Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf
Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf
9th Edition
ISBN: 9781259989452
Author: Hayt
Publisher: Mcgraw Hill Publishers
bartleby

Concept explainers

bartleby

Videos

Textbook Question
Book Icon
Chapter 12, Problem 18E

Repeat Exercise 17 with Rw = 10 Ω, and verify your answers with an appropriate set of simulations if the operating frequency is 60 Hz.

Assume the system shown in Fig. 12.34 is balanced, Rw = 0, Van = 208∠0° V, and a positive phase sequence applies. Calculate all phase and line currents, and all phase and line voltages, if Zp is equal to (a) 1 kΩ; (b) 100 + j48 Ω; (c) 100 − j48 Ω.

Chapter 12, Problem 18E, Repeat Exercise 17 with Rw = 10 , and verify your answers with an appropriate set of simulations if

■ FIGURE 12.34

(a)

Expert Solution
Check Mark
To determine

Find the line and phase currents, line and phase voltages at the load when the load impedance Zp=1kΩ in the Figure 12.34 using LTSpice.

Answer to Problem 18E

The line and phase currents are IaA=0.2060° A,IbB=0.206120° A_, and, IcC=0.206120° A_. The phase voltages are VAN=2060° V,VBN=206120° V_, and VCN=206120° V_, and the line voltages are VAB=356.830° V,VBC=356.890° V_, and VCA=356.8210° V_.

Explanation of Solution

Given data:

The line resistance Rw=10Ω.

The load impedance Zp=1 kΩ.

The source phase voltage is Van=2080° V.

The simulation operation frequency is 60 Hz.

LTspice Simulation:

Draw the given circuit diagram as shown in Figure 1, where 1, 2, and 3 are placed for node representations using Label Net.

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf, Chapter 12, Problem 18E , additional homework tip  1

Set the values of voltages Van, Vbn and Vcn by right clicking on the voltage component, select none in “Functions” and enter the Small signal AC analysis parameters: AC amplitude as 208 and AC phase as 0 for V1, and enter other two voltage values accordingly positive phase sequence as shown in Figure 2 for V1.

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf, Chapter 12, Problem 18E , additional homework tip  2

Now save the circuit, and open the “Edit Simulation command” choose AC analysis and select the sweep type as Decade, Number of points per decade 1, Start frequency and Stop frequency as 60 Hz shown in Figure 3.

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf, Chapter 12, Problem 18E , additional homework tip  3

Now, run the simulation for the designed circuit. The output for the AC analysis will displays as shown in Figure 4.

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf, Chapter 12, Problem 18E , additional homework tip  4

For the wye-wye connection, phase currents and line currents are equal and they are equals to IaA,IbB and IcC respectively. From above simulation results I(R1) or I(Z1) is equals to IaA, I(R2) or I(Z2) is equals to IbB, I(R3) or I(Z3) is equals to IcC.

Then,

IaA=0.2059410° A0.2060° AIbB=0.205941120° A0.206120° AIcC=0.205941120° A0.206120° A

In above simulation results, the phase voltages at the load VAN,VBN  and VCN are represented by V(1), V(2) and V(3).

Then, the phase voltages at the load are,

VAN=205.9410° V2060° VVBN=205.941120° V206120° VVCN=205.941120° V206120° V

The magnitude of the phase voltages is Vp=206 V.

Write the formula to find the line voltage VAB as follows.

VAB=3Vp30° V

Substitute 206 V for Vp.

VAB=3(2060°)30° VVAB=356.830° V

Write the formula to find the line voltage VBC as follows.

VBC=3Vp90° V

Substitute 206 V for Vp.

VBC=3(206)90° VVBC=356.890° V

Write the formula to find the line voltage VCA as follows.

VCA=3Vp210° V

Substitute 206 V for Vp.

VCA=3(206)210° VVCA=356.8210° V

Conclusion:

Thus, the line and phase currents are IaA=0.2060° A,IbB=0.206120° A_, and, IcC=0.206120° A_. The phase voltages are VAN=2060° V,VBN=206120° V_, and VCN=206120° V_, and the line voltages are VAB=356.830° V,VBC=356.890° V_, and VCA=356.8210° V.

(b)

Expert Solution
Check Mark
To determine

Find the line and phase currents, line and phase voltages at the load when the load impedance Zp=100+j48Ω in the Figure 12.34 using LTSpice.

Answer to Problem 18E

The line and phase currents are IaA=1.73323.6° A,IbB=1.733143.6° A_, and, IcC=1.733263.6° A_.

The phase voltages are VAN=192.242.06° V,VBN=192.24117.93° V_, and VCN=192.24237.93° V_, and the line voltages are VAB=332.9632.06° V_, VBC=332.9687.93° V and VCA=332.96207.93° V_.

Explanation of Solution

Given data:

Refer to part (a).

LTspice Simulation:

The load impedance is given as,

Zp=100+j48 Ω

Where load resistance is Rp=100Ω, and the inductive reactance is XP=j48Ω.

Write the formula to find the inductive reactance as follows.

Xp=jωLXp=j2πfL

Substitute j48Ω for Xp, 60 Hz for f.

j48Ω=j2π(60 Hz)LL=482π(60)ΩHzL=0.12732 H                   {ΩHz= H} 

Draw the given circuit diagram as shown in Figure 5 for the load impedance Zp=100+j48 Ω.

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf, Chapter 12, Problem 18E , additional homework tip  5

Keep the same simulation settings as given in Part(a) and run the simulation, then the output for the AC analysis will displays as shown in Figure 6.

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf, Chapter 12, Problem 18E , additional homework tip  6

From above simulation results I(R1) or I(R4) or I(L1) is equals to IaA, I(R2) or I(R5) or I(L2) is equals to IbB, I(R3) or I(R6) or I(L3) is equals to IcC.

Then,

IaA=1.7330923.5739° A1.73323.6° AIbB=1.73309143.574° A1.733143.6° AIcC=1.7330996.4261° A or=1.733263.5739° A1.733263.6° A

The phase voltages at the load VAN,VBN  and VCN are represented by V(1), V(2) and V(3).

Then, the phase voltages at the load are,

VAN=192.242.06623° V192.242.06° VVBN=192.24117.934° V192.24117.93° VVCN=192.24122.066° V or=192.24237.934° V192.24237.93° V

The magnitude of the phase voltages is Vp=192.24 V.

Write the formula to find the line voltage VAB as follows.

VAB=3VAN30° V        (1)

Substitute 192.242.06° V for Vp.

VAB=3(192.242.06° V)30° VVAB=332.9632.06° V

Write the formula to find the line voltage VBC as follows.

VBC=3VBN30° V        (2)

Substitute 192.24117.93° V for VBN.

VBC=3(192.24117.93° V)30° VVBC=332.9687.93° V

Write the formula to find the line voltage VCA as follows.

VCA=3VCN30° V        (3)

Substitute 192.24237.93° V for VCN.

VCA=3(192.24237.93° V)30° VVCA=332.96207.93° V

Conclusion:

Thus, the line and phase currents are IaA=1.73323.6° A,IbB=1.733143.6° A_, and, IcC=1.733263.6° A_.

The phase voltages are VAN=192.242.06° V,VBN=192.24117.93° V_, and VCN=192.24237.93° V_, and the line voltages are VAB=332.9632.06° V_, VBC=332.9687.93° V and VCA=332.96207.93° V_.

(c)

Expert Solution
Check Mark
To determine

Find the line and phase currents, line and phase voltages at the load when the load impedance Zp=100j48Ω in the Figure 12.34 using LTspice.

Answer to Problem 18E

The line and phase currents are IaA=1.73323.6° A,IbB=1.73396.4° A_, and, IcC=1.733216.4° A_.

The phase voltages are VAN=192.242.06° V,VBN=192.24122.06° V_, and VCN=192.24242.06° V_, and the line voltages are VAB=332.9627.94° V_, VBC=332.9692.06° V_ and VCA=332.96212.06° V_.

Explanation of Solution

Given data:

Refer to part (a).

LTspice Simulation:

The load impedance is given as,

Zp=100j48 Ω

Where load resistance is Rp=100Ω, and the capacitive reactance is XP=j48Ω.

Write the formula to find the inductive reactance as follows.

Xp=1jωCXp=1j2πfC

Substitute j48Ω for Xp, 60 Hz for f.

j48Ω=1j2π(60 Hz)CC=12π(60)481ΩHzC=0.00005526 F                   {1ΩHz= F} 

Draw the given circuit diagram as shown in Figure 5 for the load impedance Zp=100j48 Ω.

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf, Chapter 12, Problem 18E , additional homework tip  7

Keep the same simulation settings as given in part(a) and run the simulation, then the output for the AC analysis will displays as shown in Figure 8.

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf, Chapter 12, Problem 18E , additional homework tip  8

From above simulation results, since the phase currents and line currents are equal, I(R1) or I(R4) or I(C1) is equals to IaA, I(R2) or I(R5) or I(C2) is equals to IbB, I(R3) or I(R6) or I(C3) is equals to IcC.

Then,

IaA=1.7330823.5755° A1.73323.6° AIbB=1.7330896.4245° A1.73396.4° AIcC=1.73308143.576° A or=1.733216.424° A1.733216.4° A

The phase voltages at the load VAN,VBN  and VCN are represented by V(1), V(2) and V(3).

Then, the phase voltages at the load are,

VAN=192.2412.06635° V192.242.06° VVBN=192.241122.066° V192.24122.06° VVCN=192.241117.934° V or=192.24242.066° V192.24242.06° V

Use the same formula given in equation (1) to find the line voltage VAB, and substitute 192.242.06° V for VAN in equation (1).

VAB=3(192.242.06° V)30° VVAB=332.9627.94° V

Use the same formula given in equation (2) to find the line voltage VBC, and substitute 192.24122.06° V for VBN in equation (2).

VBC=3(192.24122.06° V)30° VVBC=332.9692.06° V

Use the same formula given in equation (3) to find the line voltage VCA and substitute 192.24242.06° V for VCN in equation (3).

VCA=3(192.24242.06° V)30° VVCA=332.96212.06° V

Conclusion:

Thus, the line and phase currents are IaA=1.73323.6° A,IbB=1.73396.4° A_, and, IcC=1.733216.4° A_.

The phase voltages are VAN=192.242.06° V,VBN=192.24122.06° V_, and VCN=192.24242.06° V_, and the line voltages are VAB=332.9627.94° V_, VBC=332.9692.06° V_ and VCA=332.96212.06° V_.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
A 530 kV, three phase transmission line with a 350 km length. The series impedance Z =(0.11+j0.72) Ω/ph/km and shunt admittance y = (j73 x e(-7)) S/ph/km. Evaluate the equivalent π-model and T-model parameters.
A 3-phase, 50-Hz overhead transmission line 100 km long has the following constants : Resistance/km/phase = 0.1 Ω Inductive reactance/km/phase = 0·2 Ω Capacitive susceptance/km/phase = 0·04 × 10− 4 siemens Determine sending end voltage when supplying a balanced load of 10,000 kW at 66 kV, p.f. 0·8 lagging. Use nominal T method .   Select one: a. 330 kV b. 52 kV c. None of the above d. 69.5 kV
A short 3-phase transmission line connected to a 33kV, 50 Hz generating station at the sending end is required to supply a load of 10 MW at 0·8 lagging power factor at 30 kV at the receiving end. If the minimum transmission efficiency is to be limited to 96%, estimate the per phase value of resistance and inductance of the line.  [2·4 Ω; 0·028 H]

Chapter 12 Solutions

Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf

Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:PEARSON
Text book image
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
Text book image
Programmable Logic Controllers
Electrical Engineering
ISBN:9780073373843
Author:Frank D. Petruzella
Publisher:McGraw-Hill Education
Text book image
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:9780078028229
Author:Charles K Alexander, Matthew Sadiku
Publisher:McGraw-Hill Education
Text book image
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:9780134746968
Author:James W. Nilsson, Susan Riedel
Publisher:PEARSON
Text book image
Engineering Electromagnetics
Electrical Engineering
ISBN:9780078028151
Author:Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:Mcgraw-hill Education,
How do Electric Transmission Lines Work?; Author: Practical Engineering;https://www.youtube.com/watch?v=qjY31x0m3d8;License: Standard Youtube License