EBK ELECTRICAL WIRING RESIDENTIAL
EBK ELECTRICAL WIRING RESIDENTIAL
19th Edition
ISBN: 9781337516549
Author: Simmons
Publisher: CENGAGE LEARNING - CONSIGNMENT
bartleby

Concept explainers

bartleby

Videos

Textbook Question
Book Icon
Chapter 4, Problem 35R

A 120-volt branch circuit supplies a resistive heating load of 10 amperes. The distance from the panel to the heater is approximately 140 ft. Calculate the voltage drop using (a) 14 AWG, (b) 12 AWG, (c) 10 AWG, (d) 8 AWG copper conductors. See 210.19(A), Informational Note No. 4 and 215.2(A)(1), Informational Note No. 2.

(a)

Expert Solution
Check Mark
To determine

Find the value of voltage drop in 14 AWG copper wire.

Answer to Problem 35R

The obtained value of voltage drop in 14 AWG copper wire is 8.79Volts drop_.

Explanation of Solution

Given data:

Supply voltage is 120-volt.

Current is 10 A.

The distance between panel and heater is approximately 140 ft.

14 AWG copper conductor.

Calculation:

Write the expression for voltage drop in single-phase circuit.

Ed=K×I×L×2CMA (1)

Here,

Ed is the voltage drop,

K is the approximate resistance in ohms per circular-mil foot at 75°C. The value of K for uncoated copper wire is 12.9 and for aluminum wire is 21.2.

I is the current, and

CMA is cross-sectional area of the conductors.

Modify Equation (1) for 14 AWG copper wire.

Ed(14AWG)=K×I×L×2CMA(14AWG) (2)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 14 AWG is 4110.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 4110 for CMA(14AWG) in Equation (2) to find the voltage drop in 14 AWG copper wire.

Ed(14AWG)=12.9×10×140×24110=8.788Volts drop8.79Volts drop

Conclusion:

Thus, the obtained value of the voltage drop for 14 AWG copper wire is 8.79Volts drop_.

(b)

Expert Solution
Check Mark
To determine

Find the value of voltage drop in 12 AWG copper wire.

Answer to Problem 35R

The obtained value of the voltage drop for 12 AWG copper wire is 5.53Volts drop_.

Explanation of Solution

Given data:

12 AWG copper conductor.

Calculation:

Modify Equation (1) for 12 AWG copper wire.

Ed(12AWG)=K×I×L×2CMA(12AWG) (3)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 12 AWG is 6530.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 6530 for CMA(12AWG) in Equation (3) to find the voltage drop in 12 AWG copper wire.

Ed(12AWG)=12.9×10×140×26530=5.531Volts drop5.53Volts drop

Conclusion:

Thus, the obtained value of voltage drop for 12 AWG copper wire is 5.53Volts drop_.

(c)

Expert Solution
Check Mark
To determine

Find the value of voltage drop in 10 AWG copper wire.

Answer to Problem 35R

The obtained value of voltage drop for 10 AWG copper wire is 3.48Volts drop_.

Explanation of Solution

Given data:

10 AWG copper conductor.

Calculation:

Modify Equation (1) for 10 AWG copper wire.

Ed(10AWG)=K×I×L×2CMA(10AWG) (4)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 10 AWG is 10,380.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 10,380 for CMA(10AWG) in Equation (4) to find the voltage drop in 10 AWG copper wire.

Ed(10AWG)=12.9×10×140×210,380=3.479Volts drop3.48Volts drop

Conclusion:

Thus, the obtained value of voltage drop for 10 AWG copper wire is 3.48Volts drop_.

(d)

Expert Solution
Check Mark
To determine

Find the value of the voltage drop in 8 AWG copper wire.

Answer to Problem 35R

The obtained value of the voltage drop for 8 AWG copper wire is 2.19Volts drop_.

Explanation of Solution

Given data:

8 AWG copper conductor.

Calculation:

Modify Equation (1) for 8 AWG copper wire.

Ed(8AWG)=K×I×L×2CMA(8AWG) (5)

Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.

The value of CMA for 8 AWG is 16,510.

Substitute 12.9 for K, 10 A for I, 140 ft for L, and 16,510 for CMA(8AWG) in Equation (5) to find the voltage drop in 8 AWG copper wire.

Ed(8AWG)=12.9×10×140×216,510=2.187Volts drop2.19Volts drop

Conclusion:

Thus, the obtained value of the voltage drop for 8 AWG copper wire is 2.19Volts drop_.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
5.a. Typically, the bonding conductor installed between the panelboard equipment grounding terminal barsmust be continuous. It's only allowed to be broken where it connects to theA. signal reference grid.B. terminal bar in the panelboard.C. branch circuit.D. service entrance enclosure.5.b. An electrical system that's not grounded and is between 120 and 1000 volts must include the use ofA. arc suppression.B. ground isolators.C. ground detectors.D. equipotential barriers.
10.a. Which of the following is a condition of the exception that allows the grounded conductor of feeders tobe used for grounding at separate buildings or structures?A. There are common electrically continuous metallic paths between the feeder source and the destination at the structure served.B. There are common electrically continuous nonmetallic paths between the equipment grounding conductor and the destinationat the structure served.C. An equipment grounding conductor isn't included with the supply circuit to the separate structure.D. Ground-fault protection of equipment is provided on the supply side of the feeder.10.b. A service disconnection means must be installed adjacent to, within sight of, and no more than_______ feet from a mobile home.A. 20B. 30C. 10D. 50
A one-family dwelling has a 175-ampere, 240-volt service that is fed with 75⁰ C (167 degrees) conductors. What is the minimum size copper grounding electrode conductor required ?

Chapter 4 Solutions

EBK ELECTRICAL WIRING RESIDENTIAL

Ch. 4 - For nonmetallic-sheathed cable, may the...Ch. 4 - Prob. 12RCh. 4 - Under what condition may nonmetallic-sheathed...Ch. 4 - a. What is the maximum distance permitted between...Ch. 4 - Prob. 15RCh. 4 - Prob. 16RCh. 4 - Prob. 17RCh. 4 - Prob. 18RCh. 4 - Prob. 19RCh. 4 - Circle the correct answer to the following...Ch. 4 - When running Type NM cable through a bored hole in...Ch. 4 - Where is the main service-entrance panel located...Ch. 4 - Is it permitted to use flexible metal conduit over...Ch. 4 - Liquidtight flexible metal conduit may serve as a...Ch. 4 - It is permissible for an electrician to connect...Ch. 4 - Terminals of switches and receptacles marked...Ch. 4 - Wire connectors marked AL/CU are suitable for use...Ch. 4 - A wire connector bearing no marking or reference...Ch. 4 - When Type NM cable is run through a floor, it must...Ch. 4 - When nonmetallic-sheathed cables are bunched or...Ch. 4 - In diagrams A and B, nonmetallic-sheathed cable is...Ch. 4 - The marking on the outer jacket of a...Ch. 4 - A 120-volt branch circuit supplies a resistive...Ch. 4 - In problem 35, it is desired to keep the voltage...Ch. 4 - Prob. 37RCh. 4 - The allowable ampacity of a 4 AWG THHN from Table...Ch. 4 - If, because of some obstruction in a wall space,...Ch. 4 - The recessed fluorescent luminaires installed in...Ch. 4 - Prob. 41RCh. 4 - What size overcurrent device protects the...Ch. 4 - May the 20-ampere small-appliance branch circuits...Ch. 4 - A 30-ampere branch circuit is installed for an...Ch. 4 - In many areas, metal framing members are being...Ch. 4 - Are set screwtype connectors permitted to be used...Ch. 4 - Most armored cable today has 90C conductors. What...Ch. 4 - If you saw two different types of SE cables, how...Ch. 4 - Circle the correct answer defining the type of...
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
What is an electric furnace and how does it work?; Author: Fire & Ice Heating and Air Conditioning Inc;https://www.youtube.com/watch?v=wjAWecPGi0M;License: Standard Youtube License