Industrial Motor Control
7th Edition
ISBN: 9781133691808
Author: Stephen Herman
Publisher: Cengage Learning
expand_more
expand_more
format_list_bulleted
Concept explainers
Textbook Question
Chapter 2, Problem 6RQ
If you were installing the circuit in Figure 2–22, what type of push button would you use for the silence button?
- a. Normally closed
- b. Normally open
Expert Solution & Answer
Trending nowThis is a popular solution!
Chapter 2 Solutions
Industrial Motor Control
Ch. 2 - Prob. 1RQCh. 2 - The symbol shown is: a. Normally closed float...Ch. 2 - The symbol shown is a(n)
iron core...Ch. 2 - The symbol shown is: a. Normally open pressure...Ch. 2 - The symbol shown is: a. Double acting push button...Ch. 2 - If you were installing the circuit in Figure 2–22,...Ch. 2 - Referring to the circuit in Figure 222, should the...Ch. 2 - Prob. 8RQCh. 2 - Prob. 9RQCh. 2 - When reading a schematic diagram, are the control...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.Similar questions
- Refer to the circuit shown in Figure 109. In this circuit the jog push button has again been connected incorrectly. The normally closed section of the button has been connected in series with the normally open run push button and the normally open section of the jog button is connecting in parallel with the holding contacts. Explain how this circuit operates.arrow_forwardThe two STOP push buttons in Figure 8–2 are connected in series with each other. What would be the action of the circuit if they were to be connected in parallel as shown in Figure 8–6?arrow_forwardRefer to the circuit shown in Figure 108. In this circuit, the jog button has been connected incorrectly. The normally closed section has been connected in parallel with the run push button and the normally open section has been connected in series with the holding contacts. Explain how this circuit operates.arrow_forward
- To answer the following questions refer to the circuit shown in Figure 41–10. Assume that the third speed push button is pressed. Explain the sequence of operation for the circuit.arrow_forwardRefer to the circuit shown in Figure 5-29. Is the thermostat contact normally open, normally closed, normally closed held open, or normally open held closed? Figure 5-29 The contactor contains both load and auxiliary contacts.arrow_forwardTo answer the following questions refer to the circuit in Figure 416. The pressure switch is shown as: a. Normally open b. Normally closed c. Normally open held closed d. Normally closed held openarrow_forward
- Refer to the circuit shown in Figure 16-11. Assume that the platform is located on the lower floor. When the UP push button is pressed, the platform rises. When the platform reaches the upper floor, however, the pump does not turn off but continues to run until the overload relay opens the overload contacts. Which of the following could cause this problem? a. The solenoid valve opened when limit switch LS1 opened. b. The UP push button is shorted. c. Limit switch LS1 did not open its contacts. d. Limit switch LS2 contacts did not reclose when the platform began to rise.arrow_forwardRefer to the circuit shown in Figure 16-11. Assume that the platform is located on the bottom floor. When the UP push button is pressed the pump motor does not start. Which of the following could not cause this problem? The contacts of limit switch LS1 are open. The contacts of limit switch LS2 are open. Motor starter coil M is open. The overload contact is open.arrow_forwardRefer to the circuit shown in Figure 97. Assume that when the forward push button is pressed the motor does not start, but when the reverse push button is pressed the motor will start in the reverse direction. When the stop button is pressed the motor stops running. Which of the following could NOT cause this problem? a. The forward push button is defective. b. The F starter coil is open. c. The overload auxiliary contact is open. d. The normally closed R contact is open.arrow_forward
- Refer to the circuit shown in Figure 33–7. When the low speed push button is pressed, the motor begins to run in low speed. When the high speed push button is pressed, the motor stops running. Which of the following could cause this problem? The 1L contactor coil is open. H contactor coil is open. PR relay coil is open. The 2L contactor coil is open.arrow_forwardRefer to the circuit shown in Figure 107. Assume that when the start button is pressed the motor does not start, but when the inch push button is pressed the motor runs at reduced speed. Which of the following could NOT cause this problem? a. The control transformer fuse is blown. b. M starter coil is defective. c. The start push button is defective. d. The stop push button is defective.arrow_forwardRefer to the circuit shown in Figure 42–17. Assume that the motor is running in the forward direction. When the revers e push button is pressed, the motor continues to run in the forward direction. Which of the following could cause this problem? The normally open side of the reverse push button is not making a complete circuit when pressed. R contactor coil is open. The normally closed side of the reverse push button is not breaking the circuit when the reverse push button is pressed. There is nothing wrong with the circuit. The stop push button must be pressed before the motor will stop running in the forward direction and permit the motor to be reversed.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Understanding Motor ControlsMechanical EngineeringISBN:9781337798686Author:Stephen L. HermanPublisher:Delmar Cengage Learning
Understanding Motor Controls
Mechanical Engineering
ISBN:9781337798686
Author:Stephen L. Herman
Publisher:Delmar Cengage Learning
Hydronics Step by Step; Author: Taco Comfort Solutions;https://www.youtube.com/watch?v=-XGNl9kppR8;License: Standard Youtube License