Concept explainers
A professional center is supplied by a balanced three-phase source. The center has four balance three-phase loads as follows:
Load 1: 150 kVA at 0.8 pf leading
Load 2: 100 kW at unity pf
Load 3: 200 kVA at 0.6 pf lagging
Load 4: 80 kW and 95 kVAR (inductive)
If the line impedance is 0.02 + j0.05 Ω per phase and the line voltage at the loads is 480 V, find the magnitude of the line voltage at the source.
Find the magnitude of the line voltage at the source.
Answer to Problem 81CP
The magnitude of the line voltage at the source is
Explanation of Solution
Given data:
A balanced three-phase source connected to four balanced three-phase loads, Those are,
Load 1:
The apparent power of the Load 1
The power factor of the Load 1 is
Load 2:
The real power of the Load 2
The power factor of the Load 2 is unity.
Load 3:
The apparent power of the Load 3
The power factor of the Load 3 is 0.6 (lagging).
Load 4:
The reactive power of the Load 4
The real power of the Load 4
The line impedance
The line voltage at the loads
Formula used:
Write the expression to find the complex power of the Load 1.
Here,
Write the expression to find the real power of the Load 1.
Here,
Write the expression to find the reactive power of the Load 1.
Here,
Write the expression to find the complex power of the Load 2.
Here,
Write the expression to find the real power
Here,
Rearrange the equation (5) to find the apparent power
Write the expression to find the reactive power
Here,
Write the expression to find the complex power of the Load 3.
Here,
Write the expression to find the real power of the Load 3.
Here,
Write the expression to find the reactive power of the Load 3.
Here,
Write the expression to find the complex power of the Load 4.
Here,
Write the expression to find the total complex power
Here,
Write the expression to find the apparent power (S).
Here,
Write the expression to find the complex power absorbed by the line.
Here,
Write the expression to find the total complex power at the source.
Here,
Write the expression for the apparent power
Here
Calculation:
Load 1:
The given leading power factor of the Load 1 is ,
Re-write the equation to find the angle
Substitute
Substitute
Substitute
Load 2:
Substitute
The given unity power factor of the Load 2,
Rewrite the equation to find the angle
Substitute
Substitute
Load 3:
The given lagging power factor of the Load 3 is,
Rewrite the equation to find the angle
Substitute
Substitute
Substitute
Load 4:
Substitute
Substitute
Here, the apparent power is
Substitute
Re-write the above equation to find the line current
Substitute
Substitute
Re-write the above value as below,
Substitute
Rewrite the above equation to find
Conclusion:
Thus, the magnitude of the line voltage at the source is
Want to see more full solutions like this?
Chapter 12 Solutions
Fundamentals of Electric Circuits
- A three-phase line with an impedance of (0.2+j1.0)/ phase feeds three balanced three-phase loads connected in parallel. Load 1: Absorbs a total of 150 kW and 120 kvar. Load 2: Delta connected with an impedance of (150j48)/phase. Load 3: 120 kVA at 0.6 PF leading. If the line-to-neutral voltage at the load end of the line is 2000 v (rms), determine the magnitude of the line-to-line voltage at the source end of the line.arrow_forwardConsider a three-phase Y-connected source feeding a balanced- load. The phasor sum of the line currents as well as the neutral current are always zero. (a) True (b) Falsearrow_forwardTwo balanced Y-connected loads, one drawing 10 kW at 0.8 power factor lagging and the other IS kW at 0.9 power factor leading, are connected in parallel and supplied by a balanced three-phase Y-connected, 480-V source. (a) Determine the source current. (b) If the load neutrals are connected to the source neutral by a zero-ohm neutral wire through an ammeter, what will the ammeter read?arrow_forward
- A single-phase source is applied to a two-terminal, passive circuit with equivalent impedance Z=3.045, measured from the terminals. The source current is i(t)=22cos(t)kA. Determine the (a) instantaneous power, (b) real power, (c) reactive power delivered by the source, and (d) source power factor.arrow_forwardThree loads are connected in parallel across a single-phase source voltage of 240V(RMS). Load 1 absorbs 15 kW and 6.667 kvar; Load 2 absorbs 3 kVA at O.96PF leading; Load 3 absorbs 15 kW at unity power factor. Calculate the equivalent impedance, Z, for the three parallel loads, for two cases: (i) Series combination of R and X, and (ii) parallel combination of R and X.arrow_forwardIn a balanced system, the phasor sum of the line-to-line voltages and the phasor sum of the line-to-neutral voltages are always equal to zero. (a) False (b) Truearrow_forward
- It is stated that (i) balanced three-phase circuits can be solved in per unit on a per-phase basis after converting - load impedances to equivalent Y impedances. (ii) Base values can be selected either on a per-phase basis or on a three-phase basis. (a) Both statements are true. (b) Neither is true. (c) Only one of the above is true.arrow_forwardTwo three-phase generators supply a three-phase load through separate three-phase lines. The load absorbs 30 kW at 0.8 power factor lagging. The line impedance is (1.4+j1.6) per phase between generator G1 and the load, and (0.8+j1) per phase between generator G2 and the load. If generator G1 supplies 15 kW at 0.8 poir factor lagging, with a terminal voltage of 460 V line-to-line, determine (a) the voltage at the load terminals. (b) the voltage at the terminals of generator G2, and (c) the real and reactive power supplied by generator G2. Assume balanced operation.arrow_forwardA balanced three-phase distribution line has an impedance of (1 +j8)ohm/phase .This line is used to supply three balanced three-phase loads that are connected in parallel. The three loads are:Load I: S1/phase = 40kVA at a power factor of 0.96 leading.Load 2: S2/phase = 60 kVA at a power factor of 0.8 lagging.Load 3: P3/phase= 33.6 kW and Q3/phase = 5.2 kVAR.The magnitude of the phase-to-neutral voltage at the terminals of the loads is2400 V (rms)and is considered as phase reference. A)find the complex apparent power per phase at the source end of the linearrow_forward
- A balanced three-phase distribution line has an impedance of (1 +j8)ohm/phase .This line is used to supply three balanced three-phase loads that are connected in parallel. The three loads are:Load I: S1/phase = 40kVA at a power factor of 0.96 leading.Load 2: S2/phase = 60 kVA at a power factor of 0.8 lagging.Load 3: P3/phase= 33.6 kW and Q3/phase = 5.2 kVAR.The magnitude of the phase-to-neutral voltage at the terminals of the loads is2400 V (rms)and is considered as phase reference.a) Find the total complex apparent power per phase STotal/phaseb)Draw the single phase equivalent circuit.c)What is the magnitude of the phase-to-neutral voltage at the sending end of the line?d)Find the complex apparent power per phase at the source end ofthe line.arrow_forwardThe following three parallel-connected three-phase loads are fed by a balanced three-phase source: Load 1: 250 kVA, 0.8 pf lagging Load 2: 300 kVA, 0.95 pf leading Load 3: 450 kVA, unity pf If the line voltage is 13.8 kV, calculate the line current and the power factor of the source. Assume that the line impedance is zero.arrow_forwardIt is powered from a grounded Y-balanced three-phase source. The installations have four balanced three-phase loads: Load 1: 150 kVA Y with pf 0.8 (+), Load 2: 100 kW ∆ with pf 1.0, Load 3: 120 kW Y with pf 0.6 (-), Load 4: 80 kW and 95 kVAR (inductive - ∆). If the line impedance is 0.02 + j0.05 Ω per phase and the line voltage across the loads is 480 V, find the magnitude of the line and phase voltages at the source. Draw the phasor diagram of the voltages.arrow_forward
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning