List the proper trade size of electrical metallic tubing for the following. Assume that THHN insulated conductors are used. See Chapter 9, Table C1, NEC.

  1. a. Three 14 AWG ___________________
  2. b. Four 14 AWG ___________________
  3. c. Five 14 AWG ___________________
  4. d. Six 14 AWG ___________________
  5. e. Three 12 AWG ___________________
  6. f. Four 12 AWG ___________________
  7. g. Five 12 AWG ___________________
  8. h. Six 12 AWG ___________________
  9. i. Six 10 AWG ___________________
  10. j. Four 8 AWG ___________________

(a)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for three 14 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for three 14 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that three 14 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for three 14 AWG THHN conductors.

(b)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for four 14 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for four 14 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that four 14 AWG THHN conductors require trade size 12 EMT. The EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for four 14 AWG THHN conductors.

(c)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for five 14 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for five 14 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that five 14 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for five 14 AWG THHN conductors.

(d)

Expert Solution
Check Mark
To determine

Find the trade size EMT is required for six 14 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for six 14 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that six 14 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for six 14 AWG THHN conductors.

(e)

Expert Solution
Check Mark
To determine

Find the trade size EMT is required for three 12 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for three 12 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that three 12 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for three 12 AWG THHN conductors.

(f)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for four 12 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for four 12 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that four 12 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for four 12 AWG THHN conductors.

(g)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for five 12 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for five 12 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that five 12 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for five 12 AWG THHN conductors.

(h)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for six 12 AWG THHN conductors.

Answer to Problem 18R

The trade size 34 EMT is required for six 12 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that six 12 AWG THHN conductors require trade size 34 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 34 EMT is required for six 12 AWG THHN conductors.

(i)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for six 10 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for six 10 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that six 10 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for six 10 AWG THHN conductors.

(j)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for four 8 AWG THHN conductors.

Answer to Problem 18R

The trade size 34 EMT is required for four 8 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that four 8 AWG THHN conductors require trade size 34 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 34 EMT is required for four 8 AWG THHN conductors.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
The alternative formula used to determine the proper size wire for most installations needs a value for TA. What does TA stand for?
Which of the following statements about equipment grounding conductors (EGCs) is true?A. The National Electrical Code permits the EGC to also perform as a grounding electrode conductor.B. More than one EGC must be used if multiple circuits are installed in a single raceway, cable, or cable tray.C. No current should be present in the EGC during normal operation.D. EGCs are required to be decreased in size to address voltage drop.
10.a. Which of the following is a condition of the exception that allows the grounded conductor of feeders tobe used for grounding at separate buildings or structures?A. There are common electrically continuous metallic paths between the feeder source and the destination at the structure served.B. There are common electrically continuous nonmetallic paths between the equipment grounding conductor and the destinationat the structure served.C. An equipment grounding conductor isn't included with the supply circuit to the separate structure.D. Ground-fault protection of equipment is provided on the supply side of the feeder.10.b. A service disconnection means must be installed adjacent to, within sight of, and no more than_______ feet from a mobile home.A. 20B. 30C. 10D. 50
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Types of House Wiring - Types of Electrical Wiring - Electrical Wiring; Author: Learning Engineering;https://www.youtube.com/watch?v=A5P-buWX-dA;License: Standard Youtube License