Concept explainers
Want to see the full answer?
Check out a sample textbook solutionChapter 28 Solutions
Delmar's Standard Textbook Of Electricity
- Find the GMR of this conductor as r.( Need handwritten solution only please otherwise downvote)arrow_forwardChoose the correct statement: (i) Slip test in an alternator is conducted at lower terminal voltage to avoid large slip. (ii) Slip test in alternator is conducted at lower terminal to avoid heating.(iii) Slip test in alternator is conducted at lower terminal to avoid small slip. Option 1: (i), (ii) & (iii) Option 2: (ii) & (iii) Option 3: only (i) Option 4: only (ii)arrow_forwardApplied kirchoff's Law in simple networksarrow_forward
- T:46)arrow_forwardIn a 3-phase overhead system, each line is suspended by a string of 3 insulators. The voltage across the top unit (i.e. near the tower) and middle unit are 10 kV and 11 kV respectively. Calculate (i) the ratio of shunt capacitance to self capacitance of each insulator, (ii) the string efficiency and (iii) line voltagearrow_forward1. Calculate the reactance of generator G1 (referred to 34.5 kV) and the reactance of generator G2 (referred to 34.5 kV).arrow_forward
- heelparrow_forward3-phase single circuit bundled conductor line with two sub-conductors per phase has horizontalspacing with 6.1 m between the centre lines of adjacent phases. The distance between the subconductorsof each phase is 30.5 cm and each sub-conductor has a diameter of 2.54 cm. Find theinductance per phase per km. [0.988 mh]arrow_forwardsolve on keyboard and correct or dislike write an objects for three-phase system with load on transformer (open and short circuit )arrow_forward
- Consider the single-Line diagram of a power system shown in Figure 3.42 with equipment ratings given: Generator G1: 50MVA,13.2kV,x=0.15p.u. Generator G2: 20MVA,13.8kV,x=0.15p.u. Three-phase -Y transformer T1: 80MVA,13.2/165YkV,X=0.1p.u. Three-phase Y- transformer T2: 40MVA,165Y/13.8kV,X=0.1p.u. Load: 40MVA,0.8PFlagging,operatingat150kV Choose a base of 100 MVA for the system and 132-kV base in the transmission-line circuit. Let the load be modeled as a parallel combination of resistance and inductance. Neglect transformer phase shifts. Draw a per-phase equivalent circuit of the system showing all impedances in per unit.arrow_forwardDetermine the bus admittance matrix (Ybus) for the three-phase power system shown in Figure 6.23 with input data given in Table 6.11 and partial results in Table 6.12. Assume a three-phase 100 MVA per unit base. TABLE 6.11 Bus input data for Problem 6.20 TABLE 6.12 Partially Completed Bus Admittance Matrix (Ybus) for Problem 6.30arrow_forwardFigure 4.37 shows the conductor configuration of a three-phase transmission line and a telephone line supported on the same towers. The power line carries a balanced current of 250 A/phase at 60 Hz, while the telephone line is directly located below phase b Assume balanced three-phase currents in the power line. Calculate the voltage per kilometer induced in the telephone line.arrow_forward
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage LearningEBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENTDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage Learning