HEATING, VENTILATING,+AC ANAL...EBOOK>I<
HEATING, VENTILATING,+AC ANAL...EBOOK>I<
6th Edition
ISBN: 2819480255750
Author: Mcquiston
Publisher: INTER WILE
bartleby

Videos

Textbook Question
Book Icon
Chapter 3, Problem 3.51P

A multizone air handler provides air to several zones. One interior zone contains computer equipment with only a sensible load. The coil in the unit cools air from 85 F (29 C) db and 70 F (21 C) wb to 53 F (12 C) db and 90% relative humidity (RH). (a) If the zone is to be maintained at 75 F (24 C) and 50% RH, what proportion of the supply air to the zone bypasses the coil? The amount of air supplied to the zone is 2,500 cfm (1.18 m3/s). (b) What is the cooling load for the zone? Assume standard sea-level pressure.

Blurred answer
Students have asked these similar questions
In a place where a summer air-conditioning plant will be installed, 40% of the air entering the air-conditioning plant is the fresh air, and 60% is the return (bypass) air. The sensible heat gain of the place is 10 kW. and the latent heat gain is 2.5 kW.> Outdoor conditions: 32 °C DB, %50 RH.> Indoor conditions: 20 °C DB. %50 RH.> Take the relative humidity of the air passing through the cooling coil 90% at the coil outlet. > The total air flow rate in the mixing chamber is 3000 m3/h> Take the density of the air as 1.2 kg/m3Based on the above.a) Show the process on a psychrometric diagram. b) Calculate the amount of fresh air. c) What is the value of enthalpy of blowing air. d) Calculate the ratio of by-pass air at cooling coil. e) Calculate the flow rate of by-passed air.
In a place where a summer air-conditioning plant will be installed, 40% of the air entering the air-conditioning plant is the fresh air, and 60% is the return (bypass) air. The sensible heat gain of the place is 10 kW. and the latent heat gain is 2.5 kW.> Outdoor conditions: 32 °C DB, %50 RH.> Indoor conditions: 20 °C DB. %50 RH.> Take the relative humidity of the air passing through the cooling coil 90% at the coil outlet. > The total air flow rate in the mixing chamber is 3000 m3/h> Take the density of the air as 1.2 kg/m3Based on the above.  Calculate the amount of fresh air.  What is the value of enthalpy of blowing air.  Calculate the ratio of by-pass air at cooling coil.  Calculate the flow rate of by-passed air.
A summer air-conditioning shown below is required to maintain a certain room at specified conditions. The layout of the system is indicated on the next page and the specifications are listed below.System specifications:Required room temperature: 23⁰C, 50% Relative humidityAtmospheric pressure: 101 kPaOutside air conditions: 30⁰C, 80% Relative humidity Sensible heat gain: 5 kWLatent heat gain: 4 kWTemperature rise across fan: 1.5⁰CTemperature of air leaving cooler: 12⁰CTemperature of air entering room: 18⁰CApparatus dew point of cooler: 7⁰C

Chapter 3 Solutions

HEATING, VENTILATING,+AC ANAL...EBOOK>I<

Ch. 3 - The environmental conditions in a room are to be...Ch. 3 - Air enters a cooling coil at the rate of 5000 cfm...Ch. 3 - Air flowing in a duct has dry and wet bulb...Ch. 3 - Air is humidified with the dry bulb temperature...Ch. 3 - Air at 38 C db and 20 C wb is humidified...Ch. 3 - Two thousand cfm (1.0 m3/s) of air at an initial...Ch. 3 - Air at 40 F (5 C) db and 35 F (2 C) wb is mixed...Ch. 3 - Rework Problem 3-25, using Chart 1a, with the...Ch. 3 - The design cooling load for a zone in a building...Ch. 3 - Assume that the air in Problem 3-22 is supplied to...Ch. 3 - The sensible heat loss from a space is 500,000...Ch. 3 - Air enters a refrigeration coil at 90 Fdb and 75...Ch. 3 - A building has a total heating load of 200,000...Ch. 3 - Reconsider Problem 3-36 for an elevation of 5000...Ch. 3 - The system of Problem 3-34 has a supply air fan...Ch. 3 - An evaporative cooling system is to be used to...Ch. 3 - A cooling system is being designed for use at high...Ch. 3 - Consider a space heating system designed as shown...Ch. 3 - A variable-air-volume VAV cooling system is a type...Ch. 3 - Rework Problem 3-43 for an elevation of 5000 feet...Ch. 3 - The design condition for a space is 77 F (25 C) db...Ch. 3 - Rework Problem 3-45 for an elevation of 5000 feet...Ch. 3 - It is necessary to cool and dehumidify air from 80...Ch. 3 - Conditions in one zone of a dual-duct conditioning...Ch. 3 - Rework Problem 3-48 for an elevation of 5000 ft...Ch. 3 - A water coil in Problem 3-48 cools return air to...Ch. 3 - A multizone air handler provides air to several...Ch. 3 - Under normal operating conditions a zone has a...Ch. 3 - An interior zone of a large building is designed...Ch. 3 - Outdoor air is mixed with room return air to...Ch. 3 - Consider an enclosed swimming pool. The pool area...Ch. 3 - One particular zone served by a multizone air...Ch. 3 - A research building requires 100 percent outdoor...Ch. 3 - A space requires cooling in the amount of 120,000...
Knowledge Booster
Background pattern image
Mechanical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Refrigeration and Air Conditioning Technology (Mi...
Mechanical Engineering
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:Cengage Learning
The Refrigeration Cycle Explained - The Four Major Components; Author: HVAC Know It All;https://www.youtube.com/watch?v=zfciSvOZDUY;License: Standard YouTube License, CC-BY