Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf
Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf
9th Edition
ISBN: 9781259989452
Author: Hayt
Publisher: Mcgraw Hill Publishers
Question
Book Icon
Chapter 11, Problem 43E

(a)

To determine

Find the apparent power delivered to each load in the circuit in Figure 11.45 in the textbook and power factor of the source.

(a)

Expert Solution
Check Mark

Answer to Problem 43E

The apparent power delivered to ZA, ZB, ZC, ZD, and the source power factor are 3.4kVA_, 1.48kVA_, 87.67VA_, 147VA_, and 0.966 leading, respectively.

Explanation of Solution

Given data:

Refer to Figure 11.45 in the textbook for the given circuit.

Vs=2000°Vrms

The impedance of the loads are given as follows:

ZA=(5j2)ΩZB=3ΩZC=(8+j4)ΩZD=1530°Ω

Formula used:

Write the expression for complex power delivered to the load as follows:

S=VI*        (1)

Here,

V is the voltage across the load and

I is the current through the load.

Write the expression for voltage in terms of current and impedance as follows:

V=IZ        (2)

Write the expression for complex power in the rectangular form as follows:

S=P+jQ        (3)

Here,

P is the average power and

Q is the reactive power.

Write the expression for power factor as follows:

PF=cos[tan1(QP)]        (4)

Calculation:

Consider the current through the left-loop as I1 and the current through the right-loop as I2.

Apply KVL to the left-loop as follows:

2000°V+I1ZA+(I1I2)ZB=0        (5)

Substitute (5j2)Ω for ZA and 3Ω for ZB as follows:

2000°V+I1[(5j2)Ω]+(I1I2)(3Ω)=0(8j2)I13I2=2003I2=(8j2)I1200

I2=(8j2)3I12003        (6)

Apply KVL to the right-loop as follows:

(I2I1)ZB+I2ZC+I2ZD=0        (7)

Substitute 3Ω for ZB, (8+j4)Ω for ZC, and 1530°Ω for ZD as follows:

(I2I1)(3Ω)+I2[(8+j4)Ω]+I2(1530°Ω)=03(I2I1)+I2(8+j4)+I2(12.9903j7.5)=03I1+(23.9903j3.5)I2=0

From Equation (6), substitute [(8j2)3I12003] for I2 as follows:

3I1+(23.9903j3.5)[(8j2)3I12003]=03I1+(61.6408j25.3268)I1+(1599.3533+j233.3333)=0(58.6408j25.3268)I1+(1599.3533+j233.3333)=0

Simplify the expression as follows:

I1=(1599.3533j233.3333)(58.6408j25.3268)A=(24.4343+j6.5741)A=25.303215.06°A

Substitute (24.4343+j6.5741)A for I1 in Equation (6) to obtain the value of I2.

I2=(8j2)3[(24.4343+j6.5741)A]2003=(2.8742+j1.2414)A=3.130823.36°A

Modify the expression in Equation (2) for the voltage across the load ZA.

VA=I1ZA

Substitute (24.4343+j6.5741)A for I1 and (5j2)Ω for ZA to obtain he voltage across . ZA

VA=[(24.4343+j6.5741)A][(5j2)Ω]=(135.3197j15.9981)V=136.26216.74°V

Modify the expression in Equation (1) for the complex power delivered to the load ZA as follows:

SA=VA(I1)*

Substitute 136.26216.74°V for VA and 25.303215.06°A for I1 to obtain the complex power delivered to the load ZA.

SA=(136.26216.74°V)(25.303215.06°A)*=(136.26216.74°V)(25.303215.06°A)=3447.867121.8°VA=3.447821.8°kVA

SA3.421.8°kVA

Find the apparent power delivered to the load ZA as follows:

|SA|=|3.421.8°kVA|=3.4kVA

Modify the expression in Equation (2) for the voltage across the load ZB.

VB=(I1I2)ZB

Substitute (24.4343+j6.5741)A for I1, (2.8742+j1.2414)A for I2, and 3Ω for ZB

VB={[(24.4343+j6.5741)A][(2.8742+j1.2414)A]}(3Ω)=(21.5601+j5.3327)(3)V=(64.6803+15.9981)V=66.629413.89°V

Find the current through the load ZB as follows:

IB=(I1I2)

Substitute (24.4343+j6.5741)A for I1 and (2.8742+j1.2414)A for I2 to obtain the current through the load ZB.

IB=[(24.4343+j6.5741)A][(2.8742+j1.2414)A]=(21.5601+j5.3327)A=22.209813.89°A

Modify the expression in Equation (1) for the complex power delivered to the load ZB as follows:

SB=VB(IB)*

Substitute 66.629413.89°V for VB and 22.209813.89°A for IB to obtain the complex power delivered to the load ZB.

SB=(66.629413.89°V)(22.209813.89°A)*=(66.629413.89°V)(22.209813.89°A)=1479.82560°VA=1.47980°kVA

SB1.480°kVA

Find the apparent power delivered to the load ZB as follows:

|SB|=|1.480°kVA|=1.48kVA

Modify the expression in Equation (2) for the voltage across the load ZC.

VC=I2ZC

Substitute (2.8742+j1.2414)A for I2 and (8+j4)Ω for ZC to obtain he voltage across ZC.

VC=[(2.8742+j1.2414)A][(8+j4)Ω]=(18.028+j21.428)V=28.00349.93°V

Modify the expression in Equation (1) for the complex power delivered to the load ZC as follows:

SC=VC(I2)*

Substitute 28.00349.93°V for VC and 3.130823.36°A for I2 to obtain the complex power delivered to the load ZC.

SC=(28.00349.93°V)(3.130823.36°A)*=(28.00349.93°V)(3.130823.36°A)=87.671726.57°VA87.6726.57°VA

Find the apparent power delivered to the load ZC as follows:

|SC|=|87.6726.57°VA|=87.67VA

Modify the expression in Equation (2) for the voltage across the load ZD.

VD=I2ZD

Substitute 3.130823.36°A for I2 and 1530°Ω for ZD to obtain he voltage across ZD.

VD=[3.130823.36°A][1530°Ω]=46.9626.64°V

Modify the expression in Equation (1) for the complex power delivered to the load ZD as follows:

SD=VD(I2)*

Substitute 46.9626.64°V for VD and 3.130823.36°A for I2 to obtain the complex power delivered to the load ZD.

SD=(46.9626.64°V)(3.130823.36°A)*=(46.9626.64°V)(3.130823.36°A)=147.028630°VA14730°VA

Find the apparent power delivered to the load ZD as follows:

|SD|=|14730°VA|=147VA

Modify the expression in Equation (1) for the complex power supplied by the source as follows:

Ss=Vs(I1)*

Substitute 2000°V for Vs and 25.303215.06°A for I1 to obtain the complex power supplied by the source.

Ss=(2000°V)(25.303215.06°A)*=(2000°V)(25.303215.06°A)=5060.615.06°VA

Rewrite the expression for complex power supplied by the source in rectangular form as follows:

Ss=(4886.7899j1314.8978)VA

Compare the complex power supplied by the source with the expression in Equation (3) and write the average and reactive power supplied by the source as follows:

P=4886.7899WQ=1314.8978VAR

Substitute 4886.7899 W for P and 1314.8978VAR for Q in Equation (4) to obtain the value of source power factor.

PF=cos[tan1(1314.8978VAR4886.7899W)]=cos(15.06°)=0.96560.966

If the imaginary part of the complex power (reactive power) is positive value, then the load has lagging power factor. If the imaginary part is negative value, then the load has leading power factor.

As the imaginary part of the given complex power is negative value, the power factor is leading power factor.

PF=0.966leading

Conclusion:

Thus, the apparent power delivered to ZA, ZB, ZC, ZD, and the source power factor are 3.4kVA_, 1.48kVA_, 87.67VA_, 147VA_, and 0.966 leading, respectively.

(b)

To determine

Find the apparent power delivered to each load in the circuit in Figure 11.45 in the textbook and power factor of the source.

(b)

Expert Solution
Check Mark

Answer to Problem 43E

The apparent power delivered to ZA, ZB, ZC, ZD, and the source power factor are 9.87kVA_, 3.86kVA_, 227.13VA_, 406.3VA_, and 0.85 leading, respectively.

Explanation of Solution

Given data:

The impedance of the loads are given as follows:

ZA=215°ΩZB=1ΩZC=(2+j)ΩZD=445°Ω

Calculation:

Substitute 215°Ω for ZA and 1Ω for ZB in Equation (5) as follows:

2000°V+I1(215°Ω)+(I1I2)(1Ω)=0200+I1(1.9318j0.5176)+(I1I2)=0(2.9318j0.5176)I1I2=200

I2=(2.9318j0.5176)I1200        (8)

Substitute 1Ω for ZB, (2+j)Ω for ZC, and 445°Ω for ZD in Equation (7) as follows:

(I2I1)(1Ω)+I2[(2+j)Ω]+I2(445°Ω)=0(I2I1)+I2(2+j)+I2(2.8284+j2.8284)=0I1+(5.8284+j3.8284)I2=0

From Equation (5), substitute [(2.9318j0.5176)I1200] for I2 as follows:

I1+(5.8284+j3.8284)[(2.9318j0.5176)I1200]=0I1+(19.0692+j8.2073)I1(1165.68+j765.68)=0

Simplify the expression as follows:

I1=(1165.68+j765.68)(18.0692+j8.2073)A=(69.4342+j10.8368)A=70.27478.87°A

Substitute (69.4342+j10.8368)A for I1 in Equation (8) to obtain the value of I2.

I2=(2.9318j0.5176)[(69.4342+j10.8368)A]200=(9.1763j4.1678)A=10.078424.43°A

Modify the expression in Equation (2) for the voltage across the load ZA.

VA=I1ZA

Substitute 70.27478.87°A for I1 and 215°Ω for ZA to obtain he voltage across . ZA

VA=(70.27478.87°A)(215°Ω)=140.54946.13°V

Modify the expression in Equation (1) for the complex power delivered to the load ZA as follows:

SA=VA(I1)*

Substitute 140.54946.13°V for VA and 70.27478.87°A for I1 to obtain the complex power delivered to the load ZA.

SA=(140.54946.13°V)(70.27478.87°A)*=(140.54946.13°V)(70.27478.87°A)=9877.066915°VA=9.877015°kVA

SA9.8715°kVA

Find the apparent power delivered to the load ZA as follows:

|SA|=|9.8715°kVA|=9.87kVA

Modify the expression in Equation (2) for the voltage across the load ZB.

VB=(I1I2)ZB

Substitute (69.4342+j10.8368)A for I1, (9.1763j4.1678)A for I2, and 1Ω for ZB

VB={[(69.4342+j10.8368)A][(9.1763j4.1678)A]}(1Ω)=(60.2579+j15.0046)(1)V=(60.2579+j15.0046)V=62.097913.98°V

Find the current through the load ZB as follows:

IB=(I1I2)

Substitute (69.4342+j10.8368)A for I1 and (9.1763j4.1678)A for I2 to obtain the current through the load ZB.

IB=[(69.4342+j10.8368)A][(9.1763j4.1678)A]=(60.2579+j15.0046)A=62.097913.98°A

Modify the expression in Equation (1) for the complex power delivered to the load ZB as follows:

SB=VB(IB)*

Substitute 62.097913.98°V for VB and 62.097913.98°A for IB to obtain the complex power delivered to the load ZB.

SB=(62.097913.98°V)(62.097913.98°A)*=(62.097913.98°V)(62.097913.98°A)=3856.14910°VA=3.85610°kVA

SB3.860°kVA

Find the apparent power delivered to the load ZB as follows:

|SB|=|3.860°kVA|=3.86kVA

Modify the expression in Equation (2) for the voltage across the load ZC.

VC=I2ZC

Substitute (9.1763j4.1678)A for I2 and (2+j)Ω for ZC to obtain he voltage across ZC.

VC=[(9.1763j4.1678)A][(2+j)Ω]=(22.5204+j0.8407)V=22.53602.14°V

Modify the expression in Equation (1) for the complex power delivered to the load ZC as follows:

SC=VC(I2)*

Substitute 22.53602.14°V for VC and 10.078424.43°A for I2 to obtain the complex power delivered to the load ZC.

SC=(22.53602.14°V)(10.078424.43°A)*=(22.53602.14°V)(10.078424.43°A)=227.126826.57°VA227.1326.57°VA

Find the apparent power delivered to the load ZC as follows:

|SC|=|227.1326.57°VA|=227.13VA

Modify the expression in Equation (2) for the voltage across the load ZD.

VD=I2ZD

Substitute 10.078424.43°A for I2 and 445°Ω for ZD to obtain he voltage across ZD.

VD=[10.078424.43°A][445°Ω]=40.313620.57°V

Modify the expression in Equation (1) for the complex power delivered to the load ZD as follows:

SD=VD(I2)*

Substitute 40.313620.57°V for VD and 10.078424.43°A for I2 to obtain the complex power delivered to the load ZD.

SD=(40.313620.57°V)(10.078424.43°A)*=(40.313620.57°V)(10.078424.43°A)=406.296545°VA406.345°VA

Find the apparent power delivered to the load ZD as follows:

|SD|=|406.345°VA|=406.3VA

Modify the expression in Equation (1) for the complex power supplied by the source as follows:

Ss=Vs(I1)*

Substitute 2000°V for Vs and 70.27478.87°A for I1 to obtain the complex power supplied by the source.

Ss=(2000°V)(70.27478.87°A)*=(2000°V)(70.27478.87°A)=14054.488.87°VA

Rewrite the expression for complex power supplied by the source in rectangular form as follows:

Ss=(11946.5528j7403.2616)VA

Compare the complex power supplied by the source with the expression in Equation (3) and write the average and reactive power supplied by the source as follows:

P=11946.5528WQ=7403.2616VAR

Substitute 11946.5528W for P and 7403.2616VAR for Q in Equation (4) to obtain the value of source power factor.

PF=cos[tan1(7403.2616VAR11946.5528W)]=cos(31.79°)=0.84990.85

If the imaginary part of the complex power (reactive power) is positive value, then the load has lagging power factor. If the imaginary part is negative value, then the load has leading power factor.

As the imaginary part of the given complex power is negative value, the power factor is leading power factor.

PF=0.85leading

Conclusion:

Thus, the apparent power delivered to ZA, ZB, ZC, ZD, and the source power factor are 9.87kVA_, 3.86kVA_, 227.13VA_, 406.3VA_, and 0.85 leading, respectively.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
2) The net inlet to a factory powered by a 2300 volt infinite busis measured as 765 A, for a lag 0.92 power factor. although mostloads is inductive, the input power factor has been improved by installing asynchronous capacitor operating at its nominal value of 1000 KVA. Determine the factor oforiginal factory power.
A 550-V feeder line supplies an industrial plant consisting of a motor drawing 60 kW at 0.75 pf (inductive), a capacitor with a rating of 20 kVAR, and lighting drawing 10 kW. (a) Calculate the total reactive power and apparent power absorbed by the plant. (b) Determine the overall pf. (c) Find the current in the feeder line.
Design a power factor correction circuit with the value of parallel capacitance needed tocorrect a load of 179 kVAR at 0.85 lagging pf to unity pf. Assume that the load issupplied by a 110-V (rms), 60-Hz line.

Chapter 11 Solutions

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf

Ch. 11 - Determine the power absorbed at t = 1.5 ms by each...Ch. 11 - Calculate the power absorbed at t = 0, t = 0+, and...Ch. 11 - Three elements are connected in parallel: a 1 k...Ch. 11 - Let is = 4u(t) A in the circuit of Fig. 11.28. (a)...Ch. 11 - Prob. 6ECh. 11 - Assuming no transients are present, calculate the...Ch. 11 - Prob. 8ECh. 11 - Prob. 9ECh. 11 - Prob. 10ECh. 11 - The phasor current I=915mA (corresponding to a...Ch. 11 - A phasor voltage V=10045V (the sinusoid operates...Ch. 11 - Prob. 13ECh. 11 - Prob. 14ECh. 11 - Find the average power for each element in the...Ch. 11 - (a) Calculate the average power absorbed by each...Ch. 11 - Prob. 17ECh. 11 - Prob. 18ECh. 11 - Prob. 19ECh. 11 - The circuit in Fig. 11.36 has a series resistance...Ch. 11 - Prob. 21ECh. 11 - Prob. 22ECh. 11 - Prob. 23ECh. 11 - Prob. 24ECh. 11 - Prob. 25ECh. 11 - Prob. 26ECh. 11 - Prob. 27ECh. 11 - Prob. 28ECh. 11 - Prob. 29ECh. 11 - Prob. 30ECh. 11 - Prob. 31ECh. 11 - Prob. 32ECh. 11 - Prob. 33ECh. 11 - (a) Calculate both the average and rms values of...Ch. 11 - Prob. 35ECh. 11 - FIGURE 11.43 Calculate the power factor of the...Ch. 11 - Prob. 37ECh. 11 - Prob. 38ECh. 11 - Prob. 40ECh. 11 - Prob. 41ECh. 11 - Prob. 42ECh. 11 - Prob. 43ECh. 11 - Compute the complex power S (in polar form) drawn...Ch. 11 - Calculate the apparent power, power factor, and...Ch. 11 - Prob. 46ECh. 11 - Prob. 48ECh. 11 - Prob. 49ECh. 11 - Prob. 50ECh. 11 - Prob. 51ECh. 11 - Prob. 52ECh. 11 - FIGURE 11.49 Instead of including a capacitor as...Ch. 11 - Prob. 54ECh. 11 - A load is drawing 10 A rms when connected to a...Ch. 11 - For the circuit of Fig. 11.50, assume the source...Ch. 11 - Prob. 57ECh. 11 - A source 45 sin 32t V is connected in series with...Ch. 11 - Prob. 60ECh. 11 - FIGURE 11.51 The circuit in Fig. 11.51 uses a Pi...Ch. 11 - Prob. 62ECh. 11 - Prob. 63ECh. 11 - You would like to maximize power transfer to a 50 ...
Knowledge Booster
Background pattern image
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:PEARSON
Text book image
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
Text book image
Programmable Logic Controllers
Electrical Engineering
ISBN:9780073373843
Author:Frank D. Petruzella
Publisher:McGraw-Hill Education
Text book image
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:9780078028229
Author:Charles K Alexander, Matthew Sadiku
Publisher:McGraw-Hill Education
Text book image
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:9780134746968
Author:James W. Nilsson, Susan Riedel
Publisher:PEARSON
Text book image
Engineering Electromagnetics
Electrical Engineering
ISBN:9780078028151
Author:Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:Mcgraw-hill Education,