Determine the new per unit value of the generator impedance base from the given bases. Generator G: 15 MVA, 13.8 kV, X = 0.15 p.u. Motor M1: 5 MVA, 13.8 kV, X = 0.15 p.u. Motor M2: 5 MVA, 14.4 kV, X = 0.15 p.u. T;: 25 MVA, 13.2 – 161 kV, X = 0.1 p.u. T;:15 MVA, 13.8 –. 161 kV, X = 0.1 p.u. Line: j100 N (actual) Select a base of 100 MVA and 161 kV in the transmission line. T T2 Line pu 1.09 pu 0.15 pu 0.91 pu
Q: A 70-kV, three-phase short .Determine t
A: It is given that: V= 70 kVL=18 KmZphase=1+j5 ΩPR3-ϕ=90 MW
Q: Q1/ Equipment ratings for the four-bus power system shown in Figure are as follows: Generator G1:…
A:
Q: Consider a 220-kV transmission system shown in Figure Q2. The per phase the impedances of the lines…
A: Given V=220 kV Z01=2+j 20 Ω Z02 =2.5 +j 25 Ω P=100 MVA
Q: For the power system shown at right the impedance matrix (2 is j0.4 3 j0.5 j0.2 0.164 0.101 0.0692…
A:
Q: A three-phase fault with a fault impedance Zf = j0.16 per unit occurs at bus 3 in the Figure beside,…
A: The answer is 2. Please fill answer only 2.
Q: QUESTION 1 Figure Q1 shows a single-line diagram of an 8-bus system. Line-1 and Line-2 have…
A: Part (c): Consider the base MVA is 50 MVA and base kVA is 22 kV. The base impedance is determined…
Q: Generators generate positive sequence voltage only False True
A: Positive Sequence: The positive sequence is a three-phase balanced system in which the system has…
Q: Refer to Figure 1. Using its equivalent reactance diagram, what is the total impedance of the system…
A:
Q: Three single-phase two-winding transformers,
A:
Q: Derive an expression of per unit impedance of a given base MVA and base KV in term of new base MVA…
A: To derive the expression of per unit impedance at a given base MVA and base KV in term of new base…
Q: The one-line diagram of an unloaded power system is shown below. T | 1000 T Reactances of the two…
A:
Q: Obtain the per-unit equivalent circuit for the following one-line diagram in Figure 1. Xine = 100 Q…
A:
Q: Hourly variation factor need to consider while dealing with the non-coincidence demand of different…
A: A power station is to provide electricity to a huge number of people. Different customers' power…
Q: 4. A two-bus power system bus admittance matrix is bus -j9 j3 j3 -j8 53] P per unit. Suppose…
A: Note: We are authorized to answer three subparts at a time since you have not mentioned which part…
Q: a) The one line diagram of a three phase system is shown below, draw an impedance diagram showing…
A: (a) The new value of per unit impedance is given by the below formula, Znew=ZoldSnewSold----(1) The…
Q: Problem 2.. Determine the 3×3 bus admittance matrix Yous for the 3-bus circuit in the figure below.…
A: Given circuit diagram, YBUS =?
Q: A DC Optimal Power Flow problem is to be solved for a 3-bus network. The per-unit reactances of the…
A: The per-unit reactances of the lines A 3-BUS network interconnecting the buses are…
Q: The 13.2 kV 50-Hz generator feeds a load over a line with (Zload) impedance Zline. Load is 80on +…
A: Given: A 13.2 kV, 50 Hz single-phase generator supplies power to a load through a transmission line.…
Q: The single-line diagram of a three-phase system is given in Figure 3. The three-phase generator is…
A: Given: The ratings of each element are as follows: Generator-4.16 MVA, 2.4 kV, 1000 A.Transformer…
Q: Q4 / Equipment ratings for the four - bus power system shown in Figure are given as follows: TI 73…
A: Solution Consider the following schematic single line diagram: Figure 1 Consider the following…
Q: Draw the reactance diagram, with all reactance's marked in per-unit. Select the 100 MVA and 25kV as…
A: In this question we need to draw a reactance diagram of the given single line diagram.
Q: Q1. The following figure shows the differential protection of power transformers with specifications…
A:
Q: A single line diagram of a small power system is shown below. The corresponding reactances…
A:
Q: 2. A 3-phase, 75 MVA, 11-8 kV star-connected alternator with a solidly earthed neutral point has th…
A: As per Bartleby guidelines we are allowed to solve only one question,please ask the rest again.
Q: The one-line diagram of a power system is shown in the figure below. A single-line-to- ground (SLG)…
A: A single line to ground fault occurs at bus 2. So the fault current will be- Ea=Genetaror terminal…
Q: Consider the same 4-bus system shown. Use the tie set method to determine the reliability,…
A:
Q: Determine the per unit impedance of a transmission line having an impedance of 30 + j110 Ω on 100…
A:
Q: The base current and base voltage of a 345 kV system are chosen to be 3000A and 300kV respectively.…
A: The solution is given below
Q: 6.32 For a two-bus power system, a 0.7 + j0.4 per unit load at bus 2 is supplied by a generator at…
A:
Q: The voltage regulation of a shunt transmission line will be maximum when the value of tan ÖR, for…
A: The voltage regulation formula is, V.R.=IRcosϕR±IXsinϕRV2×100 (+) for lagging (-) for leading
Q: a) Draw impedance diagram in per unit, by using 100-MVA base. Select 20kV as the base voltage for…
A: You have asked multiple independent questions. We are authorized to answer one question at a time.…
Q: A private developer proposes to install a synchronous type generating plant connected to the local…
A: Answer(1) According to the given data The generator produces 14 MW at 11 kV So, during the peak…
Q: A single-line diagram of a four-bus system is shown in fiugre. Equipment ratings and per-unit…
A: Given: A single-line diagram of a four-bus system is shown below: Machines 1 and 2: 100 MVA 20 kV;…
Q: 3 Referring to a 3-phase power system as shown, a short circuit fault occurs at point F. The…
A:
Q: The base current and base voltage of a 345-kV system are chosen to be 3000 A and 300 kV,…
A: Given: Base current =3000 A Base Voltage=300 KV Actual value =345 KV
Q: Figure 6.12 shows the one-line diagram of a simple three-bus power system with generators at buses 1…
A:
Q: A three-phase fault with a fault impedance Zf = jo.16 per unit occurs at bus 3 in the Figure beside,…
A: The solution is given below
Q: B) Develop an expression, in terms of the generated e.m.f. and the sequence impedances (ZI, Z2 and…
A: According to the question we have, Develop an expression, in terms of the generated e.m.f. and the…
Q: The zero sequence currents of a generator for line to ground fault is j2.4 p.u. then the current…
A:
Q: Q2\ Calculate the fault current for the given system if symmetrical three-phase fault occurs at…
A:
Q: Figure 3 shows the one-line diagram of a three-bus power system with generation at bus X. The…
A:
Q: QI/A: The per unit admittances are indicated at the diagram and the bus data are given in table as…
A: YBUS=Y11Y12Y13Y21Y22Y23Y31Y32Y33where,Y11=y12+y13Y12=Y21=-y12Y13=Y31=-y13Y22=y12+y23Y23=Y32=-y23Y33=…
Q: The bus impedance matrix for a three-bus power system has per-unit elements as: Z11 = 0.5 Z12 = 0.4…
A: In this question we need to find a subtransient fault current when a 3 phase fault occur at bus 3.
Q: Draw the reactance diagram of the given one-line diagram below marked in appropriate per unit…
A:
Q: Refer to the 5-bus data given below. Sbase = 400 MVA, the base voltage is 15.0 kV for buses 1 and 3,…
A: a) Single line diagram of given power system here series parameter are in impedance and shunt…
Q: A three-bus power system has generators at buses 1 and 2 with per unit subtransient reac- cances…
A: “Since you have asked multiple question, we will solve the first question for you. If you want any…
Q: 6. For a three bus power system assume bus 1 is the swing with a per unit voltage of 1.020 , bus 2…
A: Given data, Per unit voltage=1.0∠0 Per unit load=2.0+j0.5
Q: Calculate the per unit voltage drop on the transmission line e) Calculate also the sending end…
A:
Q: a) The one line diagram of a three phase system is shown below, draw an impedance diagram showing…
A: It is given that:
asap please
Step by step
Solved in 2 steps with 1 images
- Equipment ratings for the five-bus power system shown in Figure 7.15 are as follows: Generator G1:    50 MVA, 12kV, X=0.2 per unit Generator G2: 100 MVA, 15 kV, X=0.2 per unit Transformer T1: 50 MVA, 10 kV Y/138kVY,X=0.10 per unit Transformer T2: 100 MVA, 15 kV /138kVY,X=0.10 per unit Each 138-kV line: X1=40 A three-phase short circuit occurs at bus 5, where the prefault voltage is 15 kV. Prefault load current is neglected. (a) Draw the positive-sequence reactance diagram in unit on a 100-MVA, 15-kV base in the zone of generator G2. Determine (b) the Thévenin equivalent at the fault, (c) the subtransient fault current in per unit and in kA rms, and (d) contributions to the fault from generator G2 and from transformer T2.With the same transformer banks as in Problem 3.47, Figure 3.41 shows the oneline diagram of a generator, a step-up transformer bank, a transmission line, a stepown transformer bank, and an impedan load. The generator terminal voltage is 15 kV (line-to-line). (a) Draw the per-phase equivalent circuit, aounting for phase shifts for positive-sequence operation. (b) By choosing the line-to-neutral generator terminal voltage as the reference, determine the magnitudes of the generator current, transmiss ion-line current, load current, and line-to-line load voltage. Also, find the three-phase complex power delivered to the load.Figure 3.39 shows a oneline diagram of a system in which the three-phase generator is rated 300 MVA, 20 kV with a subtransient reactance of 0.2 per unit and with its neutral grounded through a 0.4- reactor. The transmission line is 64km long with a cries reactance of 0.5-/km. The three-phase transformer T1 is rated 350MVA.230/20kV with a leakage reactance of 0.1 per unit. Transformer T2 is composed of three single-phase transformers, each rated 100 MVA, 127/13.2kV with a leakage reactance of 0.1 per unit. Two 13.2kV motors M1 and M2 with a subtransient reactance of 0.2 per unit for each motor represent the load. M1 has a rated input of 200 MVA with its neutral grounded through a 0.4- current-limiting reactor, M2 has a rated input of 100 MVA with its neutral not connected to ground. Neglect phase shifts associated with the transformers. Choose the generator rating as base in the generator circuit and draw the positive-sequence reactance diagram showing all reactances in per unit.
- PowerWorid Simulator case Problem 3_60 duplicates Example 3.13 except that a resistance term of 0.06 per unit has been added to the transformer and 0.05 per unit to the transmission line. Since the system is no longer lossless, a field showing the real power losses has also been added to the oneline. With the LTC tap fixed at 1.05, plot the real power losses as the phase shift angle is varied from 10 to +10 degrees. What value of phase shift minimizes the system losses?Determine the bus admittance matrix (Ybus) for the three-phase power system shown in Figure 6.23 with input data given in Table 6.11 and partial results in Table 6.12. Assume a three-phase 100 MVA per unit base. TABLE 6.11 Bus input data for Problem 6.20 TABLE 6.12 Partially Completed Bus Admittance Matrix (Ybus) for Problem 6.30Consider the single-Line diagram of a power system shown in Figure 3.42 with equipment ratings given: Generator G1: 50MVA,13.2kV,x=0.15p.u. Generator G2: 20MVA,13.8kV,x=0.15p.u. Three-phase -Y transformer T1: 80MVA,13.2/165YkV,X=0.1p.u. Three-phase Y- transformer T2: 40MVA,165Y/13.8kV,X=0.1p.u. Load: 40MVA,0.8PFlagging,operatingat150kV Choose a base of 100 MVA for the system and 132-kV base in the transmission-line circuit. Let the load be modeled as a parallel combination of resistance and inductance. Neglect transformer phase shifts. Draw a per-phase equivalent circuit of the system showing all impedances in per unit.
- Three single-phase two-winding transformers, each rated 25MVA,34.5/13.8kV, are connected to form a three-phase bank. Balanced positive-suence voltages are applied to the high-voltage terminals, and a balanced, resistive Y load connected to the low-voltage terminals absorbs 75 MW at 13.8 kV. If one of the single-phase transformers is removed (resulting in an open connection) and the balanced load is simultaneously reduced to 43.3 MW (57.7 of the original value), determine (a) the load voltages Va,Vb, and Vc; (b) load currents Ia,Ib, and Ic; and (c) the MVA supplied by each of the remaining two transformers. Are balanced voltages still applied to the load? Is the open transformer overloaded?The motors M1andM2 of Problem 3.45 have inputs of 120 and 60 MW, respectively, at 13.2 kV, and both operate at unity power factor. Determine the generator terminal voltage and voltage regulation of the line. Neglect transformer phase shifts.Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X1=0.24 (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio =N2/N1=10. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, Va as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.
- Consider the single-line diagram of the power system shown in Figure 3.38. Equipment ratings are Generator 1: 1000MVA,18kV,X=0.2perunit Generator 2: 1000MVA,18kV,X=0.2p.u. Synchronous motor 3: 1500MVA,20kV,X=0.2p.u. Three-phase -Y transformers T1,T2,T3,T4,: 1000MVA,500kV,Y/20kV,X=0.1p.u. Three-phase YY transformer T5: 1500MVA,500kV,Y/20kVY,X=0.1p.u. Neglecting resistance, transformer phase shift, and magnetizing reactance, draw the equivalent reactance diagram. Use a base of 100 MA and 500 kV for the 50-ohm line. Determine the per-unit reactances.Consider a single-phase electric system shown in Figure 3.33. Transformers are rated as follows: XY15MVA,13.8/138kV, leakage reactance 10 YZ15MVA,138/69kV, leakage reactance 8 With the base in circuit Y chosen as 15MVA,138kV determine the per-unit impedance of the 500 resistive load in circuit Z, referred to circuits Z, Y, and X. Neglecting magnetizing currents, transformer resistances, and line impedances, draw the impedance diagram in per unit.For the power system in Problem 3.41, the synchronous motor absorbs 1500 MW at 0.8 power factor leading with the bus 3 voltage at 18 kV. Determine the bus I and bus 2 voltages in kV Assume that generators I and 2 deliver equal real powers and equal reactive powers. Also assume a balanced three-phase system with positive-sequence sources.