Question
Chapter 20, Problem 1RQ
To determine
The operation of the circuit 2 if contact M1 did not close.
Expert Solution & Answer
Explanation of Solution
Consider the contact M1 is not closed and the current do not flow through the auxiliary contact and to the motor starter, then to the relay coil TR1. Thus, the motor 1 do not operate and the timer delay coil TR1 is DE energized. Since, the de-energized coil fails to close the contact of the TR1 the motor 2 do not starts.
Consider that the motor M2 is in the off state so the timer delay coil TR2 is not energized and the contacts of the TR2 is closed so the motor M3 fails to operate.
Thus, the case when the contact M1 are open the three motors M1, M2 and M3 do not work.
Want to see more full solutions like this?
Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
The problem is in the photo
Bending Tool
Problem:
Sheet metal is to be bended on a pneumatically actuated bending rig. After it has been
clamped the piece is initially bent by a double-acting cylinder A and subsequently bent
into the finished form by cylinder B. The sequence is initiated manually by a push button.
The circuit must be so constructed that each time a start signal is given a full cycle is
completed.
Draw the pneumatic circuit diagram of the given problem
Positional Sketch:
Help me solve this question ASAP !!
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.Similar questions
- Refer to the circuit shown in Figure 33–11. Explain the action of the circuit if coil 2CR is shorted and the second speed push button is pressed.arrow_forwardA single-acting cylinder of 25 mm diameter is to clamp a component when a push button is pressed. As long as the push button is activated, the cylinder is to remain in the clamped position. If the push button is released, the clamp is to retract. Draw the circuit diagram for the problem.arrow_forwardQ1 ---- - Reduce the combinational logic circuit in figure 1 to minimum form. Figure 1 B C Darrow_forward
- Refer to the circuit shown in Figure 5-29. In this circuit, the HR contactor is equipped with five contacts. Three are load contacts and two are auxiliary contacts. From looking at the schematic diagram, how is it possible to identify which contacts are the load contacts and which are the auxiliary contacts? Figure 5-29 The contactor contains both load and auxiliary contacts.arrow_forwardRefer to the circuit shown in Figure 25–5. Assume that timer TR1 is set for a delay of 10 seconds and timer TR2 is set for a delay of 5 seconds. When the START button is pressed, the motor starts. After 10 seconds the S1 contacts open and the motor continues to accelerate, but never reaches full speed. After a delay of about 30 seconds, the motor trips out on overload. Which of the following could cause this problem? TR1 coil is open. S2 coil is open. S1 coil is open. R coil is open.arrow_forwardDefine IPM.arrow_forward
- HW 4 Eind the luplace for the following inverse S-4 45 - 24 S + 6Iarrow_forwardIn relation to the circuit presented below, mark the alternative(s) that you consider correct. 1 To enable actuator A2 to advance, it is necessary to switch valve V2 to the leftmost position and ensure that valve V1 is in its initial (intermediate) position. 2 Switching valve V2 to the leftmost position allows actuator A2 to advance, but for this to happen, valve V1 must also be switched to the leftmost position. 3 When activating valve V1, using the locking lever installed on the left side of it, the two actuators (A1 and A2) are allowed to advance. 4 Hydraulic pump B1 is a simple variable displacement type. 5 Valves V1 and V2 have a TANDEM center.arrow_forwardRefer to the circuit shown in Figure 42–21. Assume that a fused jumper is connected across terminals 1 and 3 of TR2 timer. What would happen if the jumper were left in place and the FIRST SPEED push button pressed? The motor would start in its lowest speed and progress to second speed, but never increase to third speed. The motor would start operating immediately in third speed. The motor would not start. The motor would start in second speed and then increase to third speed.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Understanding Motor ControlsMechanical EngineeringISBN:9781337798686Author:Stephen L. HermanPublisher:Delmar Cengage LearningElectrical Transformers and Rotating MachinesMechanical EngineeringISBN:9781305494817Author:Stephen L. HermanPublisher:Cengage LearningRefrigeration and Air Conditioning Technology (Mi...Mechanical EngineeringISBN:9781305578296Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill JohnsonPublisher:Cengage Learning
- Precision Machining Technology (MindTap Course Li...Mechanical EngineeringISBN:9781285444543Author:Peter J. Hoffman, Eric S. Hopewell, Brian JanesPublisher:Cengage Learning
Understanding Motor Controls
Mechanical Engineering
ISBN:9781337798686
Author:Stephen L. Herman
Publisher:Delmar Cengage Learning
Electrical Transformers and Rotating Machines
Mechanical Engineering
ISBN:9781305494817
Author:Stephen L. Herman
Publisher:Cengage Learning
Refrigeration and Air Conditioning Technology (Mi...
Mechanical Engineering
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:Cengage Learning
Precision Machining Technology (MindTap Course Li...
Mechanical Engineering
ISBN:9781285444543
Author:Peter J. Hoffman, Eric S. Hopewell, Brian Janes
Publisher:Cengage Learning