(a)
Find the apparent power delivered to each load in the circuit in Figure 11.45 in the textbook and power factor of the source.
(a)
Answer to Problem 43E
The apparent power delivered to
Explanation of Solution
Given data:
Refer to Figure 11.45 in the textbook for the given circuit.
The impedance of the loads are given as follows:
Formula used:
Write the expression for complex power delivered to the load as follows:
Here,
Write the expression for voltage in terms of current and impedance as follows:
Write the expression for complex power in the rectangular form as follows:
Here,
Write the expression for power factor as follows:
Calculation:
Consider the current through the left-loop as
Apply KVL to the left-loop as follows:
Substitute
Apply KVL to the right-loop as follows:
Substitute
From Equation (6), substitute
Simplify the expression as follows:
Substitute
Modify the expression in Equation (2) for the voltage across the load
Substitute
Modify the expression in Equation (1) for the complex power delivered to the load
Substitute
Find the apparent power delivered to the load
Modify the expression in Equation (2) for the voltage across the load
Substitute
Find the current through the load
Substitute
Modify the expression in Equation (1) for the complex power delivered to the load
Substitute
Find the apparent power delivered to the load
Modify the expression in Equation (2) for the voltage across the load
Substitute
Modify the expression in Equation (1) for the complex power delivered to the load
Substitute
Find the apparent power delivered to the load
Modify the expression in Equation (2) for the voltage across the load
Substitute
Modify the expression in Equation (1) for the complex power delivered to the load
Substitute
Find the apparent power delivered to the load
Modify the expression in Equation (1) for the complex power supplied by the source as follows:
Substitute
Rewrite the expression for complex power supplied by the source in rectangular form as follows:
Compare the complex power supplied by the source with the expression in Equation (3) and write the average and reactive power supplied by the source as follows:
Substitute 4886.7899 W for
If the imaginary part of the complex power (reactive power) is positive value, then the load has lagging power factor. If the imaginary part is negative value, then the load has leading power factor.
As the imaginary part of the given complex power is negative value, the power factor is leading power factor.
Conclusion:
Thus, the apparent power delivered to
(b)
Find the apparent power delivered to each load in the circuit in Figure 11.45 in the textbook and power factor of the source.
(b)
Answer to Problem 43E
The apparent power delivered to
Explanation of Solution
Given data:
The impedance of the loads are given as follows:
Calculation:
Substitute
Substitute
From Equation (5), substitute
Simplify the expression as follows:
Substitute
Modify the expression in Equation (2) for the voltage across the load
Substitute
Modify the expression in Equation (1) for the complex power delivered to the load
Substitute
Find the apparent power delivered to the load
Modify the expression in Equation (2) for the voltage across the load
Substitute
Find the current through the load
Substitute
Modify the expression in Equation (1) for the complex power delivered to the load
Substitute
Find the apparent power delivered to the load
Modify the expression in Equation (2) for the voltage across the load
Substitute
Modify the expression in Equation (1) for the complex power delivered to the load
Substitute
Find the apparent power delivered to the load
Modify the expression in Equation (2) for the voltage across the load
Substitute
Modify the expression in Equation (1) for the complex power delivered to the load
Substitute
Find the apparent power delivered to the load
Modify the expression in Equation (1) for the complex power supplied by the source as follows:
Substitute
Rewrite the expression for complex power supplied by the source in rectangular form as follows:
Compare the complex power supplied by the source with the expression in Equation (3) and write the average and reactive power supplied by the source as follows:
Substitute
If the imaginary part of the complex power (reactive power) is positive value, then the load has lagging power factor. If the imaginary part is negative value, then the load has leading power factor.
As the imaginary part of the given complex power is negative value, the power factor is leading power factor.
Conclusion:
Thus, the apparent power delivered to
Want to see more full solutions like this?
Chapter 11 Solutions
Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf
- A 100KVA, 220V, a star-connected alternator is loaded at full load and at 60% pf lagging.The effective AC resistance per phase is 0.01411Ω. If the synchronous reactance is 4.5times the effect of the armature leakage reactance wherein the later is 0.046 Ω perphase, find(a) the phase voltage that would be generated at the load if the circuit were operating normally(b) What no-load open-circuit phase voltage must be present in order to circulate full-load current in short-circuit state while maintaining the same speed and field current?(c) What is the terminal phase voltage of the alternator when it is under a shorted load condition? Give an explanation in support of your response using just one sentence. The IA phasor should be used as the reference one.arrow_forwardAn investor own two large stores at Dubai. Both malls are connected in parallel and operating at an unknown voltage. The local utility system voltage is 13.8 kVrms and supplied power to the malls through a feeder line with impedance equal to 1+j2.5 ohms. Store 1 is consuming 400 kW at 0.8 pf lagging while Store 2 is consuming 300 kVAR at 0.75 pf lagging. Determine the following: a) The stores' operating rms voltages. b) The total real and reactive power of the ehole system. c) The overall pf of the whole system.arrow_forwardA Δ-connected, 60−Hz, balanced, 3ϕ, positive-sequence voltage source is connected to a Δ-connected, symmetric 3ϕ load via a non-ideal transmission line. The line-line voltage magnitude of the source is 480VRMS. The series impedance of each phase of the transmission line is 0.1+j1.5Ω. The impedance of each leg of the load is 3+j6Ω. a. What is the total, 3ϕ complex power consumed by the load. b. What are the total active power losses (all three phases) in the transmission line?arrow_forward
- The load on a 120-V, 60 Hz supply is 5KW (resistive), 8 KVAR (inductive), and 2 KVAR (capacitive). Find the following: a) total kilovolt-amperes, b)power factor of the combined loads, c) current drawn from the supply, d) capacitance needed to establish unity power factor, e) capacitive reactance needed to establish unity power factor, f) the current drawn from the supply at unity p.f.arrow_forwardA load of 500 kVA operates at 0.6 lagging power factor on 1100V, 50 Hz mains. The power factor of the system is improved from 0.6 lagging to 0.95 lagging by using a delta connected capacitor bank. Assuming VA of the load remains constant, indicate the rating of the capacitor and find the additional kW that can be obtained.arrow_forward. A power station has a connected load of 48 MW. The energy generated for the year is 61,500 MWh. If the station has a load factor of 35%, solve the demand factor of the station. Answer: 0.4179 or 41.79% Subject: Distribution System and Substation Designarrow_forward
- A three-phase system includes a 346.4 V line-to-line supplying a three-phase motor rated 15KVA 0.8pf lag plus additional balanced constant impedance loads. The single-phase representation of the system is shown below. Assume that sources and loads are Y-connected. 1. What is the RMS value of the line current, I in A? 2. If this set of loads will be supplied through a service transformer. What should the minimum size of the transformer in kVA? 3. What should be the size of three-phase capacitor(that will be added to the load mix) to improve power factor to almost 0.95 lag?arrow_forwardWhen connected to a 120 V (rms), 60-Hz power line, a load absorbs 4kW at a lagging power factor of 0.8. Find the value of Capacitance, C, necessary to raise the power factor to 0.95 lagging.arrow_forwardA load of 500 kVA operates at 0.6 lagging power factor on 1100 V, 50 Hz mains. The power factor of the system is improved from 0.6 lagging to 0.95 lagging by using a capacitor bank connected in delta. Assuming the KVA of the load remains constant, indicate the rating of the capacitor and find how much additional kW can be obtained.arrow_forward
- A 3-phase, 50 Hz, 440 V motor develops 100 H.P. (74·6 kW), which works for 3000 hours per annum, the power factor being 0·75 lagging and efficiency 93%. A bank of capacitors is connected in delta across the supply terminals and power factor raised to 0·95 lagging. The tariff is Rs 100 per kVA plus 20 paise per kWh. If the power factor is improved to 0·95 lagging by means of loss-free capacitors costing Rs 60 per kVAR, Compute the annual saving effected. Allow 12% per annum for interest and depreciation on capacitors.arrow_forwardSome parameters are given related to your student ID numbers. These are:V1 = XXX V (first 3 numbers, e.g. 170 V (RMS)) f1 = XXX Hz (assume that your last number is ‘y’, then f1 = (y+1)*10 Hz, e.g. if y=2 then f1=(2+1)*10=30Hz)1) A single-phase load has an active power of P = 2 kW at V1 V @f1Hz and the power factor is cosφ = 0.75. This motor iscompensated to cosφ = 0.85 using a parallel capacitor (the load is modelled as series RL). Determine:a. Reactive power and apparent power before compensation using power factorb. Current before compensationc. R, XL and L values of the loadd. Reactive power and apparent power after compensatione. Find the reactive power difference between compensated and uncompensated status (which will give thecapacitor power) and calculate XC and C using the power difference valuef. Simulate the uncompensated and compensated circuits. Plot voltage and current on components andcalculate the phase shift of the signals from Ving. Plot Vin and Iin comparison for…arrow_forwardA 400 V, 50 Hz, three-phase motor takes a line current of 15.0 A when operating at a lagging power factor of 0.65. When a capacitor bank is connected across the motor terminals, the line current is reduced to 11.5 A. Calculate the rating (in kVA) and the capa- citance per phase of the capacitor bank for: (a) star connection; (b) delta connection. Find also the new overall power factorarrow_forward
- Introductory Circuit Analysis (13th Edition)Electrical EngineeringISBN:9780133923605Author:Robert L. BoylestadPublisher:PEARSONDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningProgrammable Logic ControllersElectrical EngineeringISBN:9780073373843Author:Frank D. PetruzellaPublisher:McGraw-Hill Education
- Fundamentals of Electric CircuitsElectrical EngineeringISBN:9780078028229Author:Charles K Alexander, Matthew SadikuPublisher:McGraw-Hill EducationElectric Circuits. (11th Edition)Electrical EngineeringISBN:9780134746968Author:James W. Nilsson, Susan RiedelPublisher:PEARSONEngineering ElectromagneticsElectrical EngineeringISBN:9780078028151Author:Hayt, William H. (william Hart), Jr, BUCK, John A.Publisher:Mcgraw-hill Education,