Q10-The full-load copper loss on the H.V. side of 100KVA, 11000/317 V, single-phase transformer is o.62 Kw and on the L.V. side is 0.48 kW. i) Calculate R1 ,R2 in ohms ii) Find X1 ,X2,if the total reactance is 4% ,and the reactance is divided in same proportion as resistance.
Q: A load of 1400 KVA at 0.866 pf lagging is supplied by a 3-phase transformer of 1,000 KVA and 500 KVA…
A:
Q: 1. A 100-kVA distribution transformer has a maximum efficiency of 98 % at 50 % full-load and unity…
A: Efficiency η=98% power factor cosϕ=1
Q: A single-phase power system consists of a 400-V 60-Hz generator that is connected to the load Zload…
A: Given data: Vs=400 Vf=60 HzZL=10+j20 ΩZline=0.2+j0.8 ΩN=35
Q: 1. Cotabato Light and Power Company supplies two-single phase transformers at San Pablo Area banked…
A: As per Bartleby guidelines we are allowed to solve only one question, please ask the rest again.
Q: Find the size of wire in circular mils needed in each winding of a 10-kVA 2400/240-V 60-Hz…
A: There are two independent questions. We are authorized to answer one question at a time, since you…
Q: In a 30kVA, 2000/220V power transformer, the iron and full load copper losses are 400W and 450W…
A:
Q: 2. The number of turns on the primary and secondary windings of a single-phase transformer are 350…
A: This question belongs to electrical machine . It is based on the concept of single phase transformer…
Q: A star connected load with real impedance ZL= 1-j1 Ohm per phase is connected to the secondary of a…
A: The given data about a three phase YNyn0 connected transformer is: Star connected load is connected…
Q: A 1-phase transformer has a no-Load power input of 250W, when supplied at 250V, 50Hz has pf of 0.25.…
A:
Q: A single phase transformer with a ratio of 6600/600 V has a load impedance of (4+ j3)ohms connected…
A:
Q: 1. A large power plant generates electricity at 12.0 kV. Its old transformer once converted the…
A:
Q: 29: For the ide al transformer circuit shown, find th average power delivered to (1Q) resistor?…
A:
Q: A 2000-kVA, 6,600/400-V, 3-phase transformer is delta-connected on the high Example voltage side and…
A:
Q: The shown distribution network is to supply two factories A & B with load curves indicated. Assume…
A: Note: We are authorized to answer three subparts at a time, since you have not mentioned which part…
Q: Find the all-day efficiency of a 500 kVA distribution transformer whose copper loss and iron loss at…
A:
Q: Calculate the daily efficiency of a single-phase joule with an output power of 350 kilovolts-ampere…
A:
Q: A simple power system diagram is given below. The system consists of a 120/0 volt generator…
A: Steps: Shift line and load impedance into the Generator side Convert into Pu Zpu=ZactualV2P…
Q: Day loading duty-cycle profile of a 100 kVA, 2400/240 V, 50 Hz transformer is given below. The SC…
A:
Q: Q1) A 22 kVA, 2200/220 V, 50 Hz single-phase transformer's low voltage side is short-circuited and…
A:
Q: Determine the all-day efficiency of a 10 KVA 2220/220V 60 Hz transformer. During a day of 24 hours,…
A:
Q: Day loading duty-cycle profile of a 100 kVA, 2400/240 V, 50 Hz transformer is given below. The SC…
A: By definition, the all-day efficiency of a transformer is given by: ηall-day=Output kWh in 24…
Q: Q5: A 30 kVA transformer has the iron loss and full load copper loss of 350 and 650 W, respectively.…
A:
Q: Example 32.82. Find "all day" efficiency of a transformer having maximum efficiency of 98 % at 15…
A: We need to find all day efficiency of the given transformer
Q: 12. A 600 kVA, 1-ph transformer has an efficiency of 92 % both at full-load and half-load at unity…
A:
Q: A 20 kVA, 220 V / 110 V, 50 Hz single phase transformer has full load copper loss = 200W and core…
A:
Q: 8. The two winding transformer and the autotransformer of the circuit shown in Figur Determine the…
A: given transformer and autotransformer
Q: Data obtained from short circuit and open circuit tests of a 75-kVA, 4600-230 V, 60 Hz transformer…
A: Open circuit test The power factor is PF=cosϕ=POCVOC×IOC=52230×13.04=0.017 lagging The admittance is…
Q: 1. The equivalent circuit impedances of a single phase 10-KVA, 480/120 V, 60 Hz transformer are to…
A:
Q: 2 (a) Why the primary winding of the distribution transformer used in electrical installation in…
A:
Q: 6. 150 kVA, 2800-240 V, 50 Hz transformer. Reg.Ls = 0.0082N , Xeq.Ls = 0.02230 Step down transformer…
A: Note: We are authorized to answer three subparts at a time since you have not mentioned which part…
Q: 1. A 100-kVA distribution transformer has a maximum efficiency of 98 % at 50 % full-load and unity…
A: As per our company guidelines we are supposed to answer only first one question. Kindly repost other…
Q: a three-phase step-down transformer with 150 kVA, 2080/208 V 60 Hz Y / Y connected R1 = 0.45 ohm, X1…
A:
Q: Shown in the following table are the 15 min kW demands for two customers between the hours of 17:00…
A: Bartleby has policy to solve only first question and if it has subparts then solve only first 3…
Q: 01 A 10 kVA, 500/2000 V, single-phase, 50 Hz transformer gave the following test results : 500 V at…
A: In this solution the concepts related to the SC & OC tests of a transformer is discussed. Given…
Q: A 50 Hz, 110 kVA single phase transformer has a voltage ratio of 11000/440 V. The iron loss measured…
A: Given transformer of50 Hz, 110 kVA ,11000/440 vThe iron loss is Pi=1100 wThe full load copper load…
Q: The shown distribution network is to supply two factories A & B with load curves indicated. Assume…
A: We are authorized to answer three subparts at a time, since you have not mentioned which part you…
Q: The shown distribution network is to supply two factories A & B with load curves indicated. Assume…
A: given peak load of A=400KVApeak load of B=400KVApower factor=0.8
Q: The shown distribution network is to supply two factories A & B with load curves indicated. Assume…
A: Hello. Since your question has multiple sub-parts, we will solve the first three sub-parts for you.…
Q: Q2) A 1.5 KVA, 220/110V, single-phase transformer has the following test data: Open circuit test:…
A:
Q: 6. 150 kVA, 2800-240 V, 50 Hz transformer. Req.Ls Step down transformer delivers 135 kW to a load at…
A: “Since you have posted a question with multiple subparts, we will solve the first three subparts for…
Q: Provide an analysis for the transformer mentioned below. The followings are the reading from the…
A: Note: We are authorized to answer three subparts at a time, since you have not mentioned which part…
Q: determine (i) the core loss current(Ic) (ii) the power factor on no-load and (iii) the magnetizing…
A: Given,the measurement is taken while the secondary of transformer is open circuited. So we can say…
Q: Example 32.72. A 300-kVA, single-phase transformer is designed to have a resistance of 1.5% and…
A:
Q: 2. Given three identical ideal single-phase transformers with each rated at 100KVA and 7kV/3.5kV,…
A:
Q: Example: A 50 kVA distribution transformer has iron loss of 600W and full-load copper loss of 700w.…
A:
Q: 10. The phase current produced by a certain 240V, Y-connected generator is 12A. The corresponding…
A: QUESTION 1. The phase current produced by a certain 240V, Y-connected generator is 12A. The…
Q: equivalent series impedance 62 + j388 mN referred to the low-voltage winding. 1. A three-phase short…
A: Given data, Rating P=25 MVA Impedance ZEQL=62+j388 mΩ a) The rated current on the low voltage side…
Q: A single-phase ideal transformer is rated at 1OKVA, 240V/120V. Calculate the following: a. Rated…
A:
Q: 9. A 10-kVA, 2000/400-V, single-phase transformer has resistances and leakage reactances as follows:…
A: Given, Primary voltage, V1 = 2000 V Secondary voltage, V2 = 400 V So, transformation ratio,…
Q: Q1. A single-phase transformer rated 1.2kV/120 V, 7.2 kVA yields the following test results;…
A:
Trending now
This is a popular solution!
Step by step
Solved in 2 steps with 2 images
- A single-phase 100-kVA,2400/240-volt,60-Hz distribution transformer is used as a step-down transformer. The load, which is connected to the 240-volt secondary winding, absorbs 60 kVA at 0.8 power factor lagging and is at 230 volts. Assuming an ideal transformer, calculate the following: (a) primary voltage, (b) load impedance, (c) load impedance referred to the primary, and (d) the real and reactive power supplied to the primary winding.A two-winding single-phase transformer rated 60kVA,240/1200V,60Hz, has an efficiency of 0.96 when operated at rated load, 0.8 power factor lagging. This transformer is to be utilized as a 1440/1200-V step-down autotransformer in a power distribution system. (a) Find the permissible kVA rating of the autotransformer if the winding currents and voltages are not to exceed the ratings as a two-winding transformer. Assume an ideal transformer. (b) Determine the efficiency of the autotransformer with the kVA loading of part (a) and 0.8 power factor leading.A single-phase two-winding transformer rated 90MVA,80/120kV is to be connected as an autotransformer rated 80/200kV. Assume that the transformer is ideal. (a) Draw a schematic diagram of the ideal transformer connected as an autotransformer. showing the voltages, currents, and dot notation for polarity. (b) Determine the permissible kVA rating of the autotransformer if the winding currents and voltages are not to exceed the rated values as a two-winding transformer. How much of the kA rating is transferred by magnetic induction?
- What are the benefits of microgrids?Three single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance Xeq=0.10perunit, are connected to form a three-phase bank. The high-voltage windings are connected in Y with a solidly grounded neutral. Draw the per-unit equivalent circuit if the low-voltage windings are connected (a) in with American standard phase shift or (b) in Y with an open neutral. Use the transformer ratings as base quantities. Winding resistances and exciting current are neglected.A single-phase 50-kVA,2400/240-volt,60-Hz distribution transformer is used as a step-down transformer at the load end of a 2400-volt feeder whose series impedance is (1.0+j2.0) ohm. The equivalent series impedance of the transformer is (1.0+j2.5) ohms referred to the high-voltage (primary) side. The transformer is delivering rated load at a 0.8 power factor lagging and at a rated secondary voltage. Neglecting the transformer exciting current, determine (a) the voltage at the transformer primary terminals, (b) the voltage at the sending end of the feeder, and (c) the real and reactive power delivered to the sending end of the feeder.
- A 400-turns auto transformer, operating in the step-down mode with 25 percent tap supplies a 4.8 kVA, 0.85 lagging power factor load. The input to the transformer is 2400 V, 60 Hz. Neglect the small losses and leakage effects. What will be the apparent power(in kVA) conducted and transformed respectively?A 15kVA, 440V, single-phase alternator draws a field current of 5A at rated load. With the same field current, the open circuit emf and short-circuit current are 100V and 80A respectively. The ohmic resistance of the armature between terminals is 0.12 ohm. The ratio of effective to ohmic resistance maybe taken as 1.1. Determine the voltage regulation (in %) when the load is purely resistive.A Step-Down Transformer. A transformer connected to a 120 V (rms) ac line is to supply 12.0 V (rms) to a portable electronic device. The load resistance in the secondary is 5.00 Ω. (a) What should the ratio of primary to secondary turns of the transformer be? (b) What rms current must the secondary supply? (c) What average power is delivered to the load? (d) What resistance connected directly across the 120 V line would draw the same power as the transformer? Show that this is equal to 5.00 Ω times the square of the ratio of primary to secondary turns.
- A transformer with a 10:1 ratio and rated at 60kVA, 2200/220V, 60Hz is used to step down the voltage of a distribution system. The low tension voltage is to kept constant at 220V. (a) What load Impedance connected to the low-tension side will be loading the transformer fully at 0.8 power factor (lag) ? (b) What is the value of this impedance referred to the high tension side?Incremental fuel costs in dollars per megawatthour for a plant consisting of two units are given by:dC(P)/dP = 0.0080 P1 + 8.0dC(P)/dP = 0.0096 P2 + 6.4Assume that both units are operating at all times, that total load varies from 250 to 1250 MW, and that maximum and minimum loads on each unit are to be 625MW and 100MW respectively. Find the incremental fuel cost and the allocation of load between units for the minimum cost of various total loads.Write your answers in the given format below.How to generate 480V three phase 400Hz ac from 230V three phase 60Hz ac source? (Please specify the power components you pick, such as transformers, dc-dc converter, dc-ac converter and/or ac-dc converter, how these components are connected and the key parameters of these components, such as the turns ratio of transformer and the duty cycle functions for the converters.)