A 120-volt branch circuit supplies a resistive heating load of 10 amperes. The distance from the panel to the heater is approximately 140 ft. Calculate the voltage drop using (a) 14 AWG, (b) 12 AWG, (c) 10 AWG, (d) 8 AWG copper conductors. See 210.19(A), Informational Note No. 4 and 215.2(A)(1), Informational Note No. 2.
(a)
Find the value of voltage drop in 14 AWG copper wire.
Answer to Problem 35R
The obtained value of voltage drop in 14 AWG copper wire is
Explanation of Solution
Given data:
Supply voltage is 120-volt.
Current is 10 A.
The distance between panel and heater is approximately 140 ft.
14 AWG copper conductor.
Calculation:
Write the expression for voltage drop in single-phase circuit.
Here,
K is the approximate resistance in ohms per circular-mil foot at
I is the current, and
CMA is cross-sectional area of the conductors.
Modify Equation (1) for 14 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 14 AWG is 4110.
Substitute
Conclusion:
Thus, the obtained value of the voltage drop for 14 AWG copper wire is
(b)
Find the value of voltage drop in 12 AWG copper wire.
Answer to Problem 35R
The obtained value of the voltage drop for 12 AWG copper wire is
Explanation of Solution
Given data:
12 AWG copper conductor.
Calculation:
Modify Equation (1) for 12 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 12 AWG is 6530.
Substitute
Conclusion:
Thus, the obtained value of voltage drop for 12 AWG copper wire is
(c)
Find the value of voltage drop in 10 AWG copper wire.
Answer to Problem 35R
The obtained value of voltage drop for 10 AWG copper wire is
Explanation of Solution
Given data:
10 AWG copper conductor.
Calculation:
Modify Equation (1) for 10 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 10 AWG is 10,380.
Substitute
Conclusion:
Thus, the obtained value of voltage drop for 10 AWG copper wire is
(d)
Find the value of the voltage drop in 8 AWG copper wire.
Answer to Problem 35R
The obtained value of the voltage drop for 8 AWG copper wire is
Explanation of Solution
Given data:
8 AWG copper conductor.
Calculation:
Modify Equation (1) for 8 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 8 AWG is 16,510.
Substitute
Conclusion:
Thus, the obtained value of the voltage drop for 8 AWG copper wire is
Want to see more full solutions like this?
Chapter 4 Solutions
Electrical Wiring Residential
Additional Engineering Textbook Solutions
Introductory Circuit Analysis (13th Edition)
Electric Circuits (10th Edition)
Principles and Applications of Electrical Engineering
Electric Circuits. (11th Edition)
Engineering Electromagnetics
Principles Of Electric Circuits
- What is the minimum size copper grounding electrode conductor for each of the following residential electrical services? Refer to Table 250.66. The ungrounded conductors are Type THW copper. 310.15(B)(7) is only for 120/240-volt, single-phase residential services and feeders. This Section does not apply to services and feeders other than residential.arrow_forward12.a. FMC and LFMC wiring methods are permitted to be used for service-entrance conductors in lengths ofup toA. 12 feet.B. 9 feet.C. 6 feet.D. 3 feet. 12.b. The NEC states that service-drop conductors with voltage limited to 300 volts to ground shall have aminimum of _______ feet vertical clearance from final grade over residential property, driveways, andthose commercial areas not subject to truck traffic.A. 12B. 20C. 15D. 18arrow_forwardL1. Boxes are classified by type, construction, andA. installation location.B. luminaire support capability.C. number of knockouts.D. power rating L2. Which of the following devices must be placed at each end of an armored cable to prevent damage tothe conductors?A. An insulating sliderB. An insertion couplingC. An antishort bushingD. A metal loop fitting L3. Which of the following is the maximum cross-sectional conductor fill area for underfloor raceways?A. 50%B. 60%C. 40%D. 30%arrow_forward
- Refer to the National Electrical Code or the working drawings when necessary. Whereapplicable, responses should be written in complete sentences.A 300-kilovolt-ampere transformer bank consisting of three 100-kilovolt-amperetransformers has a 3-phase, 480-volt delta primary and a 120/240-volt, 3-phase, 4-wiredelta-connected secondary.For problems 1 through 4 show calculations and/or source of information. 1. Sketch the secondary connections, and indicate where a 120-volt load couldbe connected.arrow_forward10.A. Which of the following is required in each separate service disconnecting means?A. Grounding electrodeB. Service conductorC. Main bonding jumperD. Equipment grounding conductor10.B. When sizing an equipment bonding jumper on the load side of an overcurrent protective device, thesize of the conductor jumper is based on theA. current rating of the protective device.B. size of the feeder's equipment grounding conductor.C. size of the grounding electrode conductor.D. size of the conductors feeding the protective device.10.C. Grounding clamps are typically suitable for connecting how many conductors?A. OneB. ThreeC. FourD. Twoarrow_forwardAssume a bank of heating strips is rated at 22 KW and is connected to 240 volts. The heat strips operate for 4 hours at a time and are located in an area with an ambient temperature of 86 degrees F. The termination temperature rating of the heat disconnect lugs are unknown. Copper conductors with type THWN-2 insulation are to be used because of the environment of the installation to connect the heaters. What size conductors should be used?arrow_forward
- Refer to the National Electrical Code or the working drawings when necessary. Whereapplicable, responses should be written in complete sentences.A 300-kilovolt-ampere transformer bank consisting of three 100-kilovolt-amperetransformers has a 3-phase, 480-volt delta primary and a 120/240-volt, 3-phase, 4-wiredelta-connected secondary.For problems 1 through 4 show calculations and/or source of information. 1. What is the proper rating of the fuses to install for overcurrent protection of thesecondary?2. What is the kilovolt-ampere of the bank if one of the transformers is removed?arrow_forwardRefer to the National Electrical Code or the working drawings when necessary. Whereapplicable, responses should be written in complete sentences.A 300-kilovolt-ampere transformer bank consisting of three 100-kilovolt-amperetransformers has a 3-phase, 480-volt delta primary and a 120/240-volt, 3-phase, 4-wiredelta-connected secondary.For problems 1 through 4 show calculations and/or source of information 1. What is the full-load current in the primary? 2. What is the full-load current in the secondary?arrow_forwarda. What is the minimum power demand allowed by the Code for an electric dryer if no actual rating is available for the purpose of calculating feeder and service-entrance conductor sizing? ______________ b. What is the current draw? _____________________arrow_forward
- 11.a. Which of the following is a point where a grounding electrode conductor connection must be made inthe communication system?A. The flexible nonmetallic power service racewayB. The grounding electrode conductor or metal enclosure for a grounding electrode conductorC. The space opposite the service equipment enclosureD. The grounded exterior metal water piping system within six feet of the point where it enters the building11.b. The equipment grounding conductor of a pump motor for a swimming pool must be grounded with asolid copper conductor that's no smaller thanA. AWG 8.B. AWG 12.C. AWG 10.D. AWG 6.arrow_forward14. During normal operation of a typical 120-volt appliance circuit, current flows through the hot, grounding, and neutral conductors.arrow_forwardA ____shall be used to connect the equipment grounding conductors, the service equipment enclosures, and where the system is grounded, the grounded service conductor to the grounding electrode. (a.) bus bar ( b.) 5/8” ground rod (c.) neutral conductor (d.) grounding electrode cond. For equipment rated 1200 amperes or more 600 volts or less, and over 6 feet wide, containing overcurrent devices, switching devices, or control devices, there shall be one entrance not less than ____inches wide and 6 ½ feet high at each end. (a.) 24 (b.) 36 (c.) 30 (d.) 48 When calculating the conductor fill for strut-type channel raceway with internal joiners, the raceway shall be permitted to be filled to _____% of the cross-sectional area. (a.) 20 ( c.) 30 (b.) 25 (d.) 40arrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT