Textbook Question
Chapter 4, Problem 38R
The allowable ampacity of a 4 AWG THHN from Table 310.15(B)(16) is 95 amperes. What is this conductor’s ampacity if connected to a terminal listed for use with 60°C wire? ______
Expert Solution & Answer
Trending nowThis is a popular solution!
Students have asked these similar questions
The white wire of a cable may be used to connect to a "hot" ungrounded circuit conductor only if ?
Assuming all terminals are rated 75 degrees Celsius, you have three (3) #10 AWG THHN/THWN conductors in a conduit and the conduit is run inside an office building, the largest size circuit breaker or fuse permitted to protect this wire?
What size equipment grounding conductor is used with # 8 AWG nonmetallic-sheathed cable?
Chapter 4 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Ch. 4 - The largest size solid conductor generally...Ch. 4 - What is the minimum branch-circuit wire size that...Ch. 4 - What exceptions, if any, are there to the answer...Ch. 4 - What determines the ampacity of a wire?Ch. 4 - What unit of measurement is used for the diameter...Ch. 4 - What unit of measurement is used for the...Ch. 4 - What is the voltage rating of the conductors in...Ch. 4 - Indicate the allowable ampacity of the following...Ch. 4 - Prob. 9RCh. 4 - What are the colors of the conductors in...
Ch. 4 - For nonmetallic-sheathed cable, may the...Ch. 4 - Prob. 12RCh. 4 - Under what condition may nonmetallic-sheathed...Ch. 4 - a. What is the maximum distance permitted between...Ch. 4 - Prob. 15RCh. 4 - Prob. 16RCh. 4 - Prob. 17RCh. 4 - Prob. 18RCh. 4 - Prob. 19RCh. 4 - Circle the correct answer to the following...Ch. 4 - When running Type NM cable through a bored hole in...Ch. 4 - Where is the main service-entrance panel located...Ch. 4 - Is it permitted to use flexible metal conduit over...Ch. 4 - Liquidtight flexible metal conduit may serve as a...Ch. 4 - It is permissible for an electrician to connect...Ch. 4 - Terminals of switches and receptacles marked...Ch. 4 - Wire connectors marked AL/CU are suitable for use...Ch. 4 - A wire connector bearing no marking or reference...Ch. 4 - When Type NM cable is run through a floor, it must...Ch. 4 - When nonmetallic-sheathed cables are bunched or...Ch. 4 - In diagrams A and B, nonmetallic-sheathed cable is...Ch. 4 - The marking on the outer jacket of a...Ch. 4 - A 120-volt branch circuit supplies a resistive...Ch. 4 - In problem 35, it is desired to keep the voltage...Ch. 4 - Prob. 37RCh. 4 - The allowable ampacity of a 4 AWG THHN from Table...Ch. 4 - If, because of some obstruction in a wall space,...Ch. 4 - The recessed fluorescent luminaires installed in...Ch. 4 - Prob. 41RCh. 4 - What size overcurrent device protects the...Ch. 4 - May the 20-ampere small-appliance branch circuits...Ch. 4 - A 30-ampere branch circuit is installed for an...Ch. 4 - In many areas, metal framing members are being...Ch. 4 - Are set screwtype connectors permitted to be used...Ch. 4 - Most armored cable today has 90C conductors. What...Ch. 4 - If you saw two different types of SE cables, how...Ch. 4 - Circle the correct answer defining the type of...
Additional Engineering Textbook Solutions
Find more solutions based on key concepts
Electric power systems provide energy in a variety of commercial and industrial settings. Make a list of system...
Principles and Applications of Electrical Engineering
Find I0 and I1 in the circuit in Fig.P2.12.
Basic Engineering Circuit Analysis
When travelers from the USA and Canada visit Europe, they encounter a different power distribution system. Wall...
Electric machinery fundamentals
Three point charges of equal magnitude q, that will yield a zero net electric field at the origin.
Engineering Electromagnetics
Identify the type of input and output configuration for each diff-amp in Figure 18-35.
Electronics Fundamentals: Circuits, Devices & Applications
How many coulombs do 93.8 1016 electrons represent?
Principles Of Electric Circuits
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- When two nonmetallic-sheathed cables (Type NM-B) enter a box, is it permitted to bring both of the bare equipment grounding conductors directly to the grounding terminal of a receptacle, using the terminal as a splice point? _______arrow_forwarda. Does the circuit for the Master Bedroom have a grounded circuit conductor? ____________________ b. Does it have an equipment grounding conductor? ____________________ c. Explain the difference between a grounded conductor and an equipment grounding conductor. ____________________ ____________________arrow_forwardHow and where is the grounding electrode conductor attached to the water pipe?arrow_forward
- Where insulated conductors are deflected within a wireway, either at the ends or where conduits, fittings, or other raceways or cables enter or leave the wireway, or where the direction of the wireway is deflected greater than ____, dimensions corresponding to one wire per terminal in Table 312.6(A) shall apply.arrow_forwardAssuming all terminals are rated 75 degrees Celsius, and you have six (6) #10 AWG THHN/THWN conductors in a conduit and the conduit is run inside an office building, What is the largest size circuit breaker or fuse permitted to protect this wire?arrow_forward10.a. Which of the following is a condition of the exception that allows the grounded conductor of feeders tobe used for grounding at separate buildings or structures?A. There are common electrically continuous metallic paths between the feeder source and the destination at the structure served.B. There are common electrically continuous nonmetallic paths between the equipment grounding conductor and the destinationat the structure served.C. An equipment grounding conductor isn't included with the supply circuit to the separate structure.D. Ground-fault protection of equipment is provided on the supply side of the feeder.10.b. A service disconnection means must be installed adjacent to, within sight of, and no more than_______ feet from a mobile home.A. 20B. 30C. 10D. 50arrow_forward
- When the ground is removed from the sheath at one end to reduce heating in a cable, what hazard exists at the ungrounded end of the cable?arrow_forwardEighty 16 AWG copper conductors with type THWN-2 insulation are to be run in a conduit. The conduit used in an area that has an ambient temperature of 120 F. What is the maximum ampacity of these conductors?arrow_forwardHow many circuit conductors enter the box a. where the range hood will be installed? _________________ b. in the ceiling box over which the track will be installed? _________________ c. at the switch location to the right of the sliding door? _________________arrow_forward
- If you use 600-volt rated conductors for Class 2 wiring, does the Code permit pulling these conductors through the same raceway as the power conductors? (Yes) (No) (Circle the correct answer.) Give the NEC section number. ____________arrow_forwardWhat section of the Code prohibits supporting telephone wires from raceways that contain light or power conductors? NEC _____arrow_forward6. Which of the following is a condition that a liquidtight flexible metal conduit must meet in order to be suitable as an equipment grounding conductor? A. The conduit is terminated in listed fittings.B. For trade sizes 3/4 through 1 1/4, the conduit conductors contained in the conduit are protected by overcurrent devices rated at 20 amperes or less.C. The combined length of the conduit and other tubing and conduit in the same ground-fault path exceeds six feet. D. For trade sides 3/8 through 1/2, the circuit conductors contained in the conduit are protected by overcurrent devices rated not more than 60 amperes. 7. You're going to connect a surge protection device to a separately derived electrical system. In this situation, the surge protection device should be connected at A. the load side of the first overcurrent protection device. B. the input to the transformer's primary winding.C. the end of the shortest branch circuit.D. the first connected IT cabinet. 8. What is another term…arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Types of House Wiring - Types of Electrical Wiring - Electrical Wiring; Author: Learning Engineering;https://www.youtube.com/watch?v=A5P-buWX-dA;License: Standard Youtube License