Question
Chapter 3, Problem 3.9P
To determine
(a)
The voltage
To determine
(b)
Percentage voltage regulation.
Expert Solution & Answer
Trending nowThis is a popular solution!
Students have asked these similar questions
Q.) A single-phase transformer is rated at 10 kVA, 230 V/100 V. When the secondary terminals are open-circuited and the primary winding is supplied at normal voltage (230 V), the current input is 2.6 A at a power factor of 0.3. When the secondary terminals are short-circuited, a voltage of 18 V applied to the primary causes the full-load current (100 A) to flow in the secondary, the power input to the primary being 240 W.
Calculate:
(i) The efficiency of the transformer at full load, unity power factor.
(ii) The load at which maximum efficiency occurs.
(iii) The value of the maximum efficiency
A 1100/110V step down single phase transformer has the following parameters. Rc= 2 KΩ, Xm= 1.5 KΩ, R1=4Ω, X1=3 Ω, R2=0.04 Ω, X2=0.03 Ω. If the transformer delivers its output to a load of 5.5 kVA with 0.8 lagging power factor at 110V.
Calculate the primary voltage, voltage regulation and the transformer efficiency.
1. A 30KVA, 6000/230V, 50Hz single phase transformer has HV and LV winding resistances of 10.2Ω and0.0016Ω respectively. The equivalent leakage reactance as referred to HV side is 34Ω. Find the voltageto be applied to the HV side in order to circulate the full load current with LV side short circuited. Alsoestimate the full load %regulation of the transformer at 0.8 lagging power factor.
Chapter 3 Solutions
Power System Analysis and Design (MindTap Course List)
Ch. 3 - The Ohms law for the magnetic circuit states that...Ch. 3 - For an ideal transformer, the efficiency is (a) 0...Ch. 3 - For an ideal 2-winding transformer, the...Ch. 3 - An ideal transformer has no real or reactive power...Ch. 3 - For an ideal 2-winding transformer, an impedance...Ch. 3 - Consider Figure 3.4. For an ideal phase-shifting...Ch. 3 - Consider Figure 3.5. Match the following, those on...Ch. 3 - The units of admittance, conductance, and...Ch. 3 - Match the following: (i) Hysteresis loss (a) Can...Ch. 3 - For large power transformers rated more than 500...
Ch. 3 - For a short-circuit test on a 2-winding...Ch. 3 - The per-unit quantity is always dimensionless. (a)...Ch. 3 - Consider the adopted per-unit system for the...Ch. 3 - The ideal transformer windings are eliminated from...Ch. 3 - To convert a per-unit impedance from old to new...Ch. 3 - In developing per-unit circuits of systems such as...Ch. 3 - Prob. 3.17MCQCh. 3 - Prob. 3.18MCQCh. 3 - With the American Standard notation, in either a...Ch. 3 - Prob. 3.20MCQCh. 3 - In order to avoid difficulties with third-harmonic...Ch. 3 - Does an open connection permit balanced...Ch. 3 - Does an open- operation, the kVA rating compared...Ch. 3 - It is stated that (i) balanced three-phase...Ch. 3 - In developing per-unit equivalent circuits for...Ch. 3 - In per-unit equivalent circuits of practical...Ch. 3 - Prob. 3.27MCQCh. 3 - Prob. 3.28MCQCh. 3 - For developing per-unit equivalent circuits of...Ch. 3 - Prob. 3.30MCQCh. 3 - Prob. 3.31MCQCh. 3 - Prob. 3.32MCQCh. 3 - The direct electrical connection of the windings...Ch. 3 - Consider Figure 3.25 of the text for a transformer...Ch. 3 - (a) An ideal single-phase two-winding transformer...Ch. 3 - An ideal transformer with N1=1000andN2=250 is...Ch. 3 - Consider an ideal transformer with...Ch. 3 - A single-phase 100-kVA,2400/240-volt,60-Hz...Ch. 3 - Prob. 3.5PCh. 3 - Prob. 3.6PCh. 3 - Consider a source of voltage v(t)=102sin(2t)V,...Ch. 3 - Prob. 3.8PCh. 3 - Prob. 3.9PCh. 3 - A single-phase step-down transformer is rated...Ch. 3 - For the transformer in Problem 3.10. The...Ch. 3 - Prob. 3.12PCh. 3 - A single-phase 50-kVA,2400/240-volt,60-Hz...Ch. 3 - A single-phase 50-kVA,2400/240-volt,60-Hz...Ch. 3 - Rework Problem 3.14 if the transformer is...Ch. 3 - A single-phase, 50-kVA,2400/240-V,60-Hz...Ch. 3 - The transformer of Problem 3.16 is supplying a...Ch. 3 - Using the transformer ratings as base quantities,...Ch. 3 - Using the transformer ratings as base quantities....Ch. 3 - Using base values of 20 kVA and 115 volts in zone...Ch. 3 - Prob. 3.21PCh. 3 - A balanced Y-connected voltage source with...Ch. 3 - Figure 3.32 shows the oneline diagram of a...Ch. 3 - For Problem 3.18, the motor operates at full load,...Ch. 3 - Consider a single-phase electric system shown in...Ch. 3 - A bank of three single-phase transformers, each...Ch. 3 - A three-phase transformer is rated...Ch. 3 - For the system shown in Figure 3.34. draw an...Ch. 3 - Consider three ideal single-phase transformers...Ch. 3 - Reconsider Problem 3.29. If Va,VbandVc are a...Ch. 3 - Prob. 3.31PCh. 3 - Determine the positive- and negative-sequence...Ch. 3 - Consider the three single-phase two-winding...Ch. 3 - Three single-phase, two-winding transformers, each...Ch. 3 - Consider a bank of this single-phase two-winding...Ch. 3 - Three single-phase two-winding transformers, each...Ch. 3 - Three single-phase two-winding transformers, each...Ch. 3 - Consider a three-phase generator rated...Ch. 3 - The leakage reactance of a three-phase,...Ch. 3 - Prob. 3.40PCh. 3 - Consider the single-line diagram of the power...Ch. 3 - For the power system in Problem 3.41, the...Ch. 3 - Three single-phase transformers, each rated...Ch. 3 - A 130-MVA,13.2-kV three-phase generator, which has...Ch. 3 - Figure 3.39 shows a oneline diagram of a system in...Ch. 3 - The motors M1andM2 of Problem 3.45 have inputs of...Ch. 3 - Consider the oneline diagram shown in Figure 3.40....Ch. 3 - With the same transformer banks as in Problem...Ch. 3 - Consider the single-Line diagram of a power system...Ch. 3 - A single-phase three-winding transformer has the...Ch. 3 - The ratings of a three-phase three-winding...Ch. 3 - Prob. 3.52PCh. 3 - The ratings of a three-phase, three-winding...Ch. 3 - An infinite bus, which is a constant voltage...Ch. 3 - A single-phase l0-kVA,2300/230-volt,60-Hz...Ch. 3 - Three single-phase two-winding transformers, each...Ch. 3 - A two-winding single-phase transformer rated...Ch. 3 - A single-phase two-winding transformer rated...Ch. 3 - Prob. 3.59PCh. 3 - PowerWorid Simulator case Problem 3_60 duplicates...Ch. 3 - Rework Example 3.12 for a+10 tap, providing a 10...Ch. 3 - A 23/230-kV step-up transformer feeds a...Ch. 3 - The per-unit equivalent circuit of two...Ch. 3 - Reconsider Problem 3.64 with the change that now...Ch. 3 - What are the advantages of correctly specifying a...Ch. 3 - Why is it important to reduce the moisture within...Ch. 3 - What should be the focus of transformer preventive...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- A two-winding single-phase transformer rated 60kVA,240/1200V,60Hz, has an efficiency of 0.96 when operated at rated load, 0.8 power factor lagging. This transformer is to be utilized as a 1440/1200-V step-down autotransformer in a power distribution system. (a) Find the permissible kVA rating of the autotransformer if the winding currents and voltages are not to exceed the ratings as a two-winding transformer. Assume an ideal transformer. (b) Determine the efficiency of the autotransformer with the kVA loading of part (a) and 0.8 power factor leading.arrow_forward(a) An ideal single-phase two-winding transformer with turns ratio at=N1/N2 is connected with a series impedance Z2 across winding 2. If one wants to replace Z2, with a series impedance Z1 across winding 1 and keep the terminal behavior of the two circuits to be identical, find Z1 in terms of Z2. (b) Would the above result be true if instead of a series impedance there is a shunt impedance? (c) Can one refer a ladder network on the secondary (2) side to the primary (1) side simply by multiplying every impedance byat2 ?arrow_forwardA 10 kVA, 2000/400 V, single-phase transformer has resistances and leakage reactance as; R1 = 5.2 Ω, X1 = 12.5 Ω, R2 = 0.2 Ω, X2 = 0.5 Ω. Determine the value of secondary terminal voltage when the transformer is operating with rated primary voltage with the secondary current at its rated value with power factor 0.8 lag. The no-load current can be neglected. Draw the phasor diagram.arrow_forward
- The parameters of a 1000/250V, 50HZ single phase transformer are: R1=1.3 N, X1=2.8 N, R2=0.11 N, X2=0.2 N, R,=250 N, X,=900 N. If the load voltage is 220V, load power is 10kW, and load power factor is 0.8 lagging. Find by using the exact equivalent circuit: (i) Input current, (ii) The input voltage and power factor, (iii) The magnetizing current, (iv) The copper losses, (v) The voltage regulation.arrow_forwardPower transformer A, has Rated power of 150MVA. Line voltage of 330/66 kV Frequency=50Hz Connection Yd1 Z impedance=8% X/R =7.94 To accommodate a higher load a new transformer B,rated 180 MVA, 330/66 kV, 50 Hz,is to be installed in parallel with the existing transformer. Determine the load on each transformer if the total load is 300 MVA at a power factor of 0.9 laggingarrow_forwardA 15-kVA, 2400/240-V, 60 Hz single phase transformer has the following equivalent circuit parameters:R1 = 2.5 Ω R2 = 0.025 Ω X1 = 7 Ω X2 = 0.07 ΩRc = 32 kΩ Xm = 11.5 kΩIf the transformer is supplying a 10-kW, 0.8 PF lagging load at rated voltage, calculate the primary voltageand current.arrow_forward
- A 125 kVA transformer having a primary voltage of 2200 V at 50 Hz has 182 primary turns and 40 secondary turns. Neglecting losses calculate (i) full load primary and secondary currents and (ii) no load secondary induced emf. The secondary windings of a 2 kVA, 2400/120 V, 50 Hz single phase transformer is short circuited and potential difference of 16.2 V produces a primary current of 6 A, the input being 33.5 W. Calculate the total primary impedance, resistance and reactance. solve all partarrow_forwardA 2MVA, 3-phase transformer, 33/11-kV, Y/Y, has a copper loss of 6 kW. The impedance drop at full-load is 7.5%. Calculate the primary voltage at rated load, 0.8 pf laggingarrow_forward1) An ideal transformer, connected to a 240V mains supplies 12V, 150W lamp. Calculate the transformer turns ratio and current taken from the supply. 2) A 5kVA single phase transformer has turns ratio of 10:1 and is fed from 2.5kV supply. Neglecting losses, Determine; a) full load secondary current b) minimum load resistance which can be connected to the secondary windings to give full load kVA c) primary current at full load. 3) A current of 5A is passed through a 1000 turn coil wound on a circular magnetic circuit of radius 120mm, calculate; a) magnetomotive force b) magnetic field strengtharrow_forward
- A 6.9 kV/600 V, multi-tap, single-phase distribution transformer is connected to the far end of a distribution line for which the rear end voltage is maintained at 6.9 kV. The equivalent impedance of the transformer referred to low voltage side is 0.05 + j0.25 Ω per phase. The impedance of each line is 1 + j2 Ω. It is required to maintain a terminal voltage of 600 V when the line current of 300 A at 80% pf lagging is delivered to the load. What approximate percentage tapping is required in the primary side? Neglect the changes in impedance due to changes in turns ratio. A. 94 % B. 92 % C. 90 % D. 88 %arrow_forwarda 10 KVA, 1940 / 490 V 1-phase transformer with R1=0.35 ohms, R2=0.03 ohms, X1=1.6 ohms and X2=0.06 ohms. Also calculate the equivalent resistance and reactance referred to primary winding.arrow_forwardThe maximum efficiency of a 500 – kVA, 3300/500 V, 50Hz, single phase transformer is 97% and occurs at 3/4 ofthe full load at unity factor. If the impedance is 0.05referred to the 500 V side, calculate the regulation atfull load and power factor 0.8 lagging.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning