner is rated at 3,050watts for a 230-volt circuit. (This rating is while the air conditioner is runningsteadily.)
Chapter 11 Solutions
Delmar's Standard Textbook of Electricity (MindTap Course List)
Ch. 11 - What is the maximum temperature rating of Type...Ch. 11 - 2. Name two types of conductor insulation designed...Ch. 11 - A 10 AWG copper conductor with Type THW insulation...Ch. 11 - 4. Six 1/0 aluminum conductors are to be run in a...Ch. 11 - Name five conditions that must be met for running...Ch. 11 - What is the largest solid (nonstranded) conductor...Ch. 11 - Can Type TW cable be used in an area that has an...Ch. 11 - How is the grounded conductor in a flat...Ch. 11 - What three colors are ungrounded conductors not...Ch. 11 - Twenty-five 12 AWG copper conductors are run in...
Ch. 11 - A single-hase load is located 2800 ft from its...Ch. 11 - It is decided to use parallel 0000 conductors to...Ch. 11 - A three-phase motor operates on 480 V and is...Ch. 11 - You have been hired by a company to connect an...Ch. 11 - 2. You are a journeyman electrician in an...Ch. 11 - You are an electrician working in an industrial...Ch. 11 - Using the above example, determine the wire size...Ch. 11 - 1. A 2 AWG copper conductor is 450 ft long. What...Ch. 11 - 2. An 8 AWG conductor is 500 ft long and has a...Ch. 11 - 3. Three 500-kcmil copper conductors with Type RHH...Ch. 11 - 4. Eight 10 AWG aluminum conductors with Type THWN...Ch. 11 - 5. A three-phase motor is connected to 480 V and...Ch. 11 - 6. A 50-hp DC motor is connected to 250 volts. The...Ch. 11 - 7. A bank of electric heaters has a power rating...Ch. 11 - A 15-hp squirrel-cage induction motor is connected...Ch. 11 - Determine the resistance of a 16 AWG copper...Ch. 11 - Determine the ohms-per-mil-foot of an aluminum...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- A certain type of control connects electric heating units to a 120-volt supply or a 240-volt supply, depending on the amount of the temperature drop in a room. These controls are supplied from a 120/240-volt, 3-wire, single-phase source. Assuming that this type of device controls a 240-volt, 2000-watt heating unit, what is the wattage produced when the control supplies 120 volts to the heating unit? Show all calculations. ______________________________________________________________________ ______________________________________________________________________arrow_forwardAn electric dryer is rated at 7.5 kW and 120/240 volts, 3-wire, single-phase. The terminals on the dryer and panelboard are marked 75C. a. What is the wattage rating? ___________ b. What is the current rating? ___________ c. What minimum size type THHN copper conductors are required? ___________ d. If EMT is used, what minimum size is required? ___________arrow_forward8. What is the maximum load to be connected to a single receptacle rated at 20A?arrow_forward
- DETERMINE THE PROPER SIZE CONDUCTORS for a 500 watt load that is located 100 ft from a 250 volt panelboard the permissable line drop is 2 volts and k=12.6arrow_forwardEighty 16 AWG copper conductors with type THWN-2 insulation are to be run in a conduit. The conduit used in an area that has an ambient temperature of 120 F. What is the maximum ampacity of these conductors?arrow_forwardHow many lighting branch circuits are provided in this dwelling? __________ a. What is the minimum load allowance for small-appliance circuits for dwellings? See NEC 220.52(A). __________ b. An individual 15-ampere branch circuit is run to the receptacle outlet behind the refrigerator instead of connecting it to one of the two 20-ampere small-appliance branch circuits that are required in kitchens. For this separate circuit, an additional 1500 volt-amperes (shall) (does not have to) be added to the load calculations for dwellings. (Circle the correct answer.)arrow_forward
- Show the connections for a ceiling outlet that is to be controlled from any one of three switch locations. The 120-volt feed is at the light. Use colored pens or pencils. Assume the installation is in cable.arrow_forwardA central air-conditioning unit is rated at 4,100 watts. The unit uses 230 volts.How many amperes of current does the electrical cable for this unit carrywhen current is flowing?arrow_forwardThe branch circuit supplying a fixed electric space heater must be sized to at least ___________ percent of the heaters rating according to NEC ________________.arrow_forward
- Refer to the specifications in the back of this text following Chapter 33. a. What electrical codes must be conformed to? ________________________________________________________________________ ________________________________________________________________________ ________________________________________________________________________ b. What is the wiring method to be used in the workshop? ________________________________________________________________________ c. What size conductors are to be used for the lighting branch circuits? ______________________ AWG the small-appliance branch circuits? ______________________ AWG d. What section of the specifications tells us the size of the service entrance to be installed for this residence?arrow_forwardIs it permissible to use standard 60C insulated conductors to connect all counter-mounted cooking units? ___________________________________________________ Why? ________________________________________________________________arrow_forwardDetermine the proper size of copper wire conductor necessary to apply a 750 W electric motor that is located 100 feet from the panel board. The voltage at the panelboard is 120 volts. The permissible line drop is 1.2 volts. (for your final answer: no decimal places and unit to have one common answer)arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Delmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningEBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
What is an electric furnace and how does it work?; Author: Fire & Ice Heating and Air Conditioning Inc;https://www.youtube.com/watch?v=wjAWecPGi0M;License: Standard Youtube License