Question
Chapter 3, Problem 3.40P
To determine
To draw:
Per unit equivalent circuit.
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
Three zones of a single-phase circuit are identified in the figure. The zones are connected by
transformers T₁ and T2, whose ratings are also shown. Using base values of 100 kVA and 240 volts in
zone 1, draw the per-unit circuit and determine the per-unit impedances and the per-unit source
voltage. Then calculate the load current both in per-unit and in amperes. Transformer winding
resistances and shunt admittance branches are neglected.
Zone 1
Zone 2
Vs = 220/0° volts
3---38
T,
30 KVA
240/480 volts
M 0.10 p.u.
Xoa
Xune = 2 fl
T
T₂
20 kVA
460/115 volts
Xeg = 0.10 p.u.
Zone 3
ww
Zload = 0.9 - 10.20
HOME WORK: Per-unit circuit: three-zone single-phase network
determine the per-unit impedances and the per-unit source voltage. Then cal-
culate the load current both in per-unit and in amperes. Transformer winding
resistances and shunt admittance branches are neglected.
Zone 1
Vs = 220/0° volts i
Three zones of a single-phase circuit are identified in Figure 3.10(a). The zones
are connected by transformers T₁ and T₂, whose ratings are also shown. Using
base values of 30 kVA and 240 volts in zone 1, draw the per-unit circuit and
T₁
30 kVA
240/480 volts
Xeq = 0.10 p.u.
V sp.u. =
0.9167/0° p.u.
Zoase
Zone 2
Xune 20
(a) Single-phase circuit
I'spu i Xtio.u
Zone 1
Vbase1 = 240 volts
(240)²
30,000
Spase = 30 kVA
= 1.92
T₂ Zload = 0.9 +0.2
20 KVA
460/115 volts
Xea = 0.10 p.u.
jXunepu
j0.10 p.u. j0.2604 p.u.
Zone 2
Vbase2 = 480 volts
Zbase2 =
Zone 3
(480)²
30,000
¡XT2pu hoadp.u.
= 7.68
(b) Per-unit circuit
/0.1378
p.u.
Zone 3
Vbase3= 120 volts
Zbase3 =
base3 =
Zoadp.u. =
1.875+ 0.4167 p.u.…
Three single-phase two-winding transformers, each rated 3 kVA, 220/110volts, 60 Hz, with a 0.10 per-unit leakage reactance, are connected as athree-phase extended D autotransformer bank, as shown in Figure 3.36 (c).The low-voltage D winding has a 110-volt rating. (a) Draw the positive sequencephasor diagram and show that the high-voltage winding has a479.5-volt rating. (b) A three-phase load connected to the low-voltageterminals absorbs 6 kW at 110 volts and at 0.8 power factor lagging. Drawthe per-unit impedance diagram and calculate the voltage and current atthe high-voltage terminals. Assume positive-sequence operation.
Chapter 3 Solutions
MindTap Engineering, 1 term (6 months) Printed Access Card for Glover/Overbye/Sarma's Power System Analysis and Design, 6th
Ch. 3 - The Ohms law for the magnetic circuit states that...Ch. 3 - For an ideal transformer, the efficiency is (a) 0...Ch. 3 - For an ideal 2-winding transformer, the...Ch. 3 - An ideal transformer has no real or reactive power...Ch. 3 - For an ideal 2-winding transformer, an impedance...Ch. 3 - Consider Figure 3.4. For an ideal phase-shifting...Ch. 3 - Consider Figure 3.5. Match the following, those on...Ch. 3 - The units of admittance, conductance, and...Ch. 3 - Match the following: (i) Hysteresis loss (a) Can...Ch. 3 - For large power transformers rated more than 500...
Ch. 3 - For a short-circuit test on a 2-winding...Ch. 3 - The per-unit quantity is always dimensionless. (a)...Ch. 3 - Consider the adopted per-unit system for the...Ch. 3 - The ideal transformer windings are eliminated from...Ch. 3 - To convert a per-unit impedance from old to new...Ch. 3 - In developing per-unit circuits of systems such as...Ch. 3 - Prob. 3.17MCQCh. 3 - Prob. 3.18MCQCh. 3 - With the American Standard notation, in either a...Ch. 3 - Prob. 3.20MCQCh. 3 - In order to avoid difficulties with third-harmonic...Ch. 3 - Does an open connection permit balanced...Ch. 3 - Does an open- operation, the kVA rating compared...Ch. 3 - It is stated that (i) balanced three-phase...Ch. 3 - In developing per-unit equivalent circuits for...Ch. 3 - In per-unit equivalent circuits of practical...Ch. 3 - Prob. 3.27MCQCh. 3 - Prob. 3.28MCQCh. 3 - For developing per-unit equivalent circuits of...Ch. 3 - Prob. 3.30MCQCh. 3 - Prob. 3.31MCQCh. 3 - Prob. 3.32MCQCh. 3 - The direct electrical connection of the windings...Ch. 3 - Consider Figure 3.25 of the text for a transformer...Ch. 3 - (a) An ideal single-phase two-winding transformer...Ch. 3 - An ideal transformer with N1=1000andN2=250 is...Ch. 3 - Consider an ideal transformer with...Ch. 3 - A single-phase 100-kVA,2400/240-volt,60-Hz...Ch. 3 - Prob. 3.5PCh. 3 - Prob. 3.6PCh. 3 - Consider a source of voltage v(t)=102sin(2t)V,...Ch. 3 - Prob. 3.8PCh. 3 - Prob. 3.9PCh. 3 - A single-phase step-down transformer is rated...Ch. 3 - For the transformer in Problem 3.10. The...Ch. 3 - Prob. 3.12PCh. 3 - A single-phase 50-kVA,2400/240-volt,60-Hz...Ch. 3 - A single-phase 50-kVA,2400/240-volt,60-Hz...Ch. 3 - Rework Problem 3.14 if the transformer is...Ch. 3 - A single-phase, 50-kVA,2400/240-V,60-Hz...Ch. 3 - The transformer of Problem 3.16 is supplying a...Ch. 3 - Using the transformer ratings as base quantities,...Ch. 3 - Using the transformer ratings as base quantities....Ch. 3 - Using base values of 20 kVA and 115 volts in zone...Ch. 3 - Prob. 3.21PCh. 3 - A balanced Y-connected voltage source with...Ch. 3 - Figure 3.32 shows the oneline diagram of a...Ch. 3 - For Problem 3.18, the motor operates at full load,...Ch. 3 - Consider a single-phase electric system shown in...Ch. 3 - A bank of three single-phase transformers, each...Ch. 3 - A three-phase transformer is rated...Ch. 3 - For the system shown in Figure 3.34. draw an...Ch. 3 - Consider three ideal single-phase transformers...Ch. 3 - Reconsider Problem 3.29. If Va,VbandVc are a...Ch. 3 - Prob. 3.31PCh. 3 - Determine the positive- and negative-sequence...Ch. 3 - Consider the three single-phase two-winding...Ch. 3 - Three single-phase, two-winding transformers, each...Ch. 3 - Consider a bank of this single-phase two-winding...Ch. 3 - Three single-phase two-winding transformers, each...Ch. 3 - Three single-phase two-winding transformers, each...Ch. 3 - Consider a three-phase generator rated...Ch. 3 - The leakage reactance of a three-phase,...Ch. 3 - Prob. 3.40PCh. 3 - Consider the single-line diagram of the power...Ch. 3 - For the power system in Problem 3.41, the...Ch. 3 - Three single-phase transformers, each rated...Ch. 3 - A 130-MVA,13.2-kV three-phase generator, which has...Ch. 3 - Figure 3.39 shows a oneline diagram of a system in...Ch. 3 - The motors M1andM2 of Problem 3.45 have inputs of...Ch. 3 - Consider the oneline diagram shown in Figure 3.40....Ch. 3 - With the same transformer banks as in Problem...Ch. 3 - Consider the single-Line diagram of a power system...Ch. 3 - A single-phase three-winding transformer has the...Ch. 3 - The ratings of a three-phase three-winding...Ch. 3 - Prob. 3.52PCh. 3 - The ratings of a three-phase, three-winding...Ch. 3 - An infinite bus, which is a constant voltage...Ch. 3 - A single-phase l0-kVA,2300/230-volt,60-Hz...Ch. 3 - Three single-phase two-winding transformers, each...Ch. 3 - A two-winding single-phase transformer rated...Ch. 3 - A single-phase two-winding transformer rated...Ch. 3 - Prob. 3.59PCh. 3 - PowerWorid Simulator case Problem 3_60 duplicates...Ch. 3 - Rework Example 3.12 for a+10 tap, providing a 10...Ch. 3 - A 23/230-kV step-up transformer feeds a...Ch. 3 - The per-unit equivalent circuit of two...Ch. 3 - Reconsider Problem 3.64 with the change that now...Ch. 3 - What are the advantages of correctly specifying a...Ch. 3 - Why is it important to reduce the moisture within...Ch. 3 - What should be the focus of transformer preventive...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- Equipment ratings for the five-bus power system shown in Figure 7.15 are as follows: Generator G1:    50 MVA, 12kV, X=0.2 per unit Generator G2: 100 MVA, 15 kV, X=0.2 per unit Transformer T1: 50 MVA, 10 kV Y/138kVY,X=0.10 per unit Transformer T2: 100 MVA, 15 kV /138kVY,X=0.10 per unit Each 138-kV line: X1=40 A three-phase short circuit occurs at bus 5, where the prefault voltage is 15 kV. Prefault load current is neglected. (a) Draw the positive-sequence reactance diagram in unit on a 100-MVA, 15-kV base in the zone of generator G2. Determine (b) the Thévenin equivalent at the fault, (c) the subtransient fault current in per unit and in kA rms, and (d) contributions to the fault from generator G2 and from transformer T2.arrow_forwardConsider three ideal single-phase transformers (with a voltage gain of ) put together as three-phase bank as shown in Figure 3.35. Assuming positive-sequence voltages for Va,Vb, and Vc find Va,Vb, and VC. in terms of Va,Vb, and Vc, respectively. (a) Would such relationships hold for the line voltages as well? (b) Looking into the current relationships, express IaIb and Ic in terms of IaIb and Ic respectively. (C) Let S and S be the per-phase complex power output and input. respectively. Find S in terms of S.arrow_forwardConsider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X1=0.24 (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio =N2/N1=10. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, Va as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.arrow_forward
- The per-unit equivalent circuit of two transformers Ta and Tb connected in parallel, with the same nominal voltage ratio and the same reactan of 0.1 per unit on the same base, is shown in Figure 3.43. Transformer Tb has a voltage-magnitude step-up toward the load of 1.05 times that of Ta (that is, the tap on the secondary winding of Tb is set to 1.05). The load is represented by 0.8+j0.6 per unit at a voltage V2=1.0/0 per unit. Determine the complex power in per unit transmitted to the load through each transformer, comment on how the transformers share the real and reactive powers.arrow_forwardThree zones of a single-phase circuit are identified shown in Figure below. The zones are connected by transformers T1 and T2, whose ratings are also shown. Using base values of 33 kVA and 232 volts in zone 1, Find: 1- Draw the per-unit circuit including the per-unit impedances and the per-unit source voltage. 2- Calculate the load current both in per-unit and in amperes (actual or original value). Vs Zone 1 232.940° Vs G. 38 T₁ 30 KVA 240/480 volts Xeq = 0.10 p.u. Zone 2 Xiine = 4 Ω T₂ 20 KVA 460/115 volts Zload = Xea = 0.10 p.u. Zone 3 u 1+j2.2 Ω 2arrow_forwardQ5 The single-line diagram of a three-phase power system is shown in Figure Q5a, with equipment ratings given in Table Q5a. (a) (b) G₁ G₂ G3 G4 T₁ T₂ T3 TA Draw the zero, positive and negative-sequence reactance diagrams using 1000 MVA, 765 kV base in the zone of Line 1-2, neglect the (A-Y) transformer phase shifts. Calculate the short circuit current as a result of three-phase bolted fault occurred at bus 1. Line 1-2 Line 1-3 Line 2-3 bus 1 0 Υ ΔΥ Line 1-3 Line 1-2 G₂ Line 2-3 bus 2 Da Figure 05a bus 3 Table Q5a T₂ KEY YE my 1000 MVA, 15 kV, X₁-X₂-0.18 p.u., Xo = 0.07, p.u. 1000 MVA, 15 kV, X₁-X₂-0.20 p.u., Xo = 0.10, p.u. 500 MVA, 13.8 kV, X₁-X₂-0.15 p.u., Xo = 0.05, p.u. X₂ = 0.05 p.u. 750 MVA, 13.8 kV, X₁-0.3 p.u., X₂-0.4 p.u., Xo = 0.1, p.u. 1000 MVA, 15 kV (A) / 765 kV (Y), XTI = 0.10 p.u. 1000 MVA, 15 kV (A)/ 765 kV (Y), XT2 = 0.10 p.u. 500MVA, 15 kV (Y) / 765 kV (Y), XT3 = 0.12 p.u. 750 MVA, 15 kV (Y)/765 kV (Y), XT4 = 0.11 p.u. Χ = 50 Ω, X = 150 Ω. Χ = 40 Ω, Χρ = 100 Ω. Χρ= 40…arrow_forward
- EXAMPLE 3.4 Per-unit circuit: three-zone single-phase network Three zones of a single-phase circuit are identified in Figure 3.10(a). The zones are connected by transformers T, and T, whose ratings are also shown. Using base values of 30 kVA and 240 volts in zone 1, draw the per-unit circuit and de- termine the per-unit impedances and the per-unit source voltage. Then calculate the load current both in per-unit and in amperes. Transformer winding resistances and shunt admittance branches are neglected. FIGURE 3.10 Zone 1 Zone 2 Zone 3 Circuit for Example 3.4 V, = 220/0° voits muw T, Zload = 0.9 + j0.2 N Xiine = 2 1 30 kVA 20 kVA 240/480 volts 460/115 volts Xeg = 0.10 p.u. Xea = 0.10 p.u. (a) Single-phase circuit loou XT1p.u. jXinep.u. įXT2p.u. loadp.u. |j0.1378 i p.u. j0.10 p.u. j0.2604 p.u. Zioadp.u. = 1.875 + j0.4167 p.u. 0.9167/0° p.u. Zone 1 Zone 2 Zone 3 Voase = 240 volts Vosse2 = 480 voits Voase3 = 120 volts Zoase (240)2 30,000 = 1.92 N Zbase2 (480)2 30.000 - 7.68 Ω Zas3 (120)2…arrow_forwardDerive an expression of per unit impedance of a given base MVA and base KV in term of new base MVA and new base KVAarrow_forwardThree zones of a single-phase circuit are identified in Figure. The zones are connected bytransformers T1 and T2, whose ratings are also shown.Using base values of 30 kVA and 240 volts in zone 1:a. draw the per-unit circuit and determine the per-unit impedances and the per-unitsource voltage.b. calculate the load current both in per-unit and in amperes. Transformer windingresistances and shunt admittance branches are neglected.arrow_forward
- Q2) In the network in the figure below Y-Y connected transformers, each with grounded neutrals, are at the ends of each transmission line that is not terminating at bus 3. The transformers connecting the lines to bus 3 are Y-A, with the neutral of the Y solidly grounded and the A sides connected to bus 3. All the line reactances shown in the figure between busses include the reactances of the transformers. Zero sequence values for these lines including transformers are 2.0 times those shown in the figure. Both generators are Y-Connected. Zero-sequence reactances of the generators connected to bus 1 and bus 3 are 0.04 and 0.08 per unit, respectively. The neutral of the generator at bus 1 is connected to ground through a reactor of 0.02 per unit; the generator at bus 3 has a solidly ground neutral. Find the bus impedance matrices (¹), (²), z for the given network and 'bus' 'bus' bus then compute the Subtransient current in per unit for a single line-to-ground fault on bus 2 and the fault…arrow_forwardplease solve for nodal stress method. (if it is possible to apply supernodes)arrow_forwardwhat is the definition of zero sequence impedance in a transformers? And what is the benefit of this check in transformers?arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Routh Hurwitz Stability Criterion Basic Worked Example; Author: The Complete Guide to Everything;https://www.youtube.com/watch?v=CzzsR5FT-8U;License: Standard Youtube License